ALEAN AN-T60F Photoelectric Dual Beam Detector User Manual
- June 2, 2024
- ALEAN
Table of Contents
Photoelectric Dual Beam Detector
User Manual_pso7-sMo04-1.4
Features
- Interruption time adjustable
- Digital filtering,high environment adaptability to eliminate false alarms
- CPU control transmitter and receiver to eliminate false alarms
- Wide voltage design of DC9~30V/AC9~20V
- NO/NC relay outputs
- Tamper alarm function(NC,alarm when cover was removed)
- 4 frequencies selectable for long distance and stacking installations
Specification
- Model: AN-T60S. AN-T100S AN-T60F, AN-T100F (4 frequencies version)
- Detection distance:60m\100m selectable
- Power and voltage:DC9-30V/AC9-20V
- Current consumption:≤70mA max
- Detection method:interruption of all beams
- Interruption time:50ms/100ms/300ms/700ms(adjustable)
- Alarm cycle:≥1.5s
- Alarm output:NO\NC selectable
- Tamper output:NC
- IP rating:IP65
- Operating temperature:-30°C~70°C
- Humidity:≤95%
- Correction angle:Horizontal 180°(± 90°).Vertical 20°(±10°)
- Install location:Indoor\Outdoor,Wall\Pole
- Weight:≈980g
- Dimension:184mm73mm71mm
- Attachment:
- AN-T U bracket:2pcs black ABS, 653033.5mm
- Pole mounting screw:4pcs,PM4*30mm
- AN-T foam: 68 33 6mm black, 38 degree EVA cotton
Part Description
Notes: No DIP switch for non 4 frequency version.
- DIPswitch
- Indicator
- Lock screw
- Horizontal alignment bolster
- Wire hole
- Terminal
- Tamper switch
- Adjusting screw
- Lens
Connectors
Transmitter
- Power:land2 are power inputs,support DC9~30V/AC9~20V
- Tamper:3 and 4 are tamper outputs
Receiver
- Power :1 and 2 are power inputs, support DC9~30V/AC9~20V
- Alarm: 3, 4and5 arealarm signal outputs, NC\NO selectable
- Signal test: 6 and 7 are signal test terminals. Signal test is used to test alignment. during the test, the signal voltage is not less than 4.3V.6is “+” ,and 7 is “-” ;
- Tamper: 8 and 9 are tamper outputs.
DIP Switch Explanations
(No DIP switch for non 4 frequency version)
Transmitter
DIP switches 1 & 2: Set beam frequency.TX and RX must be the same
Receiver
DIP switches 1 & 2: Set beam frequency.TX and RX must be the same DIP
Switches 3 & 4: Set interruption time.50ms/100ms/300ms/700ms(adjustable)
Indicator
Note: Both LEVEL and GOOD are indicators,GOOD means the signal is better
than LEVEL.
6.1), LEVEL(Blue) indicator: it has 4 states: Off, slow flashing, fast
flashing, and On. When the receiver don’ thave signal, it goes off. When the
receiver have signal, it slow flashing. The stronger the signal strength, the
faster the LEVEL indicator flashes until it is constantly on.
6.2), GOOD(Green) indicator:it has 4 states: Off, slow flashing, fast
flashing, and On. When the signal reaches a certain strength, the LEVEL(Blue)
indicator goes off, and the GOOD indicator enters a Slow flashing state. The
stronger the signal strength is, the faster the GOOD indicator flashes, until
the signal strength is optimal, then the GOOD indicator is constantly on.
6.3), POWER indicator:when power on, the indicator is on. (Note: After 30
minutes, the indicator will go off, which will not affect the operation of the
transmitter. when the equipment is powered on again, the indicator will be on
again.)
6.4), ALARM indicator: When the alarm is triggered, the ALARM red indicator is
on; It turns off when there is no alarm. (Note: In normal working, the signal
indicator will go off after about 30 minutes, which will not affect the
receiver’s operation. After the alarm, the indicator will be on again.).
Alignment
7.1). Adjust transmitter and receiver to a same level.
7.2), Remove the cover.
7.3), Connect to power DC9~30V/AC9~20V
7.4), Firstly adjust the receiver face to transmitter. See the indicator state
to align.
7.5), Adjust the angle by screws and the horizontal alignment bolster.
meanwhile, the LEVEL indicator(blue) of the receiver changes from slow to fast
flashing. it indicates that the optical alignment accuracy is well, until the
indicator is constantly on.
7.6), Continue to adjust, the LEVEL indicator is off, the GOOD indicator
changes from slow to fast flashing, until the green indicator is always on,
which means the signal strength is the best.
7.7), Atthe same time, judge whether the detector is well aligned by measuring
the voltage of the signal test terminals. After the signal is well aligned,
can use a multimeter to measure the voltage of the signal test terminals of
the receiver. The signal voltage is not less than 4.3 V. If the voltage is
less than 4.3 V, it need to realign it.
7.8), Alarm test:When intruder enter the protection area, the ALARM red
indicator of the receiver lights up and the relay acts; When the intruder
leave the area, it goes off and the relay recovers.
Installation
8.1), Wall mounting:
- Loosen the screw and remove the cover
- Punch two mounting holes on the target wall
- Wire hole: remove the foam plug, pull wire through, leave about 10cm wire length for wiring, and then insert the foam plug into the original position;
- Fix the body on bracket
- Connecting wires to the terminals and align the detector
- Review and reset the cover
8.2). Pole mounting:
- Break out the wire hole and pull out the wires.
- Remove the cover
- Wire hole: remove the foam plug, pull wire through, leave about 10cm wire length for wiring, and then insert the foam plug into the original position;
- Fixthe body on bracket
- Connecting wires to the terminals and align the detector
- Review and reset the cover
Installation notes:
- Do notinstall on an unsteady or moveable base;
- Do notinstall the unit where objects can block the beams like plants and laundry moving the wind;
- Preventdirect sunlight onto the Rx or Rx,which can cause damage to the detector;
- Avoid cross tall;
- Avoid exposing wiring.