INTERMATIC FM1D14 Series 24-Hour-7-Day Time Switch Instruction Manual

June 4, 2024
Intermatic

INTERMATIC logo FM1D14 Series 24-Hour-7-Day Time Switch
Instruction Manual

FM1D14 Series 24-Hour-7-Day Time Switch

FM1D14 Series 24-Hour/7-Day Time Switch Operation and User Instructions
Risk of Fire or Electric Shock
WARNING

  • Disconnect power prior to installation.
  • Connect FM1D14 wiring in accordance with all applicable national and local electrical code requirements.

Specifications

Input
12 VDC (FM1D14-12)
24 VAC and VDC, 50/60 Hz (FM1D14-24)
120-277 VAC, 50/60 Hz (FM1D14-AV)
Output

NO Contact
General Purpose: 15 A, 277 VAC
Tungsten: 1000 W, 120 VAC
Ballast: 8 A, 277 VAC
Pilot Duty: B300
Electronic Ballast: 4.9 A, 120 VAC
Motor: 10 FLA, 60 LRA @ 250 VAC; ½ HP,
120 VAC; 1 HP, 250 VAC| NC Contact
General Purpose: 15 A, 277 VAC
Resistive: 12 A, 24 VDC
Ballast: 8 A, 120 VAC
Motor: 10 FLA, 60 LRA @ 250 VAC; ½ HP,
120/240 VAC
---|---

Operating Temperature: -40˚ F to 135˚ F (-40˚ C to 55˚ C)
Carry-over: 2500 hours fully charged

Description

This manual provides installation and programming instructions for the FM1D14 series timer.
INTERMATIC FM1D14 Series 24 Hour-7-Day Time Switch -
fig Mounting the FM1D14 Series Timer
The standard FM1D14 timer can be surface mounted inside a panel or flush- mounted. Mount the timer as required. Refer to the dimension drawing in Figure 2.INTERMATIC FM1D14 Series 24 Hour-7-Day Time Switch - fig
1

Connecting the FM1D14 Series Timer Wiring
Follow this procedure to connect the FM1D14 timer wiring.

  1. Make sure the supply power is disconnected.
  2. Check input and output ratings marked on a timer to verify the product is suitable for your supply voltage, load, and application.
  3. Connect the FM1D14 wiring. See Figure 3 for reference.

INTERMATIC FM1D14 Series 24 Hour-7-Day Time Switch - fig
2

Setting the Time of Day
Follow this procedure to set the time of day and day of the week.

  1. Press and release the Reset button with a blunt object to reset the unit. The timer screen flashes.
  2. Press and hold and h+ simultaneously to access the 12:00 AM screen.
  3. Take one of these actions.
    If…| Then…
    ---|---
    Your time zone currently is in Daylight Saving Time,| Press the +1h button. Go to step 4.
    Your time zone is not in Daylight Saving Time,| Go to step 4 to set the current time.
  4. Press and hold and press h+ repeatedly until you advance to the current hour.
  5. Press and hold and press m+ repeatedly until you advance to the current minute.
  6. Press and hold and press Day repeatedly until you advance to the current day.

Programming Events

To set the ON/OFF event pair, set the ON event and then repeat the procedure to set the OFF event.
The timer enables up to 7 ON/OFF event pairs.
INTERMATIC FM1D14 Series 24 Hour-7-Day Time Switch - fig
3

  1. Press the Timer button. Dashed lines appear to indicate no event is set for event 1.
  2. Press Day to select the days of the week for the ON event. NOTE: To set the ON event:
    On a Specific Day| Select: The desired day
    ---|---
    Every Day of the Week| Select MO, TU, WE, TH, FR, SA, SU
    Every Weekday:| Select: MO, TU, WE, TH, FR
    Every Weekend:| Select: SA, SU
    Monday through Saturday| Select: MO through SAT
    Monday, Wednesday, and Friday| Select: MO, WE, FR
  3. Press h+ to scroll to the desired hour for the ON event.
  4. Press m+ to scroll to the desired minute for the ON event.
  5. Press the Timer to advance to the OFF event screen.
  6. Press Day to select the days of the week for the OFF event.
  7. Press h+ to scroll to the desired hour for the OFF event.
  8. Press m+ to scroll to the desired minute for the OFF event.

Take one of these actions.

If… Then…
You need to program another ON/ OFF event pair, Press Timer to advance to the

next event ON screen and repeat steps 2 through 8.
All the required ON/OFF events are programmed,| Press to return to the main screen. The procedure is complete.

NOTE: If events include or intersect with each other, each ON/OFF event can be independently executed at the setpoint.
NOTE: If an ON event and an OFF event occur at the same time, the timer will run the OFF event.

Daily Operation

Below is an overview of the different operation modes for FM1D14.

Mode Timer Display Description
Auto ON Appears when an ON setpoint has been triggered
Auto OFF Appears when an OFF setpoint has been triggered
OVR ON Indicates relay has been overridden to ON status
OVR OFF Indicates relay has been overridden to OFF status

NOTE: To execute an ON/OFF status override, press the OVR button on the timer to override an ON or OFF status. The override remains active until the next programmed event.
Modifying an Event
Follow this procedure to review or modify an event.

  1. Press Timer to scroll to the ON or OFF event you want to modify.
  2. Take one of these actions.
    If you want to modify the…| Then…
    ---|---
    Days of the week for ON/OFF events,| Press Day repeatedly to scroll to desired days of the week Go to step 3.
    Hour for ON or OFF event,| Press h+ to scroll to desired hour Go to step 3.
    Minute for ON or OFF event,| Press m+ to scroll to desired minute Go to step
  3. Repeat steps 1 and 2 as needed to modify additional events.
  4.  When all the desired events are modified, press to confirm event settings and return to the time of day screen.

Deleting an Event
Follow this procedure to delete an event.

  1. Press Timer to scroll to the ON or OFF event you want to delete.

  2. Press OVR to delete the event. Dashed lines appear in place of the time to indicate the event is deleted.
    NOTE: If necessary, repeat this procedure to delete both ON and OFF settings for the event.

  3. When the modifications are complete, press to return to the time of day screen.

Retrieving an Event
The timer enables deleted events to be retrieved. All deleted events can be retrieved until a new event is programmed in place of the event.

  1. Press Timer to scroll to the ON/OFF event you previously deleted. Dashed lines appear in place of the event time.

  2. Press OVR to retrieve deleted event. The event ON or OFF time replaces the dashed line indicating that the event is retrieved.
    NOTE: If necessary, repeat this procedure to retrieve both ON and OFF settings for the event.

  3. When the modifications are complete, press to return to the time of day screen.

Adjusting Daylight Saving Time
Press the +1h button to add the Daylight Saving Time hour to the current time or remove the hour to return to standard time.
NOTE: Do not perform this procedure if your area does not use Daylight Saving Time.
Resetting the Timer
In case of a timer malfunction or to delete all previous settings, the unit can be reset.
To reset the timer, use a blunt pointed object to press Reset as shown in Figure 4. The timer resets and deletes all the settings in the unit.

Overview of FM1D14 Power Loss Functions

In the event of a power loss, the FM1D14 does the following:

  • The relay will be in the OFF state.
  • Upon power restore, the relay will go to the current programmed state.

LIMITED WARRANTY

Warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.intermatic.com. This warranty is made by: Intermatic
Incorporated, 1950 Innovation Way, Suite 300, Libertyville, IL 60048. For additional product or warranty information go to: http://www.Intermatic.com or call 815-675-7000..

INTERMATIC INCORPORATED
LIBERTYVILLE, ILLINOIS 60048
www.Intermatic.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Intermatic User Manuals

Related Manuals