Sensorex CX105 Conductivity Resistivity Transmitter Instruction Manual

May 15, 2024
Sensorex

Sensorex CX105 Conductivity Resistivity Transmitter Instruction Manual

IMPORTANT SAFETY INFORMATION

Please read and observe the following:

  • Remove line power before wiring transmitter connections

  • Wiring or repairs should only be performed by qualified personnel and only to an unpowered transmitter

  • Whenever it appears that transmitter safety is questionable, disable the Transmitter to ensure against any unintended operation. For example, an unsafe condition is likely
    when:
    1) The transmitter appears visibly damaged
    2) The transmitter fails to operate properly or provide the intended measurements
    3) The transmitter has been stored for long periods at temperatures above 176F (80C)

  • The transmitter must be installed by qualified personnel in accordance with relevant codes and instructions contained in this user manual. Observe the Transmitter’s specifications and relative parameter’s ratings.

Introduction

The CX105 conductivity/resistivity transmitter is a 2-wire transmitter designed for process conductivity/resistivity monitoring, measurement and control applications. This user’s  manual contains the information needed to install, set up, operate and maintain the transmitter.

Dimension Drawings

Front and Side View

Front view

Side view

Panel Mount & Field Mount

Installation

The CX105 conductivity/resistivity transmitters are supplied with hardware to install as panel mount or field(wall) mount.

Panel Installation Instructions

  1. The panel mount version is designed for installation using a 1/4 DIN Punch (92mm(3.6in) x (92mm(3.6in).
  2. Recommended clearance on all sides between instruments is 1 inch
  3. ) Slide the gasket over the back of the instrument.
  4. Place the instrument into the panel cut-out.
  5.  Attach the mounting bracket to the back of the instrument by pulling apart the quick clips and sliding it over the back of the instrument. Make sure that the quick clips are securely attached to the latches.
  6. Inspect the instrument to make sure that the instrument and the gasket are secured to the panel appropriately.
  7. To disassemble, press the clips of the mounting bracket against the panel and pull the instrument away from the front.

Panel mount installation detail schematic

**Panel Cut-out

**

**Field(Wall) Mount Installation**

The field(Wall) mount version requires a wall mounting kit, which includes a plastic wall mounting rear cover with gasket and 4 screws. This is included with your CX105 transmitter.. This makes it possible to install the transmitter on a variety of surfaces.

  1. Place the gasket on the instrument.
  2. Thread electrical cables through the connectors on the wall mounting rear cover.
  3. Connect the power, sensor and OC output wires.
  4. Secure the wall mounting rear cover to the front enclosure with screws.
  5. Fix the wall mounting rear cover to the surface by using screws or cables.

Specifications

Display:

  • LCD: 128*65 dot matrix, figure or alphabet: 12×8, 28×15, 32×18, etc.
  • Update rate: 1 second
  • Contrast: User selected, 5 levels

Measurement:

  • Conductivity: 0.05 to 500,000 μS/cm
  • Resistivity: 1KΩ•cm to 18.3MΩ•cm
  • TDS: 0.023 to 200,000 ppm
  • Accuracy: ± 0.5% of reading
  • *Repeatability:** ± 0.05% of span
  • Temperature : -10 to 70℃*These performance specifications are typical at 25°C

Electrical:

  • Power: 19 -48VDC, regulated, 30mA maximum

Current Output:

  • Isolated 4-20 mA output with 0.004 mA (12-bit) resolution
  • Update Rate: 1 second
  • Maximum Loop Impedance: 250Ω@24V; 600Ω@31V; 1500Ω@48V

Memory:

  • Non-volatile: All user settings are retained indefinitely without battery backupOpen-Collector Output:
  • Isolated, 40 VDC max. pull-up voltageThe OC output can be configured to be one of three modes below:High mode, Low mode, Proportional pulses

Ambient Conditions:

  •  Operation: -10 °C to 70 °C (14 °F to 158 °F); 0-95% relative humidity, non-condensing
  • Transport/storage: -15°C to 80°C(5°F to 176°F); 0-95% relative humidity, non-condensing

Standards and Approvals

  • CE: Certified Compliant to European Community Standards.

Electrical Connections

System Power & Loop Connections

Electrode Input Connections

CAUTION:

As electrical noise may interfere with electrode signal, please do not route the electrode cable in aconduit containing AC power wiring.wire colors in table to left apply for all
sensors except CS8000TC and CS615TC, CS620TC.

Electrode Input

Drive| Red
Ground| Black
Temp| Green
Temp| White
Electrode Input
Drive| black
Ground| white
Tepm| green
Temp| red
D|
---|---
rive| coax center
---|---
Ground| Coax braid
Tepmp| green
Tempp| red

Wiring For CS615TC, CS615TC

Transmitter Terminals

8| Drive
7| Ground
6| Temp
5| Shield

S855 cable used with CS8000TC

Transmitter Terminals

8| Drive
7| Ground
6| Temp
5| Shield
Transmitter Terminals
8| Drive
7| Ground
6| Temp
5| Shield

OC Output

Open Collector Output Connections

  • Connection to a PLC with built-in power supply
    | PLC|
    ---|---|---
    Power Supply+| +|
    | |
    | Power Supply-| –|
    | OC input+| +|
    |
    OC input-| –|
    Transmitter Terminals

    4| O.C.+
    3| O.C.-

  • Connection to a PLC, separate supply
    Transmitter Terminals

    4| O.C.+
    3| O.C.-

Open Collector Output Operation

The open collector output can be used as a switch or a warning that responds when the process value moves above or below a set point, or it can be used to generate a pulsing signal with a rate proportional to the process value. The output can be disabled if not used (select “OFF” in the OC OUTPUT menu). The “parameter” mentioned below can be either conductivity or temperature.

Low Mode:

  • In this mode, the OC output is only active when the parameter is lower than a user set point. The output will be inactive when the parameter value is greater than the set point plus the hysteresis value.

  • High Mode:
    In this mode, the OC output is only active when the parameter value is higher than a user set point.The output will be inactive when the parameter value is smaller than the set point minus the hysteresis value.

  • Proportional Pulsing
    In this mode, the OC output will generate a pulse sequence at the rate defined by the setting in the OC OUTPUT menu.In the following example, the starting point is 10μS/cm, the end point is 110μS/cm, and the maximum frequency is 200 pulses/min:

  • The output will be 0 pulses/min when the conductivity value is less than 10μS/cm.

  • The output will be 100 pulses/min when the conductivity value is 60μS/cm.

  • The output will be 200 pulses/min when the conductivity value is greater than 110μS/cm.

MenuThe menu consists of a view menu and an editable menu. The menu has several levels, with the view menu being at the topmost level. You can loop within the same level menu items by pressing the UP or DOWN arrow keys, move to a lower level menu by pressing the ENTER key, and move to an upper level menu by pressing the ESC key. At any time, the system will return to the view menu (default display) if no key is pressed for 10 minutes. During normal operation, the view menu is displayed. Use the UP or DOWN arrow keys to select the information you want displayed. The items will scroll in a continuous loop. System operations will not be interrupted during menu interaction.

View Menu

Cond μS/cm Monitors the conductivity and temperature input from the
electrode.
109.55 The unit of conductivity or temperature is set in the

calibration menu.
| 28.2               ℃|

All displays below are temporary. The system will return to the default display if no keys are pressed in 10 minutes.

Editable Menu

Editing Procedure Step 1. Press and hold the ENTER key for 3 seconds to enter Main Menu:

  • If a password is required, enter the correct key code. The key code is entered by pressing the RIGHT-DOWN-UP-DOWN keys in sequence.
  • The system will return to the view menu if no key is pressed for 10 minutes.

Step 2. Navigating the menu with the UP and DOWN keys. Once the selected menu is highlighted, press ENTER to edit the menu.

  • Only the highlighted item can be edited.
  •  No parameters will be saved if the ESC key is pressed, and the display will return to the previous menu.
  • The system will return to the view menu if no activity occurs for 10 minutes.

Step 3. Press the ENTER key to save the new settings and return to Step 2.
NOTE:

  • ESC can be pressed at any time, and the system will exit the current level without saving.
  • The edited value is effective immediately after pressing the ENTER key.
  • Repeat steps 2–3 as needed.

Main Menu

| CALIBRATION >|
---|---|---
OUTPUT>

Press the UP or DOWN arrow keys to navigate the three items. Press the ENTER key to enter the CALIBRATION menu, the OUTPUT menu, or the OPTIONS menu. Press the ESC key to return to the view menu.

Calibration Menu

Display **Description**
Menu Item Next Level Menu
CELL> 1.00 Set Cell 01.00

electrode.
---|---|---
**** UNIT >μS/cm     ℃| COND UNIT >μS/cm| Sets the unit of conductivity/resistivity. Options are:μS/cm, mS/cm, kΩcm, MΩcm, PPM.
---|---|---
TEMP UNIT >℃| Sets the unit of Temperature. Options are :℃,℉.
TEMPERATURE >20.0℃| Set Temperature|
Sets the value of temperature.
---|---|---
| +20.0 ℃
CONDUCTIVITY >μS/cm| Set conductivity| ****

Sets the value of conductivity.

---|---|---
9| 463.95μS/cm
PPM FACTOR > 2.00| Set PPM Factor 2.00| Sets the PPM Factor. It can be any value from 0.01 to 99.99. The default value is 2.00.
---|---|---

  • Output MenuC SDV DVFV

The next two sections (5.2.4.1 and 5.2.4.2) use conductivity as an example, but all of the operations are the same for temperature.

Set 4mA Output> Sets the conductivity value for 4mA current loop output.
0 00200. μS
Set 20mA Output> Sets the conductivity value for 20mA current loop output.
200000.μS
Display **Description**
Menu Item Next Level Menu

**** MIN ALARM| MIN SETPOINT>0100.00μS/cm| As described in 4.3.2, sets the minimum point forlow mode. The OC output is active when the conductivity value is less than the set value.
---|---|---
HYSTERESIS>0020.00μS/cm| As described in 4.3.2, sets the hysteresis value for low mode. The OC output is inactive when the conductivity value is greater than the sum of theminimum point and the hysteresis value.

**** MAX ALARM| MAX SETPOINT>0100.00μS/cm| As described in 4.3.2, sets the maximum point forhigh mode. The OC output is active when the conductivity value is greater than the set value.
---|---|---
HYSTERESIS>0020.00μS/cm| As described in 4.3.2, sets the hysteresis for high mode. OC output is inactive when the conductivity value is less than the maximum point minus the hysteresis value. Note: the   hysteresis   must   be less   than   the maximum point.
**** PULSE| RANGE>000000.μS/cmà 200000μS/cm| As described in 4.3.2, sets the start point and end point for pulse mode.
PULSE RATE>100 Pulse/min| As described in 4.3.2, sets the maximum pulse ratefor pulse mode.

Option Menu

| Sets the time parameter for averaging input values. There are 8
---|---
FILTER > 1S| options: 1S, 2S, 5S, 8S, 10S, 20S, 40S, and 60S. Note Larger filter values mean more stable displays but longer response  times. Please  consider  your  system  safety
| requirements.
| Press the UP and DOWN keys to manually select any output
---|---
| current value from 3.7 mA to 21.00 mA to test the current loop
TEST 4~20mAOUTPUT>| output. The value changes 0.01mA each time the UP/DOWN keyis pressed. If the UP/DOWN key is pressed and held for more
| than 5   seconds,   The   value   will   be   changed   by   0.1mA
| continuously.
| Selects whether or not the password is needed to enter the Main
---|---
PASSWORD MENU>| Menu.    Note:    the    password    is    input    by pressing    the
OFF| RIGHT-DOWN-UP-DOWN arrow keys in sequence and cannot be
| changed.

CAUTION:

All calibration procedures must be performed by trained personnel. Incorrectly set parameters may go unnoticed, but will still change the measurement properties.

 Wet     Calibration     (1     Point     Sample Method)

The “wet” calibration method requires the user to immerse the electrode into a properly prepared conductivity reference solution of known value, or to keep the electrode installed in the process while obtaining a process sample. When keeping the electrode installed, determine the process value through a laboratory analysis of comparable reading. In either case, enter the correct reference solution or sample conductivity value. The procedure is as follows:

  • Step 1 : Make sure the electrode is clean, and then immerse the electrode into solution. Stir electrode in solution to ensure no
  • Step 2 : Wait for the temperature to Depending on how great the temperature difference is, this may take up to 30 seconds.
  • Step 3 : Set the temperature to the value reading from a precision
  • Step 4: Set the conductivity to a value, which is either from a solution or read from a precise
  • Step 5: Place the electrode into a second different value solution, and verify the linearity. If the transmitter does not display the correct value (temperature ± 5℃, conductivity ±2% of reading), contact Sensorex technical support.

 Dry Calibration (Simulates the Conductivity and Temperature)

The Dry Calibration method requires the user to simulate the conductivity and temperature by using precise fixed resistors (± 0.1%). The calibration procedure is as follows.

Temperature Simulation

The temperature input to the CX105 is a PT-1000 RTD, where 1000 Ohms (Ω) is equal to 0 ℃
and a change of 3.85 Ω equals to 1℃ difference. (1000 Ω = 0 ℃, 1096 Ω = 25 ℃)

  • Step 1 : Connect a resistor (1000 Ω to 1096 Ω) between the “Temp” and “Ground” terminals.
  • Step 2 : Set the temperature in the same manner as the wet calibration procedure.
  • Step 3 : Connect a different value resistor to the “Temp” and “Ground” terminals, and verif the linearity. If the transmitter displays an incorrect value (±0.5℃),contact Sensorex
    technical support.

Conductivity Simulation

  • The following formulas will be useful for the user to simulate the conductivity and verify the
    results and linearity.
    resistance = cell constant
    conductivity e.g.
    1.00cell
    0.000010simens = 100kΩ
    conductivity = cell constant
    resistance e.g.
    1.00cell
    100kΩ = 0.000010simens

  • Step1: Connect a precise resistor between the “Drive” and “Ground” terminals.

  • Step 2 : Set the conductivity in the same manner as the wet calibration procedure.

  • Step 3 : Connect a different value resistor to the “Drive” and “Ground” terminals, and verify the linearity. If the transmitter displays an incorrect value (±2% of reading), contact Sensorex technical support

Parts per Million (PPM) Factor

When the unit in the calibration menu is PPM, the following information is useful. The PPM factor
is a value between 0.01 and 99.99, and the default value is 2.00.
The formulas are:
PPM Factor = solution conductivity(µS/cm)
TDS(PPM)
TDS(PPM) = solution conductivity(µS/cm)
PPM Factor
TDS: Total Dissolved Solids.
For example:
When the solution conductivity = 1000µS/cm and TDS = 500ppm(mg/L), the PPM Factor is 2.00.

Troubleshooting

Display Possible Cause Suggestions
ValueToo Large (or Small)! During                                temperature

calibration, the entered value is more than 25 degree awayfrom the detected value.| 1.       Check the sensor and repeat the calibration procedure.2. Enter appropriate values.
CellCan NOT Be Zero!| Cell value is set to zero.| Cell value cannot be set to zero, please set a value larger than zero.
**** HYSTERESIS Too Large| The HYSTERESIS is larger thanthe MAX SETPOINT| Set the HYSTERSIS to a smallervalue than MAX SETPOINT.

Ordering information

Part No. Description
CX105 Conductivity/Resistivity Transmitter
AR100-11 Mounting Bracket for Transmitter, Panel Mount (included with CX105, order when lost or dam aged)
AR100-15 Transmitter Gasket (included with CX105, order when lost or damaged)
AR100-17 Mounting Kit for Transmitter, Field Mount (included with CX105, order when lost or damaged)

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals