Installation

Installation spacing
To guarantee proper air suction, leave at least 15cm of space between the wall and the backside of the unit, where the carbon & dust filters and air inlet are located. At least 15cm of space should also be left between the topside of the unit and the ceiling. Larger spaces are preferred. The unit must stand free from the wall to avoid contact noises.OPTI CLIMATE Revomax II Smart Remote
Controller - Installation spacing Installation
The unit can be hung from a ceiling or placed on a stand or frame.
Ceiling
To hang the unit from a ceiling, remove both side panels and pinch a hole through the insulation at the position of the 4 holes in the bottom of the unit. Use an M8 or M10 metal threaded rod with a nut, washer and rubber damper to prevent unwanted noise or vibration. OPTI CLIMATE Revomax II Smart Remote
Controller - Ceiling

Stand or frame
Make or buy a stand or frame to hold the weight of the Opticlimate. (see nameplate )
You can use the rubber damper or a vibration damper (not incuded)
Pinch a hole through the insulation at the position of the 4 holes in the bottom of the unit. Use an M8 bolt and washer to mount the rubber or damper.

OPTI CLIMATE Revomax II Smart Remote Controller - Stand or
frameMake sure the side of the condensation outlet is 1 cm lower than the opposite side.

Routing the Cables

OPTI CLIMATE Revomax II Smart Remote Controller - Routing the
CablesFirst, the panel at the left side near the manometer should be removed to make the various electrical connections.
A magnetic valve, water leakage sensor, automatic moisture meter, remote control and room temperature sensor are supplied with the unit. Their cables can be led to the outside through the opening at the bottom of the panel.
The power cable for the power supply can be led through the black feed-through rubber at the side of the unit.
ELECTRICAL CONNECTIONOPTI CLIMATE Revomax II Smart Remote Controller -
ELECTRICAL CONNECTION Automatic Humidity Sensor with light cell
The Automatic Humidity Sensor with light cell supplied with the unit can be found in the connection set supplied with Revomax. The cable should be led through the opening in the front panel and connected to the circuit board (see picture) The sensor should be hung in the room and may not be covered. The light cell determents if it’s night or day.
Room temperature sensor
The connection set also contains a room temperature sensor, which needs to be connected to the printed circuit-board. This sensor should be led to the outside through the opening in the panel and should be hung at the level of the upper side of the vegetation. The sensor should be protected against heat radiation and must be put in the shade. A protective cover over the sensor is sufficient.
The Smart Remote Controller
The smart remote controller can be found in a separate black box, the cable to connect the smart remote controller can be found in the connection set. The cable must be led through the opening in the panel and the UTP connector must be connected to the circuit board (see picture) The USB side of the cable can be plugged in one of the USB ports on the smart remote controller.
Power supply specifications
4 different OptiClimate models are available. For your safety and the safety of the OptiClimate, the following specifcations should be observed when connecting the power supply: use the circuit breakers (MCB) and cable thickness specifed.
The cables for the supply voltage should be led through the grommet at the side of the unit and connected to the green screw terminal on the circuitboard as described in the illustration. The grounding can be connected to the PE at the bottom right of the metal back plate.OPTI CLIMATE Revomax II Smart
Remote Controller - Power supplyWhen it’s not possible to use a 3 phase power supply but only a single phase power supply is available the phase L1 + L2 + L3 need to be looped using a correct diameter wire. (only 6000 and 10000 models)

WATER CONNECTIONS

Water-in and water-out connections of the cooling water.
The unit can be used by connecting the water in and out connections to a cold water supply and a drain or can be used using the Opticlimate water cooler to cool the water in a closed loop. (connections and discription of a water cooler setup need to be obtained in the water cooler manual. Only the setup using a cold water supply and a drain are discribed in this manual.
Using a water cooler or other closed loop systems skip to page *
The unit has a water inlet and outlet. The inlet needs to be connected to a cold water supply (max 25°C) with a solenoid valve installed at the beginning of the piping going to the Opticlimate water-in connection. In case of a waterleak the valve will close.
Mounting the valve at the end of the piping (near the Opticlimate) is pointless. (always check the flow direction arrow on the valve!).
Make sure that the black magnetic coil of the solenoid valve is positioned upwards (preferred) or to the side. If it is positioned downwards, condensate from the cold valve might enter the coil. Make sure that the solenoid valve is installed at a fxed point that is always easily accessible to the user. OPTI
CLIMATE Revomax II Smart Remote Controller - WATER
CONNECTIONSA strainer should be placed in the water inlet. This strainer prevents blockage in the heat exchanger inside the unit. It is recommended to insulate the cold water supply line in order to prevent condensation build-up. The upper water connection is the water-outlet. The water-outlet can be connected directly to the drain (sewer). Alternatively, the warm water can be used for heating purposes. The water is aprox 35°C- 40°C.
The water flow (water usage) is automatic regulated by an electronic flow regulator inside the unit.
When you use and alternative cold water supply such as a well or water from a river , leak or pond, make sure the water is filtered and clean the heat exchanger on regulare base. Contact tech support for more information regarding cleaning the heat exchanger.
CONDENSATION WATER
Discharge of the condensation water
The unit will dehumidify the air during cooling and in dehumidify mode. The moisture extracted from the air is collected in the condensation an. The condensation pan has an ¾ drain pipe where the condensate will run off. The condensate can be used as irrigation water.
The cooling block has been modified to prevent metals or oxides from entering the condensate water.OPTI CLIMATE Revomax II Smart Remote Controller -
CONDENSATION WATERThe location of the drain pan is on the negative pressure side of the unit, meaning that air can enter into the unit through the condensation drain, It’s highly recommended to use a “P-trap” on the condensation outlet to prevent air entering the unit and to prevent condensate run-off problems.
Not using a p trap also results in loss of capacity and bypassing non processed air.OPTI CLIMATE Revomax II Smart Remote Controller - CONDENSATION
WATER 1If the unit is installed at the same level or lower than the drain or sewer, a condensation lift pump can collect the water. This small lift pump pumps the water through a hose of 9mm to a height of 4 metres into the drain or collecting tank. Stronger pumps are also available.

SMART RExMOTE CONTROLLER

Connecting the Smart Remote ControllerOPTI CLIMATE Revomax II Smart
Remote Controller - Smart Remote Controller Power
Connect the power supply and USB connector from the remote cable to the Smart Remote controller. OPTI CLIMATE Revomax II Smart Remote Controller -
PowerConnections
At the back of the Smart Remote Controller you find the USB, HDMI, Ethernet and power supply connections.
CONNECTIONG THE SMART REMOTE CONTROLLEROPTI CLIMATE Revomax II Smart
Remote Controller - SMART REMOTE CONTROLLER Connect the RJ45 side of the remote control cable to the RJ45 plug at the left upper corner of the circuit board (see image)
Powering up the unit

  • Power on the Smart Remote Controller
  • Power on the Opticlimate by switching on the power supply.
  • Open the water supply.

After powering up the Opticlimate, the unit will first initialize, this can take a few minutes.
All valves and sensor are tested prior to startup. The remote controller cannot be operated during initializing of the Opticlimate.
After powering up the Smart remote controller, the remote will first initialize, this can take a few minutes. You will see several screens pop-up and close again, this is normal.
The unit is now installed and ready to use

OPERATING BY USING THE SMART REMOTE CONTROLLER

After both Smart controller and Opticlimate are initialised, the Smart Remote controller will display the Home screen *1 Alarm
The ALARM icon will display an alarm (power failure) this is normal after startup and will show each time you power up the unit or in the case of a power failure.during initializing of the Opticlimate. After powering up the Smart remote controller, the remote will first initialize, this can take a few minutes. You will see several screens popup and close again, this is normal. Reading and deleting the alarm
You can obtain more information regarding this alarm by pushing on the “enlarge button .
You can erase the alarm by pushing on the alarm icon and then press the bin .
In the right upper corner you find the home icon  you can toggle between home 1 (basic) and home 2 (advanced)

OPTI CLIMATE Revomax II Smart Remote Controller -
Homescreen

Homescreen 1
You can obtain more information regarding this alarm by pushing
on the “enlarge button” .| Homescreen 2
You can obtain more information regarding this alarm by pushing
on the “enlarge button” .

Setting the basic parameters
Go to home 1 or home 2 by pressing the home icon.OPTI CLIMATE Revomax II
Smart Remote Controller - basic parametersTouch the Temperature area to enlarge the window for temperature day/night settings.OPTI CLIMATE Revomax II Smart Remote
Controller - Setting day Setting day temperature setpoint.
Touch the sun icon to set daymode temperature and use + and – to change the daymode temperature.OPTI CLIMATE Revomax II Smart Remote Controller -
Installation spacing Setting night temperature setpoint.
Touch the moon icon to set nightmode temperature and use + and – to change the nightmode temperature.
Touch the X to return to home.
Setting day and night dehumidify setpoint
Go to home 1 or home 2 by pressing the home icon.OPTI CLIMATE Revomax II
Smart Remote Controller - night temperature Setting day and night temperature setpoint.
Touch the dehumidify area to enlarge the window for dehumidify day/night settings.OPTI CLIMATE Revomax II Smart Remote Controller - Setting day
1Setting day temperature setpoint.
Touch the sun icon to set daymode humidity and use + and – to change the daymode humidity setpoint.OPTI CLIMATE Revomax II Smart Remote Controller -
night temperature 1Setting night temperature setpoint.
Touch the moon icon to set nightmode humidity and use + and – to change the nightmode humidity setpoint.
Touch the X to return to home.
On/off switchOPTI CLIMATE Revomax II Smart Remote Controller - off
switch Setting day and night temperature setpoint.
In the right upper corner you find the on/off button.
Touching the button will switch the unit on and the icon turns green.
Touching the button again will turn the unit off and the icon will turn red.
Sequence of operation when the unit is turned on.

  • The on/off button turns green
  • The fan inside the unit turns on.
  • The light sensor will determen or the room is in day or nightmode.

OPTI CLIMATE Revomax II Smart Remote Controller - turned
onIn daymode the windows with the sun turn green (night is black) and there will be an indication or the unit is cooling or not cooling and or there is a demand to dehumidify when not cooling. (Note: The unit always dehumidifies when cooling)OPTI CLIMATE Revomax II Smart
Remote Controller - windowsIn nightmode the windows with the moon turn green (day is black) and there will be an indication or the unit is cooling or heating and or there is a demand to dehumidify when not cooling. (Note: The unit always dehumidifies when cooling)
By touching the home button you can go to the advanced screen and you can see more parameters displayed and also a simple datalog window. The settings for temperature and humidity is the same as in the basic screen.OPTI CLIMATE
Revomax II Smart Remote Controller - Home - Advanced
Screen Home – Advanced Screen
By touching the home button you can go to the advanced screen and you can see more parameters displayed and also a simple datalog window. The settings for temperature and humidity is the same as in the basic screen.

Remote control via AnyDesk
The Revomax can be remotely controlled using any device connected to the internet. The remote controller uses the Anydesk application by default and you can access the unit using MIFI (modum using a sim card), Hotspot on a mobile cellphone, WIFI and LAN.
In a LAN setup, connect the LAN cable between the Smart Remote Controller and you modem or router. Connect the Smart Remote Cont oller to the network.
Go to Menu > Settings > User preferences > Remote AccessOPTI CLIMATE Revomax
II Smart Remote Controller - SettingsTap “Wi-Fi” to open Network & Internet settings and connect to your internet access-point. You can skip this step if you use wired internet.
In a wireless setup (MIFI, Hotspot or MIFI) use the manual of the wireless device you are using and connect through Anydesk.

REMOTE CONTROL VIA ANYDESK

Tap “Set password”OPTI CLIMATE Revomax II Smart Remote Controller - REMOTE
CONTROL VIA ANYDESKClick “Unlock Security Settings …”
Tap the password field to open the on-screen keyboard.
Unfortunately this obscures the password field, but that does not matter. Enter the password, which is either Maxi Controller for the smart remote controller with the golden startup logo or Revomax for the smart remote controller with the silver startup logo (the first letter must be uppercase). Press Enter  , or close the keyboard and tap “Yes”.OPTI CLIMATE Revomax II Smart Remote
Controller - REMOTE CONTROL VIA ANYDESK 1Tap “Set Password…”OPTI CLIMATE Revomax II
Smart Remote Controller - Unattended AccessEnter the password you want to use to remotely access his controller in both fields and close the keyboard.
Then tap on the “Permission Profile” box and change it to “Unattended Access” (This is important!)OPTI CLIMATE Revomax II Smart Remote Controller -
panelsClose both the settings panels by tapping the cross in the top right, then tap “Show ID”OPTI CLIMATE Revomax
II Smart Remote Controller - AnyDesk clientEnter this number into the AnyDesk client (installed in the previous section) and press connect. You can now close the AnyDesk panels on the controller. Use your AnyDesk client to test remote access to your controller now. It may take a minute before the connection succeeds.
If you get “Client Offline” you have mystyped the number or either your controller or AnyDesk client has lost internet connection. Do not attempt the option “Power On” as this has no effect.OPTI CLIMATE Revomax II Smart Remote
Controller - REMOTE CONTROL VIA ANYDESK 2When connection succeeds, the controller shows the incoming connection. There’s no need to press Accept on the controller; entering the password on the AnyDesk client will do the same. Your client will remember the 9-digit ID from now on.
Additional accessories (sold separately)
Electric solenoid valve
The plug of the solenoid valve should be connected using the black cable supplied with the unit, as shown in the illustration below.OPTI CLIMATE
Revomax II Smart Remote Controller - Electric solenoid
valveThe other end of the cable is connected to the circuit board (see picture). The third connection of the solenoid valve can be used as earthing.OPTI CLIMATE Revomax II Smart
Remote Controller - solenoid valve

ADDITIONAL ACCESSORIES

Water leakage sensor
The connection set contains a loose, 5m long white wire: the water leakage sensor. This sensor is connected to the terminal on the printed circuit-board. The sensor cable should be led to the outside through the opening in the panel and should be placed on the ground at the lowest point. The end of the sensor cable can be split into several cores using a connector, so that more than one point is secured against leakage.
If the sensor has a black cap, this should be cut back and stripped 5mm and the cores should be stripped. Connect the other side to the little white plug on the printed circuit-board as shown in the illustration. In case of water leakage, the water supply will be stopped immediately by means of the electrical valve in the water pipe.OPTI CLIMATE Revomax II Smart Remote
Controller - Water leakage sensor

www.theclimatefactory.com
info@theclimatefactory.com