Altronix SMP7PMCTXX Power Supply Chargers-8Installation Guide

June 4, 2024
Altronix

Altronix SMP7PMCTXX Power Supply Chargers-8

Altronix SMP7PMCTXX Power Supply Chargers

Models Include:
SMP7CTX
SMP7PMCTX
SMP7PMCTXX
– Single Output.

SMP7PMP4
– Four (4) Fuse Protected Outputs.
SMP7PMP8
– Eight (8) Fuse Protected Outputs.
SMP7PMP16
– Sixteen (16) Fuse Protected Outputs.

SMP7PMP4CB
– Four (4) PTC Protected Outputs.
SMP7PMP8CB
Eight (8) PTC Protected Outputs.
SMP7PMP16CB
– Sixteen (16) PTC Protected Outputs.

For a red enclosure add an “R” suffix to the part #, e.g. SMP7CTXR

Rev. 011604 More than just power.TM
Installing Company: ____ Service Rep. Name:


Address: __ Phone #: _


Overview

Altronix SMP7CTX Series power supply/chargers convert a 115VAC, 60Hz input into a regulated 12VDC or 24VDC output with up to 6A of continuous load current (see specifications).
SMP7CTX Series Power Supply Configuration Reference Chart:

Altronix SMP7PMCTXX Power Supply Chargers-1

Specifications

Input:

  • Input 115VAC, 60Hz, 2.5A.

Output:

  • 12VDC or 24VDC selectable output.
  • 6A supply current.
  • Filtered and electronically regulated outputs.
  • Short circuit and thermal overload protection.

Battery Backup:

  • Built-in charger for sealed lead acid or gel type batteries.
  • Maximum charge current 0.7A.
  • Zero voltage drop when switching over to battery backup.

Features:

  • Power ON/OFF switch.
    Supervision (select models):

  • AC fail supervision (form “C” contacts).

  • Battery presence and low battery supervision (form “C” contacts).

  • Visual Indicators:

  • AC input and DC output LED indicators.

Electrical:

  • Operating temperature: 0ºC to 49ºC ambient.

Mechanical:

  • Enclosure Dimensions (H x W x D approx.):
    SMP7CTX, SMP7PMCTX, SMP7PMP4,
    SMP7PMP4CB, SMP7PMP8, SMP7PMP8CB,SMP7PMP16, SMP7PMP16CB:
    13.5” x 13” x 3.25”(342.9mm x 330.2mm x 82.6mm)
    – Accommodates up to two (2) 12VDC/7AH batteries.
    SMP7PMCTXX:
    15.5” x 12” x 4.5”(393.7mm x 304.8mm x 114.3mm)
    – Accommodates up to two (2) 12VDC/12AH batteries.

Power Supply Voltage Output Specifications

Output VDC Switch Position Max. Load DC
12VDC SW1 – ON (Fig. 1c, pg. 5) 6A
24VDC SW1 – OFF (Fig. 1c, pg. 5) 6A

Specified at 25˚C ambient.

Installation Instructions

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.

  1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 7, 8). Secure enclosure to earth ground.

  2. Slide [Power ON/OFF] switch t o OFF position.

  3. Set SW1 on the power supply board to the desired DC output voltage (Fig. 1c, pg. 5) (Power Supply Voltage Output Specification Chart).

  4. Connect AC power to the terminals marked [L & N], connect ground to the green flying lead (Fig. 1, pg. 5). Use 18 AWG or larger for all power connections (Battery, DC output).
    Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

  5. Slide [Power ON/OFF] switch to ON position.

  6. Measure output voltage before connecting devices. This helps avoiding potential damage.
    Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input,Battery Wires). Minimum 0.25” spacing must be provided.
    CAUTION: Do not touch exposed metal parts.
    Shut branch circuit power before installing or servicing equipment.
    There are no user serviceable parts inside.
    Refer installation and servicing to qualified service personnel.

  7. Slide [Power ON/OFF] switch t o OFF position.

  8. Connect devices to be powered:
    a. For Power Supply Board connect to the terminals marked [– DC +].
    b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked [1P & 1N] through [4P & 4N] (Fig. 2, pg. 6), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 6), or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4, pg. 6), carefully observing correct polarity.
    Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 5). When servicing the unit, AC mains should be removed.

  9. When using stand-by batteries, they must be lead acid or gel type.
    Connect battery to the terminals marked [– BAT +] (battery leads included).
    12VDC operation: Use one (1) 12VDC battery.
    24VDC operation: Use two (2) 12VDC batteries connected in series.
    Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
    For supervised models only:

  10. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs marked [NC, C, NO] (Fig. 1b, pg. 5).

  11. Slide [Power ON/OFF] switch to ON position.

LED Diagnostics

Power Supply Board

Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.
Terminal Identification

Power Supply Board:

Terminal Legend Function/Description
L, G, N Connect 115VAC to these terminals: L to Hot, N to Neutral.
– DC + 12VDC / 24VDC @ 6A continuous output.
*AC FAIL NC, C, NO Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present.

Contact rating 1A @ 120VAC / 28VDC.


*Low Battery NC, C, NO

| Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.

Low battery threshold:

12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC.

– BAT +| Stand-by battery connections. Maximum charge rate 0.7A.

Note: Supervised models only

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB – Power Distribution Module:

Terminal Legend Function/Description
PD4/PD4CB PD8/PD8CB
1P to 4P 1P to 8P
1N to 4N 1N to 8N

Caution: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.

The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.

CAUTION: To reduce the risk of electric shock do not open the enclosure. There are no user-serviceable parts inside. Refer servicing to qualified service personnel.

Fig. 1

Fig. 1a
Switch disables power mains line voltage input.
If stand-by battery (batteries) are connected, the DC output remains on

Altronix SMP7PMCTXX Power Supply Chargers-3

Fig. 1c
SW1
12VDC – ON
24VDC – OFF

Power Distribution Module(s)

Fig. 2 – PD4/PD4CB

Fig. 3 – PD8/PD8CB

Fig. 4 – PD16W/PD16WCB

Altronix SMP7PMCTXX Power Supply Chargers-6

Enclosure Dimensions (BC300)

SMP7CTX, SMP7PMCTX, SMP7PMP4, SMP7PMP4CB,
SMP7PMP8, SMP7PMP8CB, SMP7PMP16, SMP7PMP16CB
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
Enclosure accommodates up to two (2) 12VDC/7AH batteries.

Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix).

Altronix SMP7PMCTXX Power Supply Chargers-7

Enclosure Dimensions (BC400):
SMP7PMCTXX
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Enclosure accommodates up to two (2) 12VDC/12AH batteries.

Altronix SMP7PMCTXX Power Supply Chargers-8

Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056