Precision GP75NL Phoenix Phase Converter User Manual

June 17, 2024
PRECISION

Precision GP75NL Phoenix Phase Converter User Manual

Precision GP75NL Phoenix Phase Converter.webp

GP75NL

ELECTRICAL SPECIFICATIONS SHEET

FIG 1 ELECTRICAL SPECIFICATIONS SHEET.JPG

FIG 2 ELECTRICAL SPECIFICATIONS SHEET.JPG

Optional Feature
• 208, 460 Volt Output (includes transformer)
• AutoStart and AutoOff with load detection
• PL Model (includes Start and Stop with Built-in Mag Starter)
• GPX Model (includes WFI Cloud Controls, Timers, Energy Monitor)
• Wireless Remote ON/OFF

CAUTION
READ INSTRUCTIONS BEFORE OPERATING

READ FIRST – BEFORE INSTALLATION

• Most important step to know.
• NEVER Start the phase converter with a load, this includes transformers.
• Make sure you have the incoming service to start the phase converter, call your electric company verify the KVA size of the transformer, that KVA number should be larger then the HP of the idler motor.
• DO NOT use WIRE NUTS for any connection, use the bolt down lugs. Check all make sure all connections even factory connections to the power block are secure, also recheck connections after a few week of using the converter.
• When powering up the unit, if the idler does NOT come up to FULL SPEED, then shut the phase converter down right away. If you don’t understand then call us or a qualified electrician. if you do not turn the unit off you have a chance to damage the idler motor that will not be covered under warranty.
• Must be installed by a license industrial electrician, our guidelines are not to supersede local and state laws.

Power requirements

• You will need to use a motor load type breaker. NOT a quick blow or trip breaker.
• Sizing a breaker for a single machine with an inductive load (motors) double the amps size of the machine. Example if the equipment pulls 20 amps use a 40 amp breaker.
• Sizing the equipment for multiple machine double the amp of the largest machine and add the the other machine that will run at the same time. Example; 20 AMP Lathe. 9 amp saw, 6 amp milling machine. 20 X 2 = 40 +9 + 6 = 45 amps, use the next standard size breaker which would be 50 Amps two pole breaker.
• Use the chart to make sure you don’t go over or under the Minimum and maximum size allowed. For rural areas increase the minimum size breaker by 20% Click on the next picture to see this chart.

FIG 4 Mounting the Phase Converter Panel.jpg

CONNECTING THE IDLER MOTOR WIRES

THIS IS JUST A ILLUSTRATION OF WHAT WIRES GET CONNECTED TOGETHER, DO NOT USE WIRE NUTS, USE BOLT DOWN LUGS

FIG 5 CONNECTING THE IDLER MOTOR WIRES.JPG

FIG 6 CONNECTING THE IDLER MOTOR WIRES.JPG

FIG 7 CONNECTING THE IDLER MOTOR WIRES.JPG

FIG 8 CONNECTING THE IDLER MOTOR WIRES.JPG

75 HP Rotary Phase Converter Components

FIG 10 75 HP Rotary Phase Converter Components.JPG

FIG 11 75 HP Rotary Phase Converter Components.JPG

Read More About This Manual & Download PDF:

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

PRECISION User Manuals

Related Manuals