SensorGruppen ULK-EIP-4A4BP6 Ethernet/IP, 8 portow IO-Link User Guide
- June 17, 2024
- SensorGruppen
Table of Contents
User Guide
UG_ULK-EIP-4A4BP6
(IO-Link MASTER,4A4B,EIP,IP67)
Introduction
1.1 Agreement
The following terms/abbreviations are used synonymously in this document:
IOL: IO-Link.
LSB: least significant bit.
MSB: most significant bit.
This device: equivalent to “this product”, refers to the product model or
series described in this manual.
1.2 Purpose
This manual contains all the information required to use the device correctly,
including information on necessary functions, performance, usage, etc.
It is suitable both for programmers and test/debugging personnel who debug the
system themselves and interface it with other units (automation systems, other
programming devices), as well as for service and maintenance personnel who
install extensions or perform fault/error analysis.
Please read this manual carefully before installing this equipment and putting
it into operation.
This manual contains instructions and notes to help you step-by-step through
installation and commissioning. This ensures trouble-free.
use of the product. By familiarizing yourself with this manual, you will gain.
The following benefits:
❖ ensuring safe operation of this device.
❖ take advantage of the full capabilities of this device.
❖ avoid errors and related failures.
❖ reduce maintenance and avoid cost waste.
1.3 Valid Scope
The descriptions in this document apply to the IO-Link device module
products of the ULKEIP series.
1.4 Declaration of Conformity
This product has been developed and manufactured in compliance with applicable
European standards and guidelines (CE, ROHS).
You can obtain these certificates of conformity from the manufacturer or your
local sales representative.
Safety Instructions
2.1 Safety Symbols
Read these instructions carefully and inspect the equipment before attempting
to install, operate, repair, or maintain it. The following special messages
may appear throughout this document or on the equipment to indicate status
information or to warn of potential hazards.
We divide the safety prompt information into four levels: “Danger”, “Warning”,
” Attention”, and “Notice”.
DANGER| indicates a severely hazardous situation which, if not avoided, will
result in death or serious injury.
---|---
WARNING| indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
ATTENTION| indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE| used to prompt information not related to personal injury
DANGER
This is the DANGER symbol, which indicates an electrical hazard exists which,
if instructions are not followed, will result in personal injury.
WARNING
This is a WARNING symbol, which indicates an electrical hazard exists which,
if instructions are not followed, could result in personal injury.
Attentio
This is the “Attention” symbol. Used to warn you of a potential personal
injury hazard. Observe all safety instructions following this symbol to avoid
injury or death.
Notice
This is the “Notice” symbol, which is used to warn the user of possible risks.
Failure to observe this regulation may result in faulty of device.
2.2 General Safety
This equipment should only be installed, operated, serviced and maintained by
qualified personnel. Qualified person is a person who has skills and knowledge
concerning the construction and operation of electrical equipment, and its
installation, and has received safety training to recognize and avoid the
hazards involved.
There shall be a statement in the instructions that if the equipment is used
in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.
Notice
User modifications and/or repairs are dangerous and will void the warranty and
release the manufacturer from any liability.
Attentio
Product maintenance can only be carried out by our personnel. Unauthorized
opening and improper servicing of the product can result in extensive
equipment damage or possibly personal injury to the user.
In the event of a serious malfunction, discontinue use of the equipment.
Prevent accidental operation of the device. If repairs are required, please
return the device to your local representative or sales office.
It is the operating company’s responsibility to comply with locally applicable
safety regulations.
Store unused equipment in its original packaging. This provides the best
protection against impact and moisture for the device. Please ensure that the
ambient conditions comply with this relevant regulation.
2.3 Special Safety
WARNING
A process started in an uncontrolled manner may endanger or be exposed to
other equipment, therefore, before commissioning, make sure that the use of
the equipment does not involve risks that may endanger other equipment or be
endangered by other equipment risks of.
Power Supply
This device can only be operated with a current source of limited power, that
is, the power supply must have overvoltage and overcurrent protection
functions. In order to prevent the power failure of this equipment, affecting
the safety of other equipment;
or the failure of external equipment, affecting the safety of this equipment.
Product Overview
The IO-Link master establishes the connection between the IO-Link device and
the automation system. As an integral part of the I/O system, the IO-Link
master station is either installed in the control cabinet, or directly
installed on site as a remote I/O, and
its encapsulation level is IP65/67.
❖ Designed for industrial environments, it is a system applied to automated
lines.
❖ Compact structure, suitable for usage scenarios with limited installation
conditions.
❖ IP67 high protection level, anti-interference design, suitable for demanding
application environments.
As a special reminder, IP rating is not part of UL certification.
Technical Parameters
4.1 ULK-EIP-4A4BP6
4.1.1 ULK-
EIP-4A4BP6 Specification
The technical specifications of ULK-EIP-4A4BP6 are as follows:
10-Link Master 1P67 U LK- E1P-4A4B P6
4xCLASS A 4xCLASS B| Ethernet/ IP
---|---
Basic Panuneters
liaising Material| Alumna Alloy
lousing Color| Metallic Silva
Protection Level| 1P67.epoxy MI potting
Ihninsiont (Wx11210)| 205reans60mnix34.4mm
Writ*| 515g
Operating lemperature| -25T.70T
Morns Tamicrature| 40t.85•C
Operating Bunichty| 5%.95%
Storage 1 tumidity| 5%.95%
opciating Attnnplicric Presstac| 80KPa..106KPa
Storage Atmospheric Procure| 801Ch.106KP
Mum&| 0..2000m
Pollution Ikgree| 3
Tightening forqu$110)| M12:0.5Nm
Application Environment| conforms b EN-61131
Vitiation Test| conform to IEC60068-2
Impact rest| conforms so IFC60068-27
Free Drop test| suntans to IEC60068.32
EMC| corium. to IEC610004-2.-3.4
Certification| Cr…R.11S
Mounting llole Sin| s4 5mn. 14)5 .5min. 1
Data Transfer
Connection Type| 24112 Dadc: 4-pin Female
Physical layer| Ethernet
Transfer Kate| 10’100 MINK. Full Duplex
Characteristic| anima to protocol features
Mann Ftmetion| diagnosis alarm process alarm
Min Cycle Tune| Ins
10w-sing lorque(data port)| M12.0.5N5n
Power Supply
Connection Ewe| M12. 5 pins. l.-code. Maki:task
System voltage Us| 18..30 VIX(type .24VDC)
Auxiliary voltage lla| 18…30 VDC(typc.24VDC)
Total (Anent slit| 12A
Static Working Curicsit1C| <150mA
Overvoltagg Protection| VCs
Power Reverie Polarity Protection| Ves
riebnins Torquopowa supply pan)| M12:0.5Nm
10-Link Master IP67
ULK-EIP-4A4BP6
4xCLASS A 4xClASS B| EtherOet/IP
---|---
IO-UNK Parameters
Port Number| 8×10-UNK
IO UNK Connection Type| 0412.Sn-code.femalt
IO-UNIC Version| 1.1
Communication Rate| COM1(4.13flps),COM2(384X8ps),COM1(230.4KBps)
Poet Voltage| type24VDC (follow US)
Port Current| 2A (follow US)
Pon Class| 4 x CLASS& 4 v CLASS 13
Port Maximum Data Length| My’,
Max. Data Transfer Distance| 1100 m
10-UNK Max Distance| s20 m
Digital Input/Output| 4N PNP (selfeadaptive)
Port Parameters (Input)
Input Number| up to 4
Input Port Position| x1…x4
Input Polarity| PNP
Input Signal 0′| low level 0.3-SV DC
Input Signal ‘1’| high level 12-30V DC
Port Parameters (Output)
Output Number| up to 4
Output Port Position| X1…X4
Output Polarity| PNP
Output Current| single channel maximum 2A
Port Protection| poet power short circuit protection (P1N1. P1N3)/ port
overload protection
Load Type| Resistive. Pilot Duty, Tungsten
4.1.2 ULK-EIP-4A4BP6 LED Definition
ULK-EIP-4A4BP6 is shown in the below figure.
Module Indicator
| Status| Solution
PWR| green: normal power supply|
red:power reversed/UA power not connected/too low/high voltage| check power
wiring
IO| green: normal channel signal|
red: port power supply short circuit (2, 3 pins)| check pin 2 and pin 3
LINK| green:normal link but abnormal data| check the network
configuration
yellow flash:normal link and data|
off:no link| check cable/network configuration
MS| red:module failure| check damage/IO-Link device connected or not
green flash:module not configured| check configuration in the program and PLC
download status
NS
| red flash:data interruption| check network cable status
green flash:data not connected
MS/NS| green:normal status|
IO- LINK| green:port running status|
green fast flash:port connecting|
green slow flash:port preoperaion status| pre-operational / port configured
but no device connected
green off:port closed| port not configured
red:power supply short circuit (1, 3 pins)| check whether the 1 and 3 pins are
short circuited
Note: When the Link indicator is always off, if there is no abnormality
in the cable inspection and replacement of other modules, it indicates that
the product is working abnormally.
Please contact the manufacturer for technical consultation.
4.1.3 ULK-EIP-4A4BP6 Dimension
The size of the ULK-EIP-4A4BP6 is 205mm×60mm×34.5mm, including one φ4.5mm and
one φ5.5mm mounting hole, the depth of the mounting hole is 20mm, as shown in
the figure below:
Product Installation
5.1 Installation Precautions
To prevent product malfunction, malfunction, or negative impact on performance
and equipment, please observe the following items.
5.1.1 Installation Site
Notice
Please avoid installing near devices with high heat dissipation (heaters,
transformers, large-capacity resistors, etc.)
Notice
Please avoid installing it near equipment with serious electromagnetic
interference (large motors, transformers, transceivers, frequency converters,
switching power supplies, etc.).
This product uses PN communication.
Radio waves (noise) generated by transceivers, motors, inverters, switching
power supplies, etc. may affect the communication between the product and
other modules.
When these devices are around, it may affect the communication between the
product and the module or damage the internal components of the module.
When using this product near these devices, please confirm the effects before
use.
Notice
When multiple modules are installed close to each other, The service life of
the modules may be shortened due to the inability to dissipate heat.
Please keep more than 20mm between the modules.
5.1.2 Application
DANGER
Do not use AC power. Otherwise, there is a risk of rupture, seriously
affecting the safety of personal and equipment.
Attentio
Please avoid wrong wiring. Otherwise, there is a risk of rupture and burnout.
It may affect the safety of personal and equipment.
5.1.3 Usage
Attentio
Do not bend the cable within a radius of 40mm. Otherwise there is a risk of
disconnection.
Attentio
If you feel that the product is abnormal, please stop using it immediately and
contact the company after cutting off the power.
5.2 Hardware Interface
5.2.1 ULK-EIP-4A4BP6 Interface Definition
Power Port Definition
- ULK-EIP-4A4BP6 Port Definition
The power port uses a 5-pin connector, and the pins are defined as follows:
Port M12 L-code
Female &Male Pin
Definiti on| Connection Type| M12, 5 pins, L-code, Male/Female|
---|---|---|---
System Supply Voltage us| 18…30 VDC (type.24VDC)
Auxiliary Supply Voltage ua| 18…30 VDC (type.24VDC)
Total Current Is| 12A
Total Current la| 12A
Static Working Current lc| 150mA
Power Reverse Polarity Protection| Yes
Tightening Torque (power port)| M12:0.5Nm
|
|
|
|
|
Note: Us is the system power and input power, and Ua is the output power.
The power supply must be a limiting power source or class 2 power supply.
Data Port Definition
The data port uses a 4-pin connector, and the pins are defined as follows:
Data Port Pin Definition
M12
D-code Female| Connection Type| 2 × M12 D-code; 4 pins, Female|
1. TX+
2. RX+
3. TX-
4. RX-
Physical Layer| Ethernet
Transfer Speed| 10/100 Mbps, full duplex
Characteristic| conforms to the protocol features
Alarm Function| diagnostic alarm, process alarm
Min. Cycle Time| 1ms
Tightening Torque (data port)| M12:0.5Nm
|
|
|
|
|
|
IO-Link Port Definition
The IO-Link port uses a 5-pin connector, and the pins are defined as follows:
WARNING
Use Copper Conductors Only.
The maximum input current per port load is 200mA .
The voltage range of the output signal and Ua has always been 18~30Vdc .
5.2.2 ULK-EIP-4A4BP6 Wiring Diagram
- PNP type input signal, that is, the jack is connected to 1 input sensor, which is divided into two-wire sensor and three-wire sensors
- PNP type output signal, that is, the jack is connected to the actuator
- The IO-Link port is connected to the ULK-EIP-4A4BP6 substation. (When the IO-Link device is an input type, the 2 pins allow no wiring.
5.2.3 ULK-EIP-4A4BP6 IO Process Image Area Allocation 8-way IO-Link Interface (4 Class-A, 4 Class-B)
Ether’s: et/P Pro to co 1P rocess 0 ut put Data
Byte| Functipn D escrip tipn
Descrt tiln| BE7 I| BUG 1| BUS| 1 BU4| BE3| 13E2| BIll| BUO
0| Standard I) 0 utput
0= off
1= on| em pty| X4P2| X3P2| X2P2| X 1P2
1| no| reserve| reserve| reserve| reserve| reserve| reserve| reserve| reserve
2-33| port 1 process output data
34-65| port2 process output data
66`97| port3 process output data
98%129| p ort 4 pro cess output data
130-161| pons process output data
162-193| port6 process output data
194-225| port7 process output data
226-257| p ort 8 process output data
EtherN et P Proto co 1Pro cess hputData
Byte| Function D escrttion
D e scrip tip n| BEr| I BIM| I BUS| I BII4| BE3| 8E2| B111| 3E0
0| Stand ard D hput
0= no signal
1= have signal| empty| 14P2| X3P2| X2P2| vh.1P2
1| C lass B pow ersupply shortcituk
0=Ph 2,5 short c itu it 1= non al| empty| port5| port6| port .| pon8
2| Port 1 process com m unicatbn status (0x03 connected, Oxa4 not connected,
Ox00 not configured)
3| Po rt 2 process corn m unicatbn status (0x03 connected, Oxa4 not connected,
Ox00 not configured)
4| Port 3 process corn m unicatbn status (0x03 connected, Oxa4 not connected,
Ox00 not configured)
S| Port 4 process corn m unicatbn status (0x03 connected, Oxa4 not connected,
Ox00 not configured)
6| Pons process com in unicatbn status (0x03 connected, Oxa4 not connected,
Ox00 not configured)
7| Po rt 6 process com in unicatbn status (0x03 connected, Oxa4 not connected,
Ox00 not configured)
8| Port 7 process corn m unicatbn status (0x03 connected, Oxa4 not connected,
Ox00 not configured)
9| Port 8 process com in unicatbn stands (0x03 connected, Oxa4 not connected,
Ox00 not configured)
10-41| port]. process hput data
42-.73| p ort 2 process hput data
74– 105| port 3 process hput data
106137| p ort 4 process hput data
138-‘169| ports process hput data
170– 201| port6 process hput data
Note: When the IO-Link master port is connected to a slave station with
output function, it is necessary to set the Pin2 output point to ON to provide
power for the IO-Link device. Otherwise, the output point of the IO-Link
device will light up in red when outputting.
The information in this document reflects products at the date of printing.
Unitronics reserves the right, subject to all applicable laws, at any time, at
its sole discretion, and without notice, to discontinue or change the
features, designs, materials and other specifications of its products, and to
either permanently or temporarily withdraw any of the forgoing from the
market.
All information in this document is provided “as is” without warranty of any
kind, either expressed or implied, including but not limited to any implied
warranties of merchantability, fitness for a particular purpose, or non-
infringement. Unitronics assumes no
responsibility for errors or omissions in the information presented in this
document. In no event shall Unitronics be liable for any special, incidental,
indirect or consequential damages of any kind, or any damages whatsoever
arising out of or in connection with the use or performance of this
information.
The tradenames, trademarks, logos and service marks presented in this
document, including their design, are the property of Unitronics (1989) (R”G)
Ltd. or other third parties and you are not permitted to use them without the
prior written consent of Unitronics or such third party as may own them.