Installation Parts

Installation

Installation Tool

Name| Drain hose| Clamp metal| Washer for hanging backet| Clamp (Tie Wrap)| Insulation for fitting|

  • (Other)
  • Paper pattern for installation
  • Owner’s manual
  • Installation manual

---|---|---|---|---|---|---
Quantity| 1 EA| 2 EA| 8 EA| 4 EA| 1 SET
Shape| | | | | or gas pipe
for liquid pipe

  • Screws for fixing panels are attached to decoration panel

Safety Instructions

The following safety guidelines are intended to prevent unforeseen risks or damage from unsafe or incorrect operation of the appliance.
The guidelines are separated into ‘WARNING’ and ‘CAUTION’ as described below

This symbol is displayed to indicate matters and operations that can cause risk. Read the part with this symbol carefully and follow the instructions in order to avoid risk.

WARNING
This indicates that the failure to follow the instructions can cause serious injury or death.

CAUTION
This indicates that the failure to follow the instructions can cause the minor injury or damage to the product.

WARNING

Installation

  • Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.

    • There is risk of fire or electric shock.
  • For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.

    • Do not disassemble or repair the product. There is risk of fire or electric shock.
  • Always ground the product.

    • There is risk of fire or electric shock.
  • Install the panel and the cover of control box securely.

    • There is risk of fire or electric shock.
  • Always install a dedicated circuit and breaker.

    • Improper wiring or installation may cause fire or electric shock.
  • Use the correctly rated breaker or fuse.

    • There is risk of fire or electric shock.
  • Do not modify or extend the power cable.

    • There is risk of fire or electric shock.
  • Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.

    • Moisture may condense and wet or damage furniture.
  • Be cautious when unpacking and installing the product.

    • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
  • For installation, always contact the dealer or an Authorized Service Center.

    • There is risk of fire, electric shock, explosion, or injury.
  • Do not install the product on a defective installation stand.

    • It may cause injury, accident, or damage to the product.
  • Be sure the installation area does not deteriorate with age.

    • If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
  • Use a vacuum pump or inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or oxygen, and do not use flammable gases. Otherwise, it may cause fire or explosion.

    • There is the risk of death, injury, fire or explosion.
  • Do not turn on the breaker or power under condition that front panel, cabinet, top cover,
    control box cover are removed or opened.

    • Otherwise, it may cause fire, electric shock, explosion or death.

Operation

  • Do not store or use flammable gas or combustibles near the product.
    • There is risk of fire or failure of product.

CAUTION

Installation

  • Always check for gas (refrigerant) leakage after installation or repair of product.
    • Low refrigerant levels may cause failure of product.
  • Install the drain hose to ensure that water is drained away properly.
    • A bad connection may cause water leakage.
  • Keep level even when installing the product.
    • To avoid vibration or water leakage.
  •  In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
  • If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazrd.
  • This equipment shall be provided with a supply conductor complying with the national regulation.
  • Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.

Installation

Read completely, then follow step by step.

Selection of the best location

  • If the temperature might rise above 30 ℃ or the humidity might rise above RH 80 %, attach the DewProtective kit or use another insulation to the indoor body. h

  Dew Protective kit is sold separately. Use glass wool material or polyethylene foam and make sure at least 10 mm thick.

  • There should not be any heat source or steam near the unit.
  • There should not be any obstacles to the air circulation.
  • A place where air circulation in the room will be good.
  • A place where drainage can be easily obtained.
  • A place where noise prevention is taken into consideration.
  • Do not install the unit near the door way.
  • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
  • The indoor unit must have the maintenance space.

CAUTION

In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti corrosion measures

Please use an annexed sheet or the corrugated cardboard on the bottom of packing as installation sheet.

When using the bottom sheet, please use it after separating the installation sheet from packing of the product floor by using a knife etc as a picture below.

Ceiling dimension and hanging bolt location

  • The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
    dimension
    dimension

CAUTION

  • This air-conditioner uses a drain pump.
  • Install the unit horizontally using a level gauge.
  • During the installation, care should be taken not to damage electric wires.

NOTICE

  1. • Avoid the following installation location.
    1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
    These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
    In these cases, take the following actions;
    • Make sure that ventilation fan is enough to cover all noxious gases from this place.
    • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
    not suck oily steam.
    2. Avoid installng air conditioner in such
    places where cooking oil or iron powder is
    generated.
    3. Avoid places where inflammable gas is
    generated.
    4. Avoid place where noxious gas is
    generated.
    5. Avoid places near high frequency generators.
    dimension
    Installation

Installation

The following parts are local purchasing.

  1. Hanging Bolt – W 3/8 or M10
  2. Nut – W 3/8 or M10
  3. Spring Washer – M10
  4. Plate Washer – M10

CAUTION
Tighten the nut and bolt to prevent the unit from falling

Wiring Connection

  • Connect the wires to the terminals on the control box individually according to the outdoor unit connection.

  • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
    Wiring Connection

  • TQ/TR Chassis• TQ/TR Chassis

  • TM/TN/TP Chassis
    • TM/TN/TP Chassis

CAUTION

After the confirmation of the above conditions, prepare the wiring as follows:

  1. Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover.
  2. Provide a circuit breaker switch between power source and the unit.
  3. The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
  4. Confirm the Specification of power source
  5. Confirm that electrical capacity is sufficient.
  6. Be sure that the starting voltage is maintained at more than 90 % of the rated voltage marked on the name plate.
  7. Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
  8. Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit.
  9. The following troubles would be caused by voltage drop-down.
    • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
    • Proper starting power is not given to the compressor.

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

NOTICE

Refer to the table below when selecting the circuit breaker.

  • * Use the circuit breaker instead of fuse.
    • MFA(Maximum Fuse Amperes) is used to select the circuit breaker and ground fault circuit interrupter.
      Capacity (kBtu/h)| MFA (A)
      ---|---
      5| 15
      7| 15
      9| 15
      12| 15
      15| 15
      18| 15
      21| 15
      24| 15
      28| 15
      30| 15
      36| 15
      42| 15
      48| 15
      54| 15

WARNING

  • Don’t install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
  • Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources .

Installation of Decoration Panel

The decoration panel has its installation direction

Before installing the decoration panel, always remove the paper template.

  1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10 mm in length.) The fixing screws (hexagon M5 screw) are included the indoor unit box.
  2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
  3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge.
  4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
  5. Connect the louver motor connector and display connector.
  6. After tightening these screws, install the air inlet grille (including the air filter).
    Installation of Decoration Panel

** CAUTION
Install certainly the decoration panel. Cool air leakage causes sweating. Water drops fall.
Installation of Decoration Panel
**

Drain Piping

  • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.

  • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.

  • The outside diameter of the drain connection on the indoor unit is  32 mm
    Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings

  • Be sure to install heat insulation on the drain piping
    Heat insulation material: Polyethylene foam with thickness more than 8 mm.

Drain test

The air conditioner uses a drain pump to drain water.\ Use the following procedure to test the drain pump operation:
Drain test

CAUTION
The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

  • Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
  • Feed water to the flexible drain hose and check the piping for leakage.
  • Be sure to check the drain pump for normal   operating and noise when electrical wiring is complete.
  • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit. Installation of Decoration Panel

Attention

  1. Possible drain-head height is up to 700 mm. So, it must be installed below 700 mm.

  2. Keep the drain hose downward up to 1/50~1/100 inclination. Prevent any upward flow or reverse flow in any part.

  3. 5 mm or thicker formed thermal insulator is  provided for the drain pipe.

  4. Upward routing is not allowed.

  5. Be sure to check the drain pump for normal operation and abnormal noise when electrical wiring is complete.

Ceiling Height Selection

The ceiling type indoor unit is available to adjust indoor airflow rate by Installer setting of the wired remote controller for better service. Please select the height level from the below table.

< Ceiling Height Selection Table>

Ceiling Height Selection Level **** Description
1.6~8.3 kW 10.0~14.5 kW
Up to 2.3 m Up to 2.7 m Low

standard level
Above 2.3 m, up to 2.7 m| Above 2.7 m, up to 3.2 m| Standard| Set the indoor airflow rate as standard level
Above 2.7 m, up to 3.1 m| Above 3.2 m, up to 3.6 m| High| Increase indoor airflow rate 1 step from standard level
Above 3.1 m, up to 3.6 m| Above 3.6 m, up to 4.2 m| Super high| Increase indoor airflow rate 2 steps from standard level

Ceiling height of ‘Very high’ function may not exist depending on the indoor unit. For the details, refer to the product manual.

DIP Switch Setting

Indoor Unit

| Function| Description| Setting Off| Setting On| Default
---|---|---|---|---|---
SW1| Communication| N/A (Default)| –| –| Off
SW2| Cycle| N/A (Default)| –| –| Off
SW3| Group Control| Selection of Master or Slave| Master| Slave| Off
SW4| Dry Contact Mode| Selection of Dry Contact Mode| Wired/Wireless remote controllerSelection of Manual or Auto operation Mode| Auto| Off
SW5| Installation| Fan continuous operation| Continuous operation Removal| –| Off
SW6| Heater linkage| N/A| –| –| Off
SW7| Ventilator linkage| Selection of Ventilator linkage| Linkage Removal| Working| **** Off
Vane selection (Console)| Selection of up/down side vane| Up side + Down side Vane| Up side Vane Only
Region selection| Selection tropical region| General model| Tropical model
SW8| Etc.| Spare| –| –| Off

CAUTION
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF

Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start automatically with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.

Specific conditions:

  • All names of the indoor units are ARNU****4.
  • The serial number of Multi V super IV (outdoor units) is after October 2013
    Installation

Group Control Setting

Group Control 1
Wired remote controller 1 + Standard Indoor Units
Group Control Setting
Indoor Unit DIP Switch

DIP Switch in PCB ¿ Master Setting – No. 3 Off
Switch
Slave Setting – No. 3 On
¡ Slave Setting

Some products have no DIP switch on PCB. It is possible to set indoor units to Master or Slave by using the wireless remote controller instead of DIP switch.
For the details of the setting, please refer to the manual of the wireless remote controller.

  1. It is possible to 16 indoor units(Max.) by one wired remote controller. Set only one indoor unit to Master, set the others to Slave.
  2. It is possible to connect with every type of indoor units.
  3. It is possible to use wireless remote controller at the same time.
  4. It is possible to connect with Dry Contact and Central controller at the same time.
    • The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
  5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote controller.
    It is possible to control the other indoor units except the error units.

 It is possible to connect indoor units since Feb. 2009.
It can be the cause of malfuctions when there is no setting of master and slave.
In case of Group Control, it is possible to use following functions.

  • Selection of operation, stop or mode
  • Temperature setting and room temperature check
  • Current time change
  • Control of flow rate (High/Middle/Low)
  • Reservation settings It is not possible to use some functions.

Group Control 2

Wired remote controllers + Standard Indoor Units
Group Control

It is possible to control N indoor units by wired remote controller M units. (M + N ≤ 17 Units) Other than those, it is same with the Group Control 1.

Group Control 3

Mixture connection with indoor units and Fresh Air Intake Unit
Group Control

In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake Unit with standard units. (Because setting temperature are different.)
Other than those, it is same with Group Control 1. Group
Control

Remote Control

Wired remote controller 2 + Indoor unit 1
Remote Control

  1. It is possible to connect two wired remote controllers with one indoor unit.
  2. Every types of indoor unit is possible to connect two remote controller.
  3. It is possible to use wireless remote controller at the same time.
  4. It is possible to connect with Dry Contact and Central controller at the same time.
  5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote controller.
  6. There isnʼt limits of indoor unit function.
    **** Maximum 2 wired remote controllers can be connected with 1 indoor unit.

Accessories for group control setting

It is possible to set group control by using below accessories.

Accessories for group control setting

CAUTION

  • Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum cable usage.

Model Designation

  • Serial Number
  • Combinations of functions A/B: Basic function C/D: Plasma Ceiling Cassetle)
  • Chassis Name
  • Electrical Ratings 3:10, 208/230 V, 60 Hz G:10, 220-240 V, 50 Hz/10, 220 V, 60 Hz (Only 50 Hz for Australia)
  • Total Cooling Capacity in Btu/h EX) 5 000 Btu/h 05 18 000 Btu/h ’18’
  • Combination of Inverter Type and Cooling Only or Heat Pump N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O
  • MULTIV. System with Indoor Unit using R410A ****LGETAU Ex) URN

Airborne Noise Emission

The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required. Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to  thenoise. Also, the permissible exposure level can vary from country to country. This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.

Limiting concentration

Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m3 (Freon gas weight per unit air volume) for facilitating calculation

Limiting concentration: 0.44 kg/m3 (R410A)

Calculate refrigerant concentration
Refrigerant concentration = Total amount of replenished refrigerant in refrigerant facility (kg) Capacity of smallest room where indoor unit is installed (m3 )