Precision GP5PL Phoenix Phase Converters User Manual
- June 16, 2024
- PRECISION
Table of Contents
- Precision GP5PL Phoenix Phase Converters
- Product Information
- Product Usage Instructions
- Breaker and Fuse Sizes
- READ FIRST – BEFORE INSTALLATION
- Power requirements
- Mounting the Phase Converter Panel
- FAQ
- Q: What wire size should I use for single-phase connections?
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Precision GP5PL Phoenix Phase Converters
Product Information
Specifications
- Model: GP5PL VER 1.1.0
- Power Requirements: Single Phase
- Idler Motor: 5 HP
Product Usage Instructions
Power Requirements
Before installation, it is important to verify the KVA size of the transformer with your electric company. The KVA number should be larger than the HP of the idler motor.
Checking Connections
Ensure that all connections, including factory connections to the power block, are secure. It is recommended to recheck connections after a few weeks of using the converter.
Understanding Speed and Shutdown
If you experience any issues with the speed of the phase converter, it is important to shut it down immediately. Failure to do so may result in damage to the idler motor, which will not be covered under warranty. If you are unsure, please contact us or a qualified electrician for assistance.
Breaker and Fuse Sizes
For motors, it is recommended to double the amp size of the machine when
selecting a breaker. For example, if the equipment pulls 20 amps, use a 40 amp
breaker. When running multiple machines simultaneously, calculate the
total amps by adding the amp size of the largest machine to the lamps of the
other machines. For example, if you have a 20 AMP lathe, a 9 amp saw, and a 6
amp milling machine, the calculation would be: 20 X 2 = 40 + 9 + 6 = 45 amps.
In this case, use the next standard size breaker, which would be a 50 Amps
two-pole breaker.
For rural areas, it is recommended to increase the minimum size breaker by 20%.
Wire and Breaker Sizes
For single-phase connections:
- 8 AWG Copper should be used for distances under 50 feet.
- Idler motor wire should be 10 AWG copper.
- The breaker/fuse size should be 15 amps minimum and 30 amps maximum.
Connecting the Idler Motor Wires
Refer to the illustrations provided in the manual for connecting the idler motor wires. Do not use wire nuts; instead, use bolt-down lugs.
Installation by a Licensed Electrician
The installation of the product must be carried out by an industrial licensed electrician. Ensure that the motor load breaker is sized twice the full load amps of your equipment.
For PL and PH models, connect the idler motor wires as follows:
- Lead 1,7 to L1
- Lead 2,8 to L2
- Lead 3,9 to L3
- Lead 4,5,6 together
For single-phase circuit breaker panels, a disconnect should be used if the run is over 50 feet.
For NL and PL models (low voltage), use a 230V connection. For NH and PH models (high voltage), use a 460V connection.
READ FIRST – BEFORE INSTALLATION
-
Most important step to know.
-
NEVER Start the phase converter with a load, this includes transformers.
-
Make sure you have the incoming service to start the phase converter, call your electric company verify the KVA size of the transformer, that KVA number should be larger then the HP of the idler motor.
-
DO NOT use WIRE NUTS for any connection, use the bolt down lugs.
Check all make sure all connections even factory connections to the power block are secure, also recheck connections after a few week of using the converter. -
When powering up the unit, if the idler does NOT come up to FULL SPEED, then shut the phase converter down right away. If you don’t understand then call us or a qualified electrician. if you do not turn the unit off you have a chance to damage the idler motor that will not be covered under warranty.
-
Must be installed by a license industrial electrician, our guidelines are not to supersede local and state laws.
Power requirements
- You will need to use a motor load type breaker. NOT a quick blow or trip breaker.
- Sizing a breaker for a single machine with an inductive load (motors) double the amps size of the machine. Example if the equipment pulls 20 amps use a 40 amp breaker.
- Sizing the equipment for multiple machine double the amp of the largest machine and add the the other machine that will run at the same time. Example; 20 AMP Lathe. 9 amp saw, 6 amp milling machine. 20 X 2 = 40 +9 + 6 = 45 amps, use the next standard size breaker which would be 50 Amps two pole breaker.
- Use the chart to make sure you don’t go over or under the Minimum and maximum size allowed. For rural areas increase the minimum size breaker by 20% Click on the next picture to see this chart.
Mounting the Phase Converter Panel
Mount the enclosure first, to a non-vibrating surface, there are two options provided for mounting, next install the back plate with the four nuts provided. Mounting the phase converter panel near the breaker panel is recommended the larger wire is your single phase line, so that is best to keep it as short as possible. Every 50 feet you will need to increase the size of the single-phase wire.
FAQ
Q: Can I install the product myself?
A: No, the product must be installed by an industrial-licensed electrician.
Q: What is the power requirement for the idler motor?
A: The idler motor is a 5 HP motor.
Q: What wire size should I use for single-phase connections?
A: For distances under 50 feet, use 8 AWG copper wire. For the idler motor, use 10 AWG copper wire.
References
- Autodesk A360
- Autodesk A360
- 100 MFD Round Motor Run Capacitor (370V) – Phoenix Phase Converters
- 630-750 MFD - 250V Start Capacitor – Phoenix Phase Converters
- CONTACTOR 3 POLE 60 AMPS 208/240 COIL VOLTAGE – Phoenix Phase Converters
- Potential Relay 90-66 | Phoenix Phase Converters
- Power Block fit 25 HP to 40 HP Rotary Phase Converters – Phoenix Phase Converters
- Start Capacitor – Phoenix Phase Converters
- Two Pole Contactor 230 Volts - 30 Amps | Phoenix Phase Converters
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>