HUAWEI FusionPower UPS5000-A Series Tower UPS User Manual
- June 16, 2024
- Huawei
Table of Contents
HUAWEI FusionPower UPS5000-A Series Tower UPS User Manual
Introduction
The UPS5000-A (30-120kVA) is an online, double-conversion, and tower/ rack convertible UPS that Huawei has launched. It usesthe digital signal processing (DSP) technology to output pure and stable sine wave with a voltage of 380/400/415 Vac. With comprehensive reliability assurance measures and other leading technologies, the UPS5000-A (30-120kVA) can provide reliable, economical, intelligent, and convenient solutions to medium power scenarios.
UPS5000-A-30/40K
Scenarios
- Small and medium-sized data centers
- Telecom and Internet switch rooms
- Equipment rooms of branch offices in sectors such as finance
- Infrastructures, such as control equipment rooms, wireless systems, etc.
Features
Reliable
- Wide input voltage range to minimize battery use: 485-305 Vac for 100% load; 305-138 Vac for 100%-40% load (derating linearly).
- High output power factor of up to 1 (30/40/80kVA), 30% more load driven than traditional UPS.
Efficient
- High efficiency at online mode of up to 95.7%, reducing power consumption of UPS and cooling equipment effectively.
Simple
- Rack/tower convertible, suitable for different installation scenarios
- Flexible battery configuration: 30-44 batteries per string allow customers to get the faulty battery out instead of replacing it.
UPS5000-A-60/80/120K
Specifications
Rated Capacity (kVA/kW)| 30kVA/30kW| 40kVA/40kW|
60kVA/54kW| 80kVA/80kW| 120kVA/108kW
---|---|---|---|---|---
| Input Wiring| 3Ph+N+PE
Rated Voltage| 380/400/415Vac
Mains| Voltage Range| 138-485Vac
Input| Frequency Range| 40-70Hz
Total Harmonic Distortion| THDi<3% for 100% linear load
Input Power Factor| 0.99
Bypass Input| Input Wiring| 3Ph+N+PE
Rated Voltage| 380/400/415Vac
Input Frequency| 50/60±6Hz
Battery| Rated Voltage| 360-528Vdc (The number of batteries can be selected
from 30 to 44; 30/40/80kVA 32 batteries in default, 60/120kVA 40 batteries in
default)
Output| Output Wiring| 3Ph+N+PE
Rated Voltage| 380/400/415Vac±1%
Frequency| Tracking the bypass input (Normal mode); 50/60Hz±0.05% (Battery
mode)
Waveform| Sine wave (THDv<1% for 100% linear load)
Overload Capacity| 30/40/80kVA: 110% overload for 60 min; 125% overload for
10 min; 150% overload for 1 min60/120kVA: 110% overload for 60 min; 125%
overload for 10 min; 150% overload for 0.5 min
System| Output Power Factor| 30/40/80kVA: 1; 60/120kVA: 0.9
Efficiency| Up to 95.7%
Expandability| Up to 8 units connected in parallel
Enviro- nment| Operating Temperature| 0-40ºC
Storage Temperature| -40 to 70ºC
Relative Humidity| 0%-95% (No condensing)
Operating Altitude| 0-1000m. Above 1000m, derating rate based on EN/IEC
62040-3
Audible Noise| 58-64dB
Others| Height×Width×Depth (mm)| 500 × 264 × 800| 1020 × 440 × 850
Weight| 70kg| 140kg| 170kg
Certifications| EN/IEC 62040-1; EN/IEC 62040-2; EN/IEC 62040-3; CE;CB; RoHS,
REACH,WEEE,etc.
Communications| Dry contacts, RS485, SNMP
Remark: For important systems that are related to important economic interests or public security, such as civil aviation management center, financial clearing center, and trading center, the Tier IV or Tier III power supply level specified in TI942 must be used. That is, two UPSs form dual-bus power supply or the UPS and mains form dual-bus power supply.
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>