AQUA-PAK IOM7203 AC ECW Space Constrained Air Conditioners with Hot Water Heating Installation Guide

June 16, 2024
AQUA-PAK

AQUA-PAK IOM7203 AC ECW Space Constrained Air Conditioners with Hot

Water Heating

SAFETY CONSIDERATIONS

  1. READ THE ENTIRE MANUAL BEFORE STARTING THE INSTALLATION.
  2. These instructions are intended as a general guide and do not supersede national, state, or local codes in any way.
  3. Altering the product, improper installation, or the use of unauthorized factory parts voids all warranty or implied warranty and may result in adverse operation and/or performance or may result in hazardous conditions to service personnel and occupants. Company employees or contractors are not authorized to waive this warning.
  4. This product should only be installed and serviced by a qualified, licensed, and factory-authorized installer or service agency.
  5. All “kits”, parts, and “accessories” used must be factory-authorized when modifying this product. Refer to and follow the instructions packaged with the kits or accessories when installing.

RECOGNIZE THE FOLLOWING SAFETY NOTATIONS THROUGHOUT THIS MANUAL AND POSTED ON THE EQUIPMENT:

WARNING

  • Indicates a potentially hazardous situation or unsafe practices that could result in severe personal injury or death and/or damage to property.
  • ELECTRIC SHOCK HAZARDS identifies  potential electrical shock hazards that could result in personal injury or death.

CAUTION

Indicates a potentially hazardous situation that may result in minor or moderate personal injury.

IMPORTANT

Suggests important procedure steps to ensure proper installation, reliability, or operation.

MODEL NOMENCLATURE

Figure 1 – Model Nomenclature

GENERAL INFORMATION

The Eco-series AQUA-PAK models are a space-constrained package air- conditioning unit with integrated hydronic hot water coils. The unit is tested to AHRI 210/240 2023 and is in compliance with UL 1995 Rev 5. These instructions are given for the installation of the Eco Series AQUA-PAK specifically. For any other related equipment, refer to the appropriate manufacturer’s instructions.

CAUTION

DO NOT use units during any phase of construction. Mechanical components and filters can become clogged with dirt and debris, which can cause damage to the system.
The manufacturer does not warrant equipment subjected to abuse. Construction debris can void warranties and liability for equipment failure, personal injury, and property damage.

WARNING

ELECTRIC SHOCK HAZARD
ALWAYS turn off all power to the unit before servicing equipment. There may be more than one disconnect switch. All lockout/tag-out procedures should be followed. Electrical shock can cause personal injury or death.

NOTE

Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. Upon receipt, a visual inspection of all cartons should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery receipt in the presence of the carrier’s representative. If damage is found, a claim should be immediately filed against the carrier.

CAUTION

Extreme caution must be taken to ensure that no internal damage will result from screws that are drilled into the cabinet.

UNIT OPERATION

Unit Operating Range °F [°C]

Condition| Cooling
Min| Max
Outdoor DB| 60 [15.6]| 115 [46.1]
Indoor DB| 60 [15.6]| 90 [32.2]
Table 1 – Unit Operating Range

Note:

  1. Operating ranges based on standard installation with “0” external static and standard Louvers. Operation with non-standard louvers may lower the unit operating range.

STORAGE

Equipment should be stored in a clean dry, conditioned area with maximum temperatures up to 120°F [48.89°C] and minimum temperatures to 32°F [0°C]. Units should be stored upright and in an indoor environment. It is recommended to leave packaging on the unit until the installation is to begin.

WARNING

Stacking the AQUA-PAK systems is strictly prohibited. Failure to follow this directive may result in system and/or property damage.  DO NOT operate units during the construction process. Mechanical components and filters could become clogged with dirt and debris, which can cause damage to the system. The manufacturer does not warrant equipment subjected to abuse. Construction debris can void warranties and liability for equipment failure, personal injury, and property damage.

UNIT INSPECTION CHECKLIST

Before preparing the unit for installation, complete the inspection procedures below.

  1. Visually inspect the unit for any shipping damage. Damage must be reported immediately to the shipping company to make a claim.
  2. Ensure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report.
  3. Verify that unit nameplates on the data label match the sales order or bill of lading (including, unit configuration, size, and voltage).
  4. Immediately before installation, remove the unit’s front panel and verify that all electrical connections are tight and that there are no loose wires.
  5. Verify that the refrigerant piping is free from any kinks and there is no interference between unit piping and sheet metal or electrical wires.
  6. Remove the blower access panel and remove the Styrofoam packaging mount underneath the blower.
  7. Check that the blower spins freely within the housing and there are no obstructions between the wheel and the housing. The wheel can sometimes come loose in shipping.
  8. Ensure that evaporator distributor tubes are not touching one another and that they are over the drain pan.
  9. Check the air-coil fins for any damage during shipping.
  10. Ensure that shipping brackets and screws are removed from the condensing section. Refer to Figure 2 – Shipping Bracket Removal

NOTE

Check the unit nameplate for the correct voltage with the plans before installing the equipment. Ensure that all electrical ground, connections are made in accordance with local code.

NOTE

Remove the Styrofoam shipping block supporting the blower assembly.

Figure 2 – Shipping Bracket Removal

ECW UNIT DIMENSIONAL DATA

DIMENSIONAL DATA| | | | | | | | |
---|---|---|---|---|---|---|---|---|---
MODEL| A| B| C| D| E| F| G| H| I| J| K| L| M| N
CABINET DIMENSIONS| SUPPLY CONNECTIONS| |
ECW09| 71.5| 34.9| 36.9| 38.9| 1.4| 23.6| 20.9| 16| 12.6| 12.3| 4.2| 20.1| 38.2| 1.6
ECW12| 71.5| 34.9| 36.9| 38.9| 1.4| 23.6| 20.9| 16| 12.6| 12.3| 4.2| 20.1| 38.2| 1.6
ECW18| 71.5| 34.9| 36.9| 38.9| 1.4| 23.6| 20.9| 16| 12.6| 12.3| 4.2| 20.1| 38.2| 1.6
ECW24| 71.5| 34.9| 36.9| 38.9| 1.4| 23.7| 26.9| 16| 12.6| 12.3| 4.2| 20.1| 38.2| 1.6
ECW30| 71.5| 34.9| 36.9| 38.9| 1.4| 23.7| 26.9| 16| 12.6| 12.3| 4.2| 20.1| 38.2| 1.6
Table 2 – ECW Dimensional Data

UNIT PHYSICAL DATA

PHYSICAL DATA AQUA-PAK

AQUA-PAK Model| ECW092B| ECW122B| ECW182B| ECW242B| ECW302B
Compressor (Quantity)**| Rotary (1)| Scroll (1)


Factory Charge (R410A) lb. [kg]

| 3.4 [1.53]| 4.1 [1.85]| 5.2 [2.36]| 5.3 [2.39]| 5.5 [2.48]
ID MOTOR
Motor (Quantity)| 1| 1| 1| 1| 1
Fan Motor Type| ECM| ECM| ECM| ECM| ECM
Motor HP| 1/4| 1/4| 1/3| 1/3| 1/2
OD MOTOR
Motor (Quantity)| 1| 1| 1| 1| 1
Fan Motor Type| ECM| ECM| ECM| ECM| ECM
Motor HP| 1/4| 1/4| 1/4| 1/4| 1/3
ID BLOWER
Blowers (Quantity)| 1| 1| 1| 1| 1


Blower Wheel Size (D x W) in. [cm]

| 6 x 4 [15.2 x 10.16]| 6 x 4

15.2 x 10.16]

| 10 x 4 [25.4 x 10.16]| 10 x 4 [25.4 x 10.16]| 10 x 4 [25.4 x 10.16]
EVAPORATOR COIL


Dimensions (H x W) in. [cm]

| 24 x 16 [61 x 41]| 24 x 16 [61 x 41]| 24 x 16 [61 x 41]| 24 x 22 [61 x 56]| 24 x 22 [61 x 56]
Face Area ft² [m²]| 2.6 [0.24]| 2.6 [0.24]| 2.6 [0.24]| 3.6 [0.33]| 3.6 [0.33]
Rows| 2| 3| 4| 4| 4
OD COIL


Dimensions (H x W) in. [cm]

| 26 x 16.5 [66 x 42]| 26 x 16.5 [66 x 42]| 26 x 16.5 [66 x 42]| 26 x 22.5 [66 x 57]| 26 x 22.5 [66 x 57]
Face Area ft² [m²]| 2.9 [0.27]| 2.9 [0.27]| 2.9 [0.27]| 4.1 [0.38]| 4.1 [0.38]
MISCELLANEOUS


Throwaway Filter Dim. in. [cm]

| 24 x 24 [61 x 61]| 24 x 24 [61 x 61]| 24 x 24 [61 x 61]| 24 x 24 [61 x 61]| 24 x 24 [61 x 61]
Throwaway Filter Quantity| 1| 1| 1| 1| 1
Operating Weight lb. [kg]| 288 [131]| 289 [131]| 290 [131]| 305 [138]| 315 [142]
Packaged Weight lb. [kg]| 310 [141]| 310 [141]| 310 [141]| 325 [147]| 335 [152]
Table 3 –ECW PHYSICAL DATA

ELECTRICAL DATA

ECW ELECTRICAL DATA (208/230-1PH-60HZ)


Model Number

| COMPRESSOR| OUTDOOR MOTOR| INDOOR MOTOR| MIN. CIRCUIT

AMPACITY (MCA)

| MAX. OVERCURRENT

PROTECTION (MOP)


RLA

| ****

LRA

| ****

FLA

| ****

HP

| ****

FLA

| ****

HP

| CIRCUIT 1 (L1-L2)| CIRCUIT 1 (L1-L2)
240V| 208V| 240V| 208V
ECW092RB| 4.4| 20| 2.3| 1/4| 2.3| 1/4| 11.3| 11.3| 15| 15
ECW122
RB| 4.7| 26| 2.3| 1/4| 2.3| 1/4| 11.6| 11.6| 20| 20
ECW182RB| 9| 56| 2.3| 1/4| 2.8| 1/3| 17.6| 17.6| 30| 30
ECW242
RB| 10.1| 62| 2.3| 1/4| 2.8| 1/3| 19.0| 19.0| 30| 30
ECW302*RB| 12.8| 65| 2.8| 1/3| 4.1| 1/2| 24.6| 24.6| 40| 40
Table 4– ECW Electrical Data Table

Notes

  1. ECW models use single-point power for unit operation
  2. Refer to wiring diagrams for additional details
  3. Wire size should be determined in accordance with National Electric Codes
  4. Unit are rated for 208/230V, but MOP, and MCA values are calculated at 208/240V
  5. For all models, the minimum voltage is 197V. Maximum voltage is 252V

INSTALLATION

INSTALLATION PRECAUTIONS

CAUTION

Always wear all appropriate personal protection equipment when installing and servicing units.

WARNING

Use multiple people to team lift when moving and installing these units. Failure to properly lift units may result in personal injury or death.

CAUTION

Contact with metal edges and corners can result in personal injury. Protective gloves should be worn when handling. Exercise caution when installing and servicing unit.

Observe the following precautions for typical installation.

  • Always use proper tools and equipment
  • No wiring or any work should be attempted without first ensuring the unit is completely disconnected from the power source and locked out. Also, verify that a proper permanent and uninterrupted, ground connection exists prior to energizing power to the unit.
  • Review unit nameplate and wiring diagram for proper voltage and control configurations. This information may vary from unit to unit.
  • Units must be installed leveled to ensure proper drainage and operation.
  • Be sure that the drain pan is free from foreign material prior to starting up.

CAUTION

Components rotate at high speeds when the unit is in operation.

  • Check filter media installation to ensure that it is installed correctly. Use the directional arrows or other information on the filter to determine the proper flow direction.
  • Ensure the air distribution system does not exceed the external static rating of the unit.

WARNING

When soldering and brazing, it is recommended that fire extinguishers be available. When soldering and brazing close to valves or sensitive components, heat shields or wet rags are required to prevent damage to the valves or components.

NOTE

Insulation is installed in the unit to provide a barrier between varying atmospheres outside and within the unit. If insulation is damaged condensation can occur and can lead to corrosion, component failure, and possible property damage. Damaged insulation must be repaired prior to the operation of the unit. Insulation will lose its effectiveness and value when wet, torn, separated, and/or damaged.

CAUTION

When servicing this equipment, ensure that the expansion device, filter drier and other components are specifically designed for R-410A refrigerant. ONLY USE service equipment specifically designated for use with R-410A.

WARNING

R-410A can become combustible if mixed with air at elevated temperature and/or pressure. Failure to observe this warning may result in property damage, personal injury, or death.

UNIT LOCATION

The AQUA-PAK AC is designed for through-the-wall installation. The interior portion of the unit is surrounded by a closet with a rear access Figure 5. The vertical discharge allows for ducting to the top of the room for best air circulation and elimination of cold drafts on occupants. Provisions should be made to allow access to the indoor side of the unit for installation and inspection. The closet or access panel opening must be centered with the exterior wall opening and must me large enough to accommodate the installation of the AQUA-PAK Sleeves. 3-in. of unobstructed clearance must be maintained around the AQUA-PAK AC chassis on all sides for adequate airflow to achieve optimum performance. These guidelines give minimum spacing requirements only. It is acceptable to go beyond these limits at any time. At least 27 in. of unobstructed space should be provided in front of the access door to permit removal of the unit, should repair and inspection be required.
The installer must adhere strictly to all local and national code requirements pertaining to the installation of this equipment. All units are designed for indoor use only and are agency-listed for installation with clearances specified in Table 5 – Clearance Requirements. This includes the cabinet, discharge plenum, and connecting ducts.

NOTE

  • Do not locate two units adjacent to each other on an inside corner or where they may exhaust into each other.
  • The AQUA-PAK units are designed for quiet operation. However, all air conditioning equipment will transfer a level of noise to the conditioned space. This should be considered when planning the location of the equipment.
  • The Architectural Grille must be installed prior to the installation of the AQUA-PAK AC unit into the sleeve.

UNIT CLEARANCE REQUIREMENTS

Service clearance must be provided for future maintenance and service. A minimum of 29 in. [73.66 cm] The open area must be left unobstructed in front of the access panels. The grille side must be kept free from any obstructions to airflow. The unit must be installed at least 4 feet [1.22m] from electric meters, gas meters, regulators, and relief equipment.

CLEARANCE REQUIREMENTS

MINIMUM CLEARANCE| INCHES| CM
Horizontal distance between units| 12| 30
Vertical distance between units| 60| 152
Distance above ground level| 6| 15
Distance above the finished floor| 6| 15
Distance above a garage floor| 18| 46
Table 5 – Clearance Requirements

Figure 3 – Clearance Requirements

WALL SLEEVE INSTALLATION

Refer to installation instructions packed with the wall sleeve to assemble and mount into the wall. Before unit installation, verify that sleeve components are not damaged and that the drain line is unobstructed and free of leaks. Check all seals to ensure that they are in position and un-damaged. Ensure that the wall sleeve is sloped toward the exterior of the building. Securely fasten the Architectural grille to the front of the sleeve using the supplied hardware.

Figure 4 – Wall Sleeve Mounting

IMPORTANT

  • After sleeve installation, ensure that the gap in-between the wall and seal is insulated and is in contact with the sleeve sides.
  • Apply a high-grade non-hardening sealant approved for the exterior at the following locations to prevent air and water from migrating inside:
    • Between the edge of the sleeve and the structure
    • On the inside/outside walls.
  • Units are ONLY intended for indoor installation applications.

Figure 5 – Rear Sleeve Installation

Figure 6 – Side Sleeve Installation

  • A” CabientSleeve rough-in opening is 43-1/2 in. (H)[110.49 cm] x 26-3/4 in. (W) [67.94 cm].
  • B” CabientSleeve rough-in opening is 43-1/2 in. (H)[110.49 cm] x 26-3/4 in. (W) [67.94 cm].
  • The bottom of the opening should be approximately 6 in.[15.24 cm] above the floor.

IMPORTANT

Sleeve should be installed in the exterior wall before constructing closet

NOTE

  • Additional insulation is required on the internal condensate connections whenever the unit is operated in an area subject to freezing temperatures.
  • Locate the unit in an area that provides minimum clearance to all service access panels. Consider all additional clearances needed for water connections, electrical connections, duct connections, and sufficient return airflow.

PACKAGED UNIT INSTALLATION

  1. Before installing the unit in the sleeve be sure to go through the unit inspection check-list
  2. Open the rear access door to grab loose items such as an electrical disconnect.
  3. Ensure that properly sized ductwork is in place to match the connections on the AQUA-PAK.
  4. Ensure that the wall sleeve is installed correctly into the wall and is secured before installing the unit. Also, ensure that the sleeve has the proper slope towards the exterior of the building.
  5. ter removing the construction debris guard, check the bottom of the sleeve pan to ensure that it is sloped toward the building exterior. Ensure that the bottom of the pan and drain are clear of obstruction and are operational.
  6. Slide the unit onto the sleeve and push from the bottom until the front of the unit is aligned with the front of the sleeve.
  7. Inspect the sleeve seal to ensure that it is properly secured and aligned.
  8. Use a high-grade non-hardening sealant to close any gaps that may exist between the seal and the wall of the sleeve.
  9. Check that the unit is completed and settled on all four sides against the wall sleeve and seals.

NOTE

The unit is fully engaged in the sleeve if the top sleeve is in contact with the blower section of the unit. The condensing section should sit 3.5” deep into the sleeve.

CAUTION

If the unit is not sealed properly, water and/or outside air will infiltrate the closet which may cause improper unit operation and can cause damage to the unit and/or property.

Figure 7 – Small Cabinet Installation

Figure 8 – Large Cabinet Installation

DUCTWORK

Discharge ductwork is normally used with these units. When return air ductwork is required, the unit is supplied with 1 in. [5.08 cm] thick filter rack/duct collar for connection of return air ductwork. All ductwork must be installed following the National Fire Protection Assoc. Codes 90A and 90B. Supply and Return ducts must be sized properly so as to not exceed the static pressure capabilities of the unit. Ducts should be adequately insulated to prevent condensation and to minimize heat loss. A flexible connector is recommended for supplying air connections on metal duct systems.

DISCHARGE DUCTING

All Ductwork must conform to industry standards of good practice as described in the ASHRAE System Guide. The transition piece from the unit discharge to the duct distribution system must not have an angle greater than 30° or severe loss of air performance can result. Do not connect the full duct size to the unit discharge collar without using a transition piece down to the size of the unit discharge collar. With metal material, the sides of the elbow and the entire branch duct should be internally lined with acoustic insulation for sound attenuation. The ductwork should be configured such that there is no line of sight between the unit discharge and the distribution diffusers.

RETURN AIR DUCTING

Return air duct can be brought in through a wall grille and then to the unit. The return duct system will normally consist of a flexible connector at the unit and a trunk duct to the return air grille. With metal duct material, the return air duct should be internally lined with acoustic insulation for sound attenuation. A 1 in. [5.08 cm] air duct collar flange is included on the filter rack for ducted return air application. A flexible duct collar can then be attached between a duct transition and the return air ductwork. The return air duct transition must be the same size as the return air coil face area. Be sure to allow for proper clearance to allow for filter changeouts.
CONDENSATE DRAIN

AIR FILTER

All indoor return air must be filtered. The preferred methods are listed below.

  1. Use the factory-supplied filter kit which attaches to the inlet of the evaporator.
  2. Use the filter kit supplied with the access panel which accepts a 24 in. [60.96 cm] x 24 in. [60.96 cm] x 1 in. [2.54 cm] throwaway type of filter.
  3. Any field installation of an air filter, means must be provided, for use of a disposable filter that is no smaller than the face area of the evaporator coil.

Figure 9 – Air Filter Installation

FRESH AIR VENT

The AQUA-PAK units come standard with an option fresh-air vent that can be used to provide ventilation to the conditioned space. If the panel is removed, the condenser fan pushes outdoor air into the indoor space. The amount of conditioned air depends on the unit size and cannot be adjusted.

Figure 10 – Fresh Air Vent

The AQUA-PAK is designed so that the wall sleeve is the principal drain pan. Drain tubing is factory installed which drains evaporator condensate though the bottom of the unit which then is allowed to drain into the wall sleeve pan. Condensate drain lines must be installed with adequate slope to ensure positive drainage. Prior to unit installation ensure that the drain is unobstructed and leak-free.

CAUTION

On units with plastic drain pans, the drain connection must be made hand-tight only.

NOTE

While preparing a unit for installation, ensure that the drain tubing from the evaporator is securely attached to the copper nipple in the pan under the compressor. The wall sleeve has a 3/4 in. NPT nipple located in the bottom for connection to a drain. A trap is required in the condensate drain line from the wall sleeve to prevent sewer gas from escaping into the room.

ECW PIPING PRECAUTIONS

  1. Flush all field water piping prior to connections to remove all debris

  2. Use wet cotton rags to cool valve bodies when soldering

  3. Open all valves (mid-way for hand valves, manually open on motorized valves) prior to soldiering

  4. When soldering to bronze or brass, heat the piping while in the socket/cup and begin introducing the solder

  5. Heat can only be applied to the cup of the valve body for a minimal time before damage occurs (even with the use of wet rags).

  6. Avoid rapid quenching of solder joints as this will produce joints of inferior quality

  7. Provisions must be made for the expansion and contraction of piping systems. All horizontal and vertical risers, including runouts, must be able to withstand significant movement with
    temperature changes. Failure to do so will result in damage and failure of piping, fittings, and valves throughout the building.

  8. Never insulate the heads or motorized portion of control valves. Damage can occur in the form of excessive heat build-up and interference to the operation and moving parts will result.

  9. All piping made in the field should be installed with consideration of additional space for any electrical routing that may be required.

  10. Connect all piping per accepted industry standards and observe all regulations governing the installation of piping systems.

  11. When all connections are complete, pressure test system. Repair any solder joint leaks and gently tighten any leaking valve packing nuts and piping accessories, as required

CAUTION

Hydronic systems are not designed to hold pressurized air and should only be tested with water. Pressurizing the system with air could damage the equipment

ECW PIPING INSTALLATION

  • All piping must be adequately sized to meet the design water flow requirements as specified for the specific installation. Piping must be installed in accordance with all applicable codes.
  • The piping connections on the equipment are not necessarily indicative of the proper supply and return line sizes. To minimize restrictions, piping design should be kept as simple as possible.

CAUTION

When connecting piping to the ECW unit, do not bend or reposition the coil header tubing for alignment purposes. This could cause the a tubing fracture and result in a water leak.

ELECTRICAL

HIGH VOLTAGE
All wiring must comply with local and national code requirements. Units are provided with wiring diagrams and nameplate data to provide information required for necessary field wiring.

WARNING

  • ELECTRIC SHOCK HAZARD Disconnect all power supplies before servicing. Lock out/tag out to prevent accidental electrical shock . NOTE: There may be multiple power sources supplying the unit.
  • Use copper conductors only. Install all parts and panels before the operation of the unit. Failure to follow these warnings can result in personal injury or death.

Units are provided with a class 2 transformer for 24VAC control circuits. Should any add-on accessory or component also have a class 2 transformer furnished, care must be taken to prevent interconnecting outputs of the two transformers by using a thermostat with isolating contacts.

WARNING

Connect the ground wire to the ground terminal marked “GND”. Failure to properly ground the unit may result in personal injury or death.

CAUTION

Any device that has been furnished by the factory for field installation must be wired in strict accordance with the associated wiring diagram. Failure to properly wire the unit may damage components and void warranties.

208 VOLT OPERATION

All 208-240 Volt units are factory wired for 240 Volt operation. For 208 Volt operation, moving, changing, or rewiring the line voltage tap on the 24 Volt control transformer is required. See note on unit wiring diagram for instructions.

THERMOSTAT REQUIREMENTS

A minimum of a 1C/1H thermostat is required to operate the AQUA-PAK AC. Thermostat connections are as follows:

THERMOSTAT CONNECTIONS KEY

LETTER| COLOR| DESCRIPTION
C| BROWN| Transformer 24VAC Common
R| RED| Transformer 24VAC Hot
G| GREEN| Evaporator Blower
Y1| BLUE| Compressor call
W2| WHITE| First Stage Heating
Table 6 – Thermostat Connections Key

THERMOSTAT INSTALLATION
The Thermostat should be located on an interior wall in a larger room, away from the supply duct draft. Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate mounting holes and drill holes with a 3/16 in. bit. Install supplied anchors and secure plate to the wall. The thermostat wire must be 18 AWC wire.

CONTROLS

ECO SERIES CONTROL MODULE

Figure 12 – ECO Series Control Module

POWER-UP

When power is first applied to the control, all timers are reset. The control will execute a random start delay before allowing normal operation of outputs, and a compressor anti-short cycle delay (6 minutes) before allowing the compressor output to be energized. While the control is operating, all of the inputs are continuously monitored for a change in the desired operating status.

RANDOM START DELAY

There will be a control random start delay which will vary from 10 to 60 seconds, which will be executed before energizing outputs when the control is powered up. All control outputs remain off during the random start delay.

ANTI-SHORT CYCLE DELAY

After the compressor output has been energized the control will execute a 6-minute anti-short cycle delay from the time the compressor is de-energized, before allowing the compressor output to be energized again. A 6-minute anti- short cycle delay will be present at control power-up, before allowing the compressor output to be energized

POWER INTERRUPTIONS

If the power to the control is interrupted for less than 100 milliseconds, the control shall resume operation at the same point in the timing cycle if the compressor output is not energized. Relays may temporarily drop out during the power interruption. Power interruptions greater than 100 milliseconds are to reset the control as a power- sequence. If the power to the control is interrupted for more than 40 milliseconds with the compressor output energized, the compressor output will be de-energized, and the control will execute a short cycle delay before allowing the compressor to operate.

COOLING OPERATION STEADY STATE COOLING

When the “W1/Y” input is present, and the compressor is not being held off by the anti-short cycle timer, the control will operate in steady-state cooling. In steady-state cooling, the compressor and condenser fan are energized. After a 7-second delay, the high-speed evaporator fan is energized. If the W2 input is applied to the control, the first-stage auxiliary heat output will be energized immediately and the second-stage auxiliary heat output will be energized after 15 seconds. The compressor and condenser outputs will be shut off and the evaporator fan will switch to low speed. When the “W2” input is removed, both auxiliary outputs will be turned off immediately, and the control will return to steady-state cooling mode, assuming the “W1/Y” input is still present. When the “W1/Y” input is removed, the compressor and condenser fan will be turned off immediately. The high-speed evaporator fan will be turned off following a 45-second blower-off delay.

LOW AMBIENT SHUTDOWN

When the control is operating in steady state cooling, and the “INDOOR” input is applied (temperature 30°F [-1] and below), the control will immediately de- energize the compressor and condenser fan. The high-speed evaporator will be turned off following a 45-second blower-off delay. The compressor will go into an anti-short cycle delay for 6 minutes
LOW AMBIENT COOLING LOCKOUT

When the control is operating in steady state cooling and the “COOLING LOCKOUT” input is applied (Outside Temperature of 40°F [4.4°C] or less) the control will continue to operate for 10 minutes. After 10 minutes, if the “COOLING LOCKOUT” is still active the cooling operation will be locked out for 30 minutes and run a high-speed evaporator during the lockout. After 30 minutes the control will be returned to normal operation.

AUXILIARY HEATING OPERATION THE THERMOSTAT CALL FOR AUXILIARY HEAT

If the “W2” thermostat input is present without a “W1/Y” input, the control will operate in the auxiliary heat mode. The low-speed evaporator fan and the first-stage auxiliary heat outputs will be energized immediately when the “W2” input is received. After a 15-second staging delay, the second-stage auxiliary heat output will be energized. When the “W2” input is removed, all of the outputs will be turned off immediately.
If the “W2” thermostat input is present with a “W1/Y” input, the control will switch the system to auxiliary heat mode and will de-energize the compressor and condenser fan immediately.
LOW ROOM AMBIENT AUXILIARY HEAT

If the “RS” low room temperature input becomes active (switch closes), the control will operate in the auxiliary heat mode, regardless of any other control inputs. The low-speed evaporator fan and the first-stage auxiliary heat outputs will be energized immediately when the
“RS” input is received. After a 15-second staging delay, the second-stage auxiliary heat output will be energized. When the “RS” input is removed, all of the outputs will be turned off immediately.

FRONT DESK SHUTDOWN OPERATION

If the front desk shutdown input “FD” is removed (switch opens), operation based upon the “W1/Y”, “W2” and “G” thermostat input will be prohibited. Auxiliary heat operation based upon the low room ambient temperature input “RS” is the only heating or cooling operation that will be allowed. When the “FD” input is re-applied (switch closes), the control will return to normal operation based upon the thermostat inputs.

THERMOSTAT INPUT OPERATION (W1/Y, W2)

If both “W1/Y” and “W2” thermostat inputs are active, the control will lock out or interrupt the operation of the compressor.

FIELD SPEEDUP MODE

The field speedup mode is entered by applying R (24VAC) to W1/Y (active) and closing the cooling lockout sensor switch (24VAC applied to the terminal). The field speedup mode is automatically canceled after 5 minutes. While in the filed speedup mode, control timings will be reduced as follows:

  • Random Start Delay: 0 Seconds
  • Short Cycle Delay:5 seconds
  • Cooling Blower off Delay: 0 Seconds
  • Auxiliary Heat Staging Delay :1 Second

BLOWER DATA

ECW AIRFLOWS

ECW BLOWER DATA


MODEL

| Motor Tap| Motor Speed| IWC STATIC PRESSURE
0.10| 0.20| 0.30| 0.40| 0.50
SCFM| W| SCFM| W| SCFM| W| SCFM| W| SCFM| W


ECW0922R

| 1| T1 H| 453| 95| 435| 97| 417| 98| 399| 98| 380| 98
2| T2 C| 352| 58| 334| 60| 316| 60| 298| 60| 279| 60


ECW122R

| 1| T1 H| 510| 128| 493| 127| 474| 127| 456| 126| 437| 125
2| T2 C| 308| 45| 290| 47| 272| 48| 254| 48| 235| 47


ECW1822R

| 1| T1 H| 723| 155| 696| 155| 673| 155| 641| 151| 598| 143
2| T2 C| 723| 155| 696| 155| 673| 155| 641| 151| 598| 143


ECW1823R

| 1| T1 H| 723| 155| 696| 155| 673| 155| 641| 151| 598| 143
2| T2 C| 723| 155| 696| 155| 673| 155| 641| 151| 598| 143


ECW2422R

| 1| T1 H| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213
2| T2 C| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213


ECW2423R

| 1| T1 H| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213
2| T2 C| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213


ECW3022R

| 1| T1 H| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213
2| T2 C| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213


ECW3023R

| 1| T1 H| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213
2| T2 C| 883| 222| 853| 222| 822| 220| 789| 218| 751| 213
Table 7 – ECW BLOWER DATA

C Factory Default Cooling Airflow
H Factory Default Electric Heat and Hot Water AIrflow
T1 is reserved for Fan Only Operation (All models)  Blower performance data is based on a dry coil at 70°F DB EAT with a standard 1″ clean air filter Do not run the unit at higher than .5 IWC For information on how to change the blower speed, review the unit wiring diagram

WARNING

ELECTRIC SHOCK HAZARD High efficiency brushless DC motors are wired with power applied at all times Low voltage thermostat demand and board algorithms will control its use.

WIRING DIAGRAMS

Figure 13 – ECW09-12, 0HTR, 1PS Wiring Diagram

Figure 14 – ECW18, 0HTR, 1PS Wiring Diagram

Figure 16 – ECW30, 0 HTR, 1PS Wiring Diagram

STARTUP INSTRUCTIONS

PRE-STARTUP CHECKS
Before starting, thoroughly check all the components. Optimal operation of equipment requires cleanliness. Often after the installation of the equipment, additional construction activities occur. Protect the equipment from debris during these construction phases.

WARNING

Electrically ground the unit by connecting the ground wire to the ground lug. Failure to properly ground the unit may result in personal injury or death.

CAUTION

Wire any field installed device such as a fan switch or thermostat furnished by the factory in strict accordance with the wiring diagram supplied with the unit. Failure to properly wire the unit could result in damage to components and will void all warranties.

PRIOR TO THE STARTUP OF THE UNIT

  1. Ensure supply voltage matches nameplate data.
  2. Ensure the unit is properly grounded
  3. With the power off, check the blower wheel set screws for proper tightness and that the blower wheel rotates freely.
  4. Ensure the unit will be accessible for servicing.
  5. Ensure the condensate line is properly sized, run,  trapped, pitched, and tested.
  6. Ensure all cabinet openings and wiring connections have been sealed.
  7. Ensure clean filters are in place.
  8. Ensure all access panels are in place and secured.
  9. Ensure that all air has been vented from the water coil.
  10. Verify that all electrical connections are tight and secure.
  11. Check the electrical overcurrent protection and wiring for the correct size.
  12.  Verify that the low-voltage wiring between the thermostat and the unit matches the wiring diagram

AQUA-PAK AC UNITS

  1. Set the thermostat system switch to the “OFF” position and the fan switch to the “Auto” position. Apply power to the AQUA-PAK Unit.

  2. Set the fan switch to “On”, the indoor blower should operate.

  3. Return the fan switch to “Auto”, the indoor blower should de-energize

  4. Set the system switch to “Cool” and lower the thermostat set point to the coldest setting. The compressor should energize as well as the outdoor fan and indoor blower.

  5. Return thermostat set-point to a temperature warmer than room temperature and the compressor, and indoor and outdoor fan should reenergize
    NOTE
    The AQUA-PAK employs a compressor short cycle delay (approx. 3 minutes) which will not allow the compressor to immediately restart following shutdown. Additional delays may be experienced if using an electronic digital thermostat.

  6. Move the system switches to “Heat” and raise the thermostat to a set point slightly higher than room temperature (less than 2 degrees). The indoor fan and heat cycle should energize.

STARTUP & PERFORMANCE CHECKLIST INSTRUCTIONS

The warranty may be void unless the FIGURE 24 – Startup & Performance Checklist is completed and returned to the warrantor. If the unit is not installed properly, the warranty will be void, as the manufacturer will not be held accountable for problems that stem from improper installation

TROUBLESHOOTING

PROBLEM POSSIBLE CAUSE CHECKS & CORRECTIONS





ENTIRE UNIT DOES NOT RUN

| Power supply off| Apply power; close disconnect.
Blown Fuse| Replace the fuse or reset the circuit breaker. Check for correct fuses.
Voltage supply low| If the voltage is below the minimum voltage specified on the unit data plate, contact the lower power company.





Thermostat

| Set the fan to “ON”, the fan should run. Set the thermostat to “COOL” and the lowest temperature setting, the unit should run in the cooling mode. Set the unit to “HEAT” and the highest temperature setting, the unit should run in the heating mode. If neither the blower nor compressor runs in all three cases, the thermostat could be miswired or faulty. To ensure miswired or faulty thermostats verify 24 volts is available on the condenser section low voltage terminal strip between “R” and “C”, “Y” and “C”, and “B” and “C”. If the blower does not operate, verify 24 colts between terminals “G” and “C” in the air handler.

Replace the thermostat if defective.



THE BLOWER OPERATES BUT THE COMPRESSOR DOES NOT RUN

| Thermostat| Check settings, calibration, and wiring.
Wiring| Check for loose or broken wires at the compressor, capacitor or contractor.
Compressor overload open| If the compressor is cool and the overload will not reset, replace the compressor.
Compressor motor

grounded

| Internal wiring grounded to the compressor shell. Replace compressor. If

the compressor burns out, install a new filter dryer.

Compressor windings open| After the compressor has cooled, check continually of compressor windings. If the windings are open, replace the compressor.



UNIT OFF ON HIGH-PRESSURE CONTROL

| ****

Discharge pressure too high

| In “COOLING” mode: Lack of or inadequate airflow. Entering air temperature too warm. Blower inoperative, clogged filter or restriction in the ductwork.

In “HEATING” mode: Lack of or inadequate airflow. Entering air temperature

too cold. Blower inoperative, clogged filter or restriction in the ductwork.

Refrigerant charge| The unit is overcharged with refrigerant. Reclaim refrigerant, evacuate, and recharge with factory recommended charge.
High-pressure switch| Check for defective or improperly calibrated high- pressure switches.



UNIT OFF ON LOW-PRESSURE CONTROL

| ****

Suction Pressure too low

| In “COOLING” mode: Lack of or inadequate airflow. Entering air temperature too cold. Blower inoperative, clogged filter or restriction in the ductwork.

In “HEATING” mode: Lack of or inadequate airflow. Entering air temperature too warm. Blower inoperative, clogged filter or restriction in the ductwork.

Refrigerant charge| The unit is low on refrigerant. Check for refrigerant leak, repair, evacuate and

recharge with factory recommended charge.

Low-pressure switch| Check for defective or improperly calibrated low-pressure switch.


UNIT SHORT CYCLES

| Unit oversized| Recalculate heating and cooling loads.
Thermostat| The thermostat installed near a supply air register, and relocate the thermostat. Check the heat anticipator.
Wiring and controls| Loose connections in the wiring or a defective compressor contactor.
Table 8 – Troubleshooting Table (1 of 2)
PROBLEM| POSSIBLE CAUSE| CHECKS & CORRECTIONS
---|---|---







INSUFFICIENT COOLING

| Unit undersized| Recalculate heating and cooling loads. If not excessive, possibly adding

insulation will rectify the situation.

Loss of conditioned air by leaks| Check for leaks in ductwork or the introduction of ambient air through doors or windows.
Airflow| Lack of adequate airflow or improper distribution of air. Replace the dirty air filter.
Refrigerant charge| Low on refrigerant charge causing inefficient operation.
Compressor| Check for defective compressors. If the discharge is too low and the suction pressure is

too high, the compressor is not pumping properly. Replace compressor.

Operating pressures| Compare unit operating pressures to the pressure/temperature chart for the unit.
Refrigerant metering device| Check for possible restrictions or defects. Replace if necessary.


Moisture, non-condensable

| The refrigerant system may be contaminated with moisture or non-condensable. Reclaim refrigerant, evacuate, and recharge with factory

recommended charge.

Table 9 – Troubleshooting Table (2 of 2)

MAINTENANCE & SERVICE

PREVENTIVE MAINTENANCE
To ensure maximum performance and service life of equipment, a formal schedule of regular preventative maintenance must be established and adhered to. Failure to do establish and perform a preventative maintenance program can void the manufacturer’s warranty. If servicing or major repairs are required, the complete unit can be removed as follows:

  1. 1. Disconnect the electrical power circuit supplying the unit.
    2. Remove line and low voltage wiring from the unit,
    3. Remove the rear access panel.
    4. Remove the supply duct from the top of the unit.
    5. Slide the unit back out of the sleeve.
    6. The unit may be removed from the closet.

To reinstall the unit, use the installation procedure outlined above.

WARNING

It is a violation of federal law to discharge refrigerant into the atmosphere. Use proper reclaiming methods and equipment when installing or servicing this unit. Service should be performed by a QUALIFIED service agency. The refrigerant system contained in the unit normally requires no maintenance since it is a closed, self-contained system.

CAUTION

All appropriate personal protection equipment should be worn when servicing or maintaining this unit. Personal injury can result from contact with sharp metal edges, moving parts, and hot or cold surfaces.

FAN
The fan should be inspected and cleaned annually in conjunction with maintenance of the motor and bearings. It is important to keep the fan section and motor clean and free from obstruction to prevent imbalance, vibration, and improper operation.

WARNING

ELECTRIC SHOCK HAZARD Check motor connections to ensure they are secure and in accordance with the unit wiring diagram. ECM motors have line voltage power applied at all times. VERIFY THAT THE POWER IS DISCONNECTED BEFORE SERVICING.

  • FILTER
    The air filter should be cleaned or replaced every 30 days or more frequently if severe operating conditions exist. Always replace the filter with the same type and size as originally furnished.
    COIL
    Clean all heat transfer surfaces and remove all dirt, dust, and contaminants that potentially impair air flow using industry-accepted practices. Care should be taken not to bend coil fin material.

  • CONDENSATE DRAIN PAN AND PIPE
    Check and clean all dirt and debris from the pan. Ensure the drain line is free-flowing and unobstructed.

  • MAINTENANCE UPDATES
    Check regularly for a current copy of the maintenance program log which can be found at under “product information”.

  • UNIT PERFORMANCE
    Record performance measurements of volts, amps, and air temperature differences (both heating and cooling). A comparison of logged data with start-up and other annual data is useful as an indicator of general equipment condition.

  • UNIT LOCKOUT
    Airflow problems could cause periodic lockouts. The lockout (shutdown) of the units is a normal protective result. Check for airflow rates (which may be caused by a dirty filter) and air temperatures.

  • LABORATORY TESTING
    When the unit has less than 100 operational hours and the coils have not had sufficient time to be “seasoned”, it is necessary to clean the coils with a mild surfactant such as Calgon to remove the oils left by manufacturing processes.

STARTUP CHECKLIST

INSTALLATION CHECK LIST

Inspect the unit for transit damage and report any damage on the carrier’s freight bill. Check the model number to ensure it matches the job requirements.

  • Install field accessories and unit adapter panels as required. Follow accessory and installation manuals.
  • Verify field wiring, including the wiring to any accessories.
  • Check all multi-tap transformers, to ensure they are set to the proper incoming voltage.
  • Power the unit. Bump the motor contractor to check rotation. Three phase motors are synchronized at the factory. If the blower fans are running backwards, de-energize power to the unit, then swap two of the three incoming electrical lines to obtain proper phasing. Re-check.
  • Perform all start up procedures outline in the installation manual shipped with the unit. Fill in the Start Up information as outlined below and on the following page.
  • Provide the owner with an information packet. Explain the thermostat and unit operation.

START UP INFORMATION SHEET

CONTACT

The manufacturer works to continually improve its products. It reserves the right to change design and specifications without notice. ©2023 First Co., Applied Environmental Air

COPYRIGHT

The Manufacturer works to continually improve its products and as a result, it reserves the right to change design and specifications without notice. The warranty may be void unless the Startup & Performance Checklist is completed and returned to the warrantor. If the AQUA-PAK AC unit is not installed properly the warranty will be void as  the manufacturer cannot be held accountable for problems that stem from improper installation.

WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER

Altering the product or replacing parts with non-authorized factory parts voids all warranty or implied warranty and may result in adverse operational performance and/or a possible hazardous condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals