elausys INV-KNX Gateway for Fronius Inverters User Manual
- June 15, 2024
- elausys
Table of Contents
|
User Manual
| Doc.Ref : INV-KNX-FR-UM
---|---|---
KNX Gateway for Fronius Inverters
| Revision : 2.00
ELAUSYS
INV-KNX
KNX Gateway for Fronius Inverters
User Manual
1. INTRODUCTION
The KNX gateway for Fronius inverters provides a simple solution to transfer all relevant data from the inverters to KNX.
It allows integrators to take advantage of a fully integrated solar panel inverter, the data can be used to optimize energy consumption, monitoring, trending or to trigger specific action in the KNX installation.
Main features:
- KNX Interface for Fronius inverters serie
- Monitoring of Energy, Power, current, voltage, frequency, temperature, …
- Connected to the inverter over Ethernet
- Galvanic insulation from the KNX bus
- Configurable refresh rate of inverter data
- DIN rail mounted
- Auxiliary power supply 12-30VDC
- KNX logic module including logic gates, sequences, triggers, math operation and weekly calendar events.
2. OVERVIEW
2.1 USAGE & LIMITATION
This gateway is intended to be used with an Fronius inverter compatible with the SMA SunSpec modbus interface definition. The inverter is connected to the ethernet network on the same router as the KNX gateway.
All Fronius inverters with SetApp configuration are SunSpec-supported. Fronius inverters with the LCD that have Firmware version 3.xxxx and above only are SunSpec-supported.
2.1 SOFTWARE
The KNX Interface is configured using the ETS tool, the free ETS Demo version can be downloaded from the website of KNX Association. The free version allows to configure up to 5 KNX modules in a project, the KNX gateway is only one module, all devices can be configured using this version.
2.2 CONNECTION DIAGRAM
The KNX bus is connected on the top side of the gateway.
An external power supply 12-30VDC is required and connected on the bottom side
of the module, beside the RJ45 connector for the ethernet cable.
- 12-30VDC
- RJ45 Ethernet
2.3 FRONT PANEL
The front panel is equipped with two green status LED:
Network: Physical connection to the ethernet network is established.
Connected: Communication with the inverter is established.
Button “P” : KNX Programming mode button
Red LED : KNX Programming status LED
3. PARAMETERS
The KNX interface parameters are defined in the “parameters” tab of the device, in the ETS project.
3.1 INVERTER SETTINGS
The following parameters are defined in the inverter settings section of the parameters:
PARAMETER
| VALUES|
DESCRIPTION
---|---|---
AC Network|
- Single phase (default)
- Tri-Phase
| Type of AC network
Number of PV Circuits|
- 1 … 4
| NOT APPLICABLE for this type of inverters
Inverter model|
- 0…255
| 3 = Fronius Inverters
Refresh rate (min)|
- 0…255
| Cyclic rate of data polling from the inverter.
Battery 1|
- Not Used / Used
| Display group objects to monitor the status of battery 1
Battery 2|
- Not Used / Used
| Display group objects to monitor the status of battery 2 (NOT USED for
this inverter)
Powermeter|
- Not Used / Used
| Display group objects to monitor the powermeter value (NOT USED for this
inverter)
Timezone|
- UTC-11… UTC+14
| Timezone where the device is installed. It is used for logic functions based
on the weekly calendar.
Daylight saving time|
- Not Used / Used
| Set if daylight saving is used where the device is installed. It is used
for logic functions based on the weekly calendar.
Device Options|
- Text string
| Device options are not available on this device.
4. LOGIC FUNCTIONS
The KNX logic module is a virtual extension module that is part of the ETS application on the inverters gateways. Each logic module includes 8 logic functions including logic gates, sequences, triggers, math operation and weekly calendar events.
- Up to 64 logic functions using extension modules
- Logic Gate with 8 inputs, configurable output delay and inversion
- Sequence with 4 steps, configurable outputs delays and datatypes
- Trigger with inputs logic, delays and weekly calendar events
- Math operations with configurable objects type and delays
Refer to the KNX Logic Module manual for more details on each function.
5. COMMUNICATION OBJECTS
5.1 GENERAL
General communication objects of the device.
GO
| NAME| DESCRIPTION
---|---|---
1
| Module status| Sends 0 when the module is operating normally, sends an error code when applicable.
2
| Firmware version| Returns the firmware version of the device when the object is read.
5.2 INVERTERS OBJECTS
GO
| NAME| DESCRIPTION
---|---|---
3
| AC Current| AC Total Current value
4
| AC Current A| AC Current phase A
5
| AC Current B| AC Current phase B
6
| AC Current C| AC Current phase C
7
| AC Voltage| AC Total Voltage (NOT USED)
8
| AC Voltage AB| AC Voltage phase AB
9
| AC Voltage BC| AC Voltage phase BC
10
| AC Voltage CA| AC Voltage phase CA
11
| AC Voltage AN| AC Voltage phase AN
12
| AC Voltage BN| AC Voltage phase BN
13
| AC Voltage CN| AC Voltage phase CN
14
| DC Current| DC Total Current value (NOT USED)
15
| DC Voltage| DC Total Voltage (NOT USED)
16
| PV1 Voltage| PV1 Voltage
17
| PV1 Current| PV1 Current
18
| PV2 Voltage| PV2 Voltage
19
| PV2 Current| PV2 Current
20
| PV3 Voltage| PV3 Voltage (NOT USED)
21
| PV3 Current| PV3 Current (NOT USED)
22
| PV4 Voltage| PV4 Voltage (NOT USED)
23
| PV4 Current| PV4 Current (NOT USED)
24
| AC Power| AC Power
25
| DC Power| DC Power (NOT USED)
26
| AC Frequency| AC Frequency
27
| AC VA| AC Apparent power
28
| AC VAR| AC Reactive power
29
| AC PF| Power factor
30
| AC Energy| Total AC Energy
31
| Efficiency| Inverter efficiency (NOT USED)
32
| Insulation| Insulation resistance (NOT USED)
33
| Temperature| Cabinet temperature (NOT USED)
40
| Daily Energy Yield| (NOT USED)
41
| Battery 1 Running Status| 0: OFF
1: EMPTY
6: DISCHAGING
7: CHARGING
9: FULL
10: HOLDING
11: TESTING
42
| Battery 1 power| (NOT USED)
43
| Battery 1 SOC| Battery’s state of capacity
44
| Battery 1 current day charge| (NOT USED)
45
| Battery 1 current day discharge| (NOT USED)
46
| Battery 1 total charge| (NOT USED)
47
| Battery 1 total discharge| (NOT USED)
48
| Battery 2 Running Status| (NOT USED)
49
| Battery 2 power| (NOT USED)
50
| Battery 2 SOC| (NOT USED)
51
| Battery 2 current day charge| (NOT USED)
52
| Battery 2 current day discharge| (NOT USED)
53
| Battery 2 total charge| (NOT USED)
54
| Battery 2 total discharge| (NOT USED)
55
| Powermeter| (NOT USED)
5.3 GROUP OBJECT LIST
GO
| Name| Function| Size| Flags| Type ID| Type
Name| Description
---|---|---|---|---|---|---|---
1
| Module status| Status code| 1 byte| C R – T –| 20.011| DPT_ErrorClass_System| Device status
2
| Firmware version| Text String| 14 bytes| C R – T –| 16.000| Character string| Firmware version of the device
3
| AC Current| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| AC Total Current value
4
| AC Current A| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| AC Current phase A
5
| AC Current B| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| AC Current phase B
6
| AC current C| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| AC Current phase C
7
| AC Voltage| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | AC Total Voltage
8
| AC Voltage AB| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | AC Voltage Phase AB value
9
| AC Voltage BC| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | AC Voltage Phase BC value
10
| AC Voltage CA| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | AC Voltage Phase CA value
11
| AC Voltage AN| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | AC Voltage Phase AN value
12
| AC Voltage BN| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | AC Voltage Phase BN value
13
| AC Voltage CN| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | AC Voltage Phase CN value
14
| DC Current| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| DC Total Current value
15
| DC Voltage| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | DC Total Voltage
16
| PV1 Voltage| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | PV1 Voltage
17
| PV1 Current| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| PV1 Current
18
| PV2 Voltage| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | PV2 Voltage
19
| PV2 Current| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| PV2 Current
20
| PV3 Voltage| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V) | PV3 Voltage
21
| PV3 Current| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| PV3 Current
22
| PV4 Voltage| Actual value| 4 bytes| C R – T –| 14.027| Electric potential (V)| PV4 Voltage
23
| PV4 Current| Actual value| 4 bytes| C R – T –| 14.019| Electric current (A)| PV4 Current
24
| AC Power| Actual value| 4 bytes| C R – T –| 14.056| Power (W) | AC Power
25
| DC Power| Actual value| 4 bytes| C R – T –| 14.056| Power (W) | DC Power
26
| AC Frequency| Actual value| 4 bytes| C R – T –| 14.033| Frequency (Hz)| AC Frequency
27
| AC VA| Actual value| 4 bytes| C R – T –| 14.056| Power (W) | AC Apparent power
28
| AC VAR| Actual value| 4 bytes| C R – T –| 14.056| Power (W) | AC Reactive power
29
| AC PF| Actual value| 4 bytes| C R – T –| 14.057| Power factor (cos phi)| Power factor
30
| AC Energy| Actual value| 4 bytes| C R – T –| 13.013| Active energy (kWh) | Total AC Energy
31
| Efficiency| Actual value| 2 bytes| C R – T –| 8.010| Percentage (%)| Inverter efficiency
32
| Insulation| Actual value| 4 bytes| C R – T –| 14.056| Resistance (Ohm) | Insulation resistance
33
| Temperature| Actual value| 2 bytes| C R – T –| 9.001| Temperature (°C)| Cabinet temperature
40
| Daily Energy Yield| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
41
| Battery 1 Running Status| Actual value| 2 bytes| C R – T –| –| –| Status code
42
| Battery 1 power| Actual value| 4 bytes| C R – T –| 14.056| Power (W)|
43
| Battery 1 SOC| Actual value| 1 byte| C R – T –| 5.001| Percentage (%)| State of charge (%)
44
| Battery 1 current day charge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
45
| Battery 1 current day discharge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
46
| Battery 1 total charge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
47
| Battery 1 total discharge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
48
| Battery 2 Running Status| Actual value| 2 bytes| C R – T –| –| –| Status code
49
| Battery 2 power| Actual value| 4 bytes| C R – T –| 14.056| Power (W)|
50
| Battery 2 SOC| Actual value| 1 byte| C R – T –| 5.001| Percentage (%)| State of charge (%)
51
| Battery 2 current day charge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
52
| Battery 2 current day discharge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
53
| Battery 2 total charge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
54
| Battery 2 total discharge| Actual value| 4 bytes| C R – T –| 13.013| Energy (kWh)|
55
| Powermeter| Actual value| 4 bytes| C R – T –| 14.056| Power (W)|
6. CONFIGURATION
6.1 NETWORK CONFIGURATION
By default, the IP address of the KNX gateway is set to 192.168.1.51
Using a laptop connected to the gateway, open a web browser and navigate to
the IP address of the gateway.
Set a fixed IP address of your choice for the KNX gateway and configure the modbus TCP settings as below:
- Mode : Connect
- IP : IP Address of the inverter
- Server Port : 502
- Uni Id : 1
6.2 KNX PHYSICAL DEVICE
ELAUSYS devices are configured using the ETS tool. You should first download and install the free version of ETS tool before you continue.
The INV-KNX Interface must be assigned a physical address on the KNX network. Assign a free address to the module, in our example we choose 1.1.2.
6.3 ETS PARAMETERS
Once a KNX physical address is set, open the parameter tab to configure the interface.
Select the type of AC network (single phase or tri-phase).
Set the inverter model to 3 for Fronius inverters.
Choose the refresh rate (min) for the complete set of data.
Select if battery 1 is available on the inverter.
Device options should remain empty.
6.4 ETS GROUP OBJECTS
A group address (GA) must be assigned to each group object (GO) needed by the
application.
Open the Group Objects tab of the device and assign a GA to the objects as
needed.
When GO and parameters are all configured, download the KNX Interface application to the device. The first download requires to press the programming button on the device to set the device in KNX programming mode then perform a full download.
6.5 INVERTER CONFIGURATION
MODBUS over TCP Support
MODBUS TCP function- is disabled by default.
-
Install Fronius Datamanager (=> see the Fronius Datamanager operating instructions.)
-
Open Internet browser
-
Enter the following in the address field of the Internet browser:
– the IP address of the Fronius Datamanager (can be accessed via System Information)
– or host name and domain name of the Fronius Datamanager.
– The web interface’s start page is displayed. -
Select the “Settings” section (1).
-
Open the “Modbus” section (2).
- Select data export : tcp
- Set modbus port : 502
- Set Sunspec model type: int+SF
7. FIRMWARE VERSION
This user manual and related ETS application is valid for firmware versions
V2.2.0.0 and above.
The firmware version can be read from the gateway webpage using a web browser.
It is displayed on the top right of the page.
In case an updated firmware would be available, the device can be updated from the FW Update page, the binary file should be selected before pressing the Update button.
8. DATASHEET
TECHNICAL DATA
| VALUE
---|---
Auxiliary power supply terminal
|
Screw terminal 12-30VDC / GND
Power consumption KNX bus typ.
| < 16 mA @ 29VDC
Operating temperature
|
+5°C to + 45°C
Enclosure Dimensions (Space Units)
| 2 SU
Mounting
|
DIN RAIL
KNX terminal
| Pluggable micro terminal, Red/Black, 4 pole PUSH WIRE for solid conductor wire 0.6-0.8 mm²
KNX bus voltage
|
29 VDC
© ELAUSYS SPRL
This document cannot be reproduced fully or partially without written authorization
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>