BINMASTER 730-0250 Compact Pro Capacitance Sensor Instruction Manual

June 14, 2024
BINMASTER

BINMASTER 730-0250 Compact Pro Capacitance Sensor

Product Information

CompactPro Capacitance Sensor

The CompactPro Capacitance Sensor is a device designed to detect the presence or absence of material in a vessel. It is commonly used in industrial applications to monitor and control the level of liquids or solids in tanks or containers. The sensor operates based on the principle of capacitance, where changes in the electrical properties of the probe are used to determine the level ofmaterial.

Specifications:

  • Operating Voltage: 115 VAC
  • Mounting: 1 NPS
  • Grounding: Earth ground reference conductor integrated within the probe
  • Recommended Wire Size: 18 or 16 AWG

Installation

Location and Mounting

The CompactPro Capacitance Sensor should be installed in a location that is out of direct flow of material. It is recommended
to mount the sensor using a 1 NPS (National Pipe Straight) fitting. If installing in areas where moisture or moist air could enter the enclosure through the electrical conduit, it is important to adequately seal the conduit opening with a duct seal compound.

Grounding

An equipment grounding connection (earth ground) must be supplied to the unit for safety and proper operation. The CompactPro uses earth ground as a reference for calibration and detecting a covered or uncovered condition. The probe includes a ground reference conductor, allowing it to be used in non- metallic vessels. However, installation in a grounded metallic vessel may provide enhanced sensitivity.

Input Power and Field Wiring

The CompactPro operates from a 115 VAC power supply. Field wiring should conform to all national and local electrical codes.
he terminals for the input power are labeled on the circuit board: L for the hot wire, N for the neutral wire, and G for the safety ground wire. It is recommended to use 18 or 16 AWG wire for the installation. The terminals are unpluggable for easier wiring. To unplug them, hold down on the circuit board transformer while pulling up on the terminals.

Fail-Safe Selection

Description

Fail-Safe refers to the relay contact positions that are set up to ensure safety in case of a power failure. In the CompactPro Capacitance Sensor, the fail-safe mode determines how the relay contacts behave when the probe is covered or uncovered.

Fail-Safe High

In Fail-Safe High mode, the relay will be energized when the probe is uncovered and de-energize when the probe is covered. In the event of a power failure, the relay contacts will indicate that the probe is covered.

Fail-Safe Low

In Fail-Safe Low mode, the relay will be de-energized when the probe is uncovered and energize when the probe is covered. In case of a power failure, the relay contacts will indicate that the probe is uncovered.

Calibration

Calibration Verification

After calibrating the CompactPro Capacitance Sensor, it is important to verify the sensitivity setting by checking if the sensor senses a covered probe condition with your material.

Calibration Procedure

Note: Ensure that the probe is uncovered and the material is at least 2 feet away from the probe before starting the calibration procedure.

  1. If the COVERED indicator light is OFF, turn the CALIBRATE
  2. control counter clockwise (CCW) until the indicator turns ON.
  3. If the COVERED indicator is ON, proceed with step 2.
  4. Turn the CALIBRATE control slowly clockwise (CW) until the COVERED indicator just turns OFF.
  5. Continue turning the control clockwise (CW) to the desired sensitivity setting.

FAQ

Q: What is the operating voltage of the CompactPro Capacitance Sensor?

A: The CompactPro operates from a 115 VAC power supply.

Q: Can the CompactPro be used in non-metallic vessels?

A: Yes, the CompactPro includes a ground reference conductor that allows operation in non-metallic vessels. However, installation in a grounded metallic vessel may provide enhanced
sensitivity.

Q: How should I verify the calibration of the sensor?

A: After calibrating, check that the CompactPro senses a covered probe condition with your material.

CompactPro Capacitance Sensor

INSTALLATION

  • Location and Mounting
    The probe should be located out of the direct flow of material. The CompactPro is designed to mount utilizing a 1” NPS. When installing the COMPACT PRO in locations where moisture or moist air could enter the enclosure through the electrical conduit, the conduit opening should be adequately sealed with a duct seal compound

  • Grounding
    An equipment grounding connection (earth ground) must be supplied to the unit for safety and to insure proper operation of the unit. The CompactPro uses earth ground as a reference for calibration and detecting a covered or uncovered  condition. A ground reference conductor is integrated within the probe allowing operation of the unit in nonmetallic vessels. Installation in a grounded metallic vessel will in some cases provide enhanced sensitivity.

  • Input Power and Field Wiring
    The CompactPro operates from 115 VAC. Field wiring should conform to all national and local electrical codes. Terminals for the input power are labeled on the circuit board; L for the 115 volt hot wire, N for the neutral wire, and G for the safety ground wire. Recommended wire size is 18 or 16 AWG. Note: The terminals are unpluggable to facilitate wiring. Hold down on the circuit board transformer when pulling up on the terminals to unplug them.
    FAIL-SAFE SELECTION

  • Description
    Fail-Safe means that the relay contact positions are set up so that in the event of a power failure the relay will de-energize to a condition that is deemed safe for the application.

  • Fail-Safe High
    Fail-Safe High means that the relay will be energized when the probe is uncovered and will de-energize when the probe is covered. In this mode, a power failure will cause the relay contacts to indicate that the probe is covered

Fail-Safe Low
Fail-Safe Low means that the relay will be de-energized when the probe is uncovered and will energize when the probe is covered. In this mode, a power failure will cause the relay contacts to indicate that the probe is uncovered.

CALIBRATION

A multiturn CALIBRATE control is used to compensate for the capacitance of the empty vessel and to set up the
desired sensitivity. A tool for adjusting the control is provided on the inside of the lid of the CompactPro. When finished,
return the tool to its clip in the lid for future use.
Calibration Verification
Following calibration, the sensitivity setting that you have set in should be checked by verifying that the CompactPro senses a covered probe condition with your material.
Calibration Procedure
(Probe must be uncovered, material at least 2 feet away from probe)

  1. .If the COVERED indicator light is OFF, turn the CALIBRATE control counter clockwise (CCW) until the indicator turnsON. If the COVERED indicator is ON proceed with step 2.
  2. Turn the CALIBRATE control slowly clockwise (CW) to the point where the COVERED indicator just turns OFF. Now  continue to turn the control clockwise (CW) to the desired sensitivity setting

Material Dielectric Constant

  • HIGH sensitivity: 1/8 to 1/2 turn 3 or less
  • MEDIUM sensitivity: 1/2 to 1 turn 3 to 6
  • LOW sensitivity: 1 turn or more 6 or more

RELAY TIME DELAY
The CompactPro has a single turn control for adjusting the time delay from approximately 1 to 30 seconds. This is a
time delay for the output relay to change states after a covered or uncovered condition is sensed. The COVERED indicator
light will immediately respond to a change in covered or uncovered condition regardless of the time delay setting.
Minimum time delay, 1 second, DELAY control full counter clockwise, CCW.
Maximum time delay, 30 seconds, DELAY control full clockwise, CW.
LIMITED WARANTY
The manufacturer warrants this equipment for one (1) year according to the following terms:

  1. This warranty extends to the original purchaser only and commences on the date of orginial purchase.
  2. The manufacturer will repair or replace any part of this equipment found to be defective, provided such part is deliverered prepaid. Manufacturer’s obligation is limited to the cost of material and labor to repair or replace and does not include transportation expenses.
  3. This warranty shall not apply to any product that has, in our judgement, been tampered with, altered, subject to misuse, neglect or accident. In addition, the warranties does not extend to repairs made necessary by normal wear.
  4. This warranty is in lieu of all other warranties, expressed or implied.

CompactPro 115 VAC

www.calcert.com sales@calcert.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals