SAFETY PRECAUTIONS
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage to properties only.
Cautions in Repair
WARNING
-
Do not turn on the breaker or power under condition that front panel, rear panel, top cover, or control box cover is removed or opened. Otherwise, it may cause fire, electric shock, explosion or death.
-
Be sure to disconnect the power to unit before disassembling the equipment for a repair .Internal components and circuit boards are at main potential when the equipment is connected to the power. This high voltage is extremely dangerous and may cause death or severe injury if come in contact with it.
-
Do not touch the discharging refrigerant gas during the repair work. The discharging refrigerant gas. The refrigerant gas can cause frostbite.
-
Release the refrigerant gas completely at a well-ventilated place first. Otherwise, when the pipe is disconnected, refrigerant gas or refrigerating machine oil discharges and it can cause injury.
-
When the refrigerant gas leaks during work, perform ventilation. If the refrigerant gas comes in contact with a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is
dangerous because a shortage of oxygen occurs. Be sure to perform ventilation. -
When removing the front panel or cabinet, execute short-circuit and discharge between high voltage capacitor terminals. If discharge is not executed, an electric shock is caused by high voltage resulting in a death or injury.
-
Do not use a defective or underrated circuit breaker. Use the correctly rated breaker and fuse. Otherwise there is a risk of fire or electric shock. Install the panel and the cover of control box securely. Otherwise there is risk of fire or electric shock due to dust, water etc.
WARNING
-
Wiring connections must be secured tightly and the cable should be routed properly so that there is no force pulling the cable from the connection terminals. Improper or loose connections can cause heat
generation or fire. -
Do not touch, operate, or repair the product with wet hands. Otherwise there is risk of electric shock or fire.
CAUTION
- Do not turn on the breaker when the front panel and cabinet are removed.
- Be sure to ground the water heater with an earthing conductor connected to the earthing terminal.
- Conduct repair works after checking that the refrigerating cycle section has cooled down sufficiently. Otherwise, working on the unit, the hot refrigerating cycle section can cause burns.
- Do not tilt the unit while removing panels. Otherwise, the water inside the unit can spill and wet floor.
- Do not use the welder in a well-ventilated place. Using the welder in an enclosed room can cause oxygen deficiency. Be sure to turn off power switch before connecting or disconnecting connector, or parts damage may be occur.
Inspections after Repair
WARNING
- Check to see if the power cable is not dirty or loose. If the cable is dusty or loose it can cause an electrical shock or fire.
- Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances. otherwise, it can cause an electrical shock, excessive heat generation or fire.
- Do not insert hands or other objects through the air inlet or outlet while the product is operating. There are sharp and moving parts that could cause personal injury.
- Do not block the inlet or outlet of air flow. It may cause product failure.
CAUTION
- Check to see if the parts are mounted correctly and wires are connected. Improper installation and connections can cause an electric shock or an injury.
- Check whether the installation platform or frame has corroded. Corroded installation platform or frame can cause the unit to fall, resulting in injury.
- Be sure to check whether the earth wire is correctly connected.
- After the work has finished, be sure to do an insulation test to check whether the resistance is 2[Mohm] or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side. Check the drainage of the indoor unit after the repair. If drainage is faulty the water may enter the room and wet floor.
NOMENCLATURE
Factory Model Name
Model
| No.
---|---
1| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11
Water Heater| R| 5| T| T| 5| 0| F| –| S| A| 1
No. | Signification |
---|---|
1, 2 | Heat Pump Water Heater for R134a |
3 | Classification |
– T : Packaged
4| Compressor Type
– T : Inverter Heating Only
5,6| Water Tank Capacity
– e.g. 50gal → “50”
7| Water Tank Capacity
– F : Frontier
8| Outdoor Unit Platform
– “-” : Packaged(No Outdoor Unit)
9| Look/Color
– S : Frontier Silver
10| Function
– A : Smart Function + Hybrid Mode
11| Serial No.
– LG Model Development Serial No.
Buyer Model Name
Refrigerant
| ****
Series
| No
---|---|---
1| 2| 3| 4| 5| 6| 7| 8| 9
R134A| 1| A| P| H| W| C| 5| 0| 1| M
No. | Signification |
---|---|
1 | Refrigerant |
– A: R134A
2| Component
– P : Packaged
3| Product Category
– H: Heating
4| Product Type
– W : Tank Water
5| Product Grade
– C : Standard Efficiency
6, 7| Nominal Capacity
– e.g. 50gal → “50”
8| Generation
9| Features
– M : Mid Temp. Water
PRODUCT SPECIFICATIONS
Model | APHWC501M | APHWC801M |
---|
Capacity
| ****
Volume(Norminal)
| Gal| 58| 80
L| 220| 303
Volume(Rated)
| Gal| 53| 72
L| 201| 273
UEF(Draw Pattern Medium)| –| –| –
UEF(Draw Pattern High)| –| 3.93| 3.90
FHR| Gal| 76| 94
Annual Energy Consumption| kWh| 1262| 1272
Power Input
| Upper Element Wattage(208V / 240V)| kW| 3.8 / 5.0| 3.8 / 5.0
Lower Element Wattage(208V / 240V)| kW| 3.8 / 5.0| 3.8 / 5.0
Energy Star| –| Yes| Yes
Power Supply| Ø, V, Hz| 1Φ,208/240V,60Hz| 1Φ,208/240V,60Hz
Available Voltage Range| V| 176~276| 176~276
Air Flow Rate| Rated| CFM| 155.4| 155.4
Sound Pressure Level
| Auto| dB(A)| 42| 42
Turbo/Heat Pump| dB(A)| 45| 45
Dimensions
| Net(W x H x D)| in.| 22-27/32 x 63-31/32 x 22-29/32| 22-27/32 x 79-1/16 x
22-29/32
Shipping(W x H x D)| in.| 29-1/16 x 69-7/8 x 27-5/32| 29-1/16 x 84-31/32 x
27-5/32
Weight
| Net| lb.| 220| 262
Shipping| lb.| 260| 304
Operation Range| Heating| °F DB| 23 ~ 120| 23 ~ 120
Ex terior Color| –| Lux ury Silver| Lux ury Silver
Compressor
| Type| –| Twin Rotary| Twin Rotary
Model| –| EST092MBA| EST092MBA
Motor Type| –| BLDC| BLDC
Locked Rotor Ampere(LRA)| A| N/A(Inverter)| N/A(Inverter)
Oil Type
| ****
–
| POE PVE| POE PVE
Oil Charge| cc| 220| 220
Rated Load Ampere(208V / 240V)| A| 3.3 / 3.1| 3.3 / 3.1
Model| APHWC501M| APHWC801M
---|---|---
Fan
| Type| –| Propeller Fan| Propeller Fan
Motor Type| –| BLDC| BLDC
Motor Output| –| 43| 43
Full Load Ampere(FLA)| –| 0.22| 0.22
Heat Ex changer(Evaporator)
| Quantity| –| 1| 1
Rows| –| 3| 3
Columns| –| 15| 15
FPI| –| 21| 21
Design Pressure(System)
| High Side| psi| 290| 290
Low Side| psi| 130.5| 130.5
Max Working Pressure(Water Tank)| psi| 150| 150
Minimum Circuit Ampacity| A| 30.1| 30.1
Max ium Circuit Breaker| Heat Pump & Heater| A| 30| 30
Wiring Connections| Power Supply Cable(included Earth)| AWG x cores| 10 x 3C|
10 x 3C
Drain Hose Size| I.D| in.| 3/4, 1/2| 3/4, 1/2
Refrigerant
| Type| –| R134a| R134a
Pre Charge| oz.| 23| 26
Additional Charge| oz./ft.| –| –
Control| –| Electronic Ex pansion Valve| Electronic Ex pansion Valve
Defrost Method| –| Reverse Cycle| Reverse Cycle
Anode| –| Sacrificial| Sacrificial
Foam Insulation| inch| 1.6 ~ 2.4| 1.6 ~ 2.4
T&P Relief Valve| –| Yes| Yes
Water Connection Location| –| Side| Side
Water Connection Size| inch| 3/4| 3/4
Digital Display| –| Yes| Yes
Wi-Fi| –| Yes| Yes
PIPING DIAGRAM
LOC | Description | PCB Connector |
---|---|---|
Th1 | Thermistor for discharge pipe temperature | CN_TH2 |
Th2 | Thermistor for evaporating temperature | CN_TEMP_AIR |
Th3 | Thermistor for indoor air temperature | CN_TEMP_AIR |
Th4 | Thermistor for suction pipe temperature | CN_TH1 |
Th5 | Thermistor for upper water tank temperature | CN_TANK_D |
Th6 | Thermistor for lower water tank temperature | CN_TANK_U |
*EEV : Electronic Expansion Valve
WIRING DIAGRAM
APHWC501M / APHWC801M
APHWC501M / APHWC801M ****
EXPLODED VIEW
DISASSEMBLY
Before the following disassembly, disconnect all power to the heater and shut off the water supply to the heater
- Top cover and Front panel
- Remove the 6 screws that fasten the top cover. (See Figure 1)
- Remove the top cover.
- Remove the front décor. (There are 4 hooks.)
- Remove the 4 screws that fasten the front panel. (See Figure 2)
- Lift the front panel out. (Lift right side first.)
- Disconnect the connector between the front panel and control box.
- Re-install the components by referring to the removal procedure, above.
- Rear panel
- Remove the top cover and front panel. (Refer to section 1)
- Remove the 2 screws that fasten the rear panel at both sides.
- Remove the 2 screws that fasten the rear panel at back.
- Lift the rear panel out. (See Figure 3)
- Re-install the components by referring to the removal procedure, above.
- Control box
- Remove the top cover and front panel. (Refer to section 1)
- Remove the 1 screw that fasten the control box cover.
- Remove the control box cover. (There are 3 hooks.) (See Figure 4)
- Re-install the components by referring to the removal procedure, above.
- Motor and Fan
- Remove the top cover, front panel, and rear panel. (Refer to section 1, 2)
- Remove the 2 screws that fasten the bracket. (See Figure 5)
- Remove the bracket.
- Remove the 4 screws that fasten the motor bracket.
- Lift out the motor bracket, motor, and fan. (See Figure 6)
- Remove the 2 screws and the nut that secure the motor and fan.
- Separate the motor bracket, motor, and fan.
- Re-install the components by referring to the removal procedure, above.
- Shroud
- Remove the fan. (Refer to section 4)
- Remove the 6 screws that fasten the shroud.
- Remove the shroud. (See Figure 7)
- Re-install the components by referring to the removal procedure, above.
- Heating Elements
- Drain the water heater to a level just below the element to be replaced.
- Remove the front décor. (There is 4 hooks.)
- Remove 2 screws that fasten the element cover.
- Remove the element cover. (See Figure 8)
- Mark, then disconnect the wires from the element by removing the 2 screws.
- Using socket wrench, remove the element.
- Re-install the components by referring to the removal procedure, above.
- ECO
- Drain the water heater to a level just below the upper element
- Remove the front decor. (There is 4 hooks.)
- Remove 2 screws that fasten the upper element cover. (See Figure 8)
- Remove the upper element cover.
- Mark, then disconnect the wires from the ECO by removing the 4 screws.
- Remove 2 nuts that fasten the ECO.
- Remove the ECO.
- Re-install the components by referring to the removal procedure, above.
CAUTION
BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
MODEL : APHWC501M(R5TT50F-SA1), APHWC801M(R5TT80F-SA1) Any reproduction,
duplication, distribution (including by way of email, facsimile or other
electronic means), publication, modification, copying or transmission of this
Service Manual is STRICTLY PROHIBITED unless you have obtained the prior
written consent of the LG Electronics entity from which you received this
Service Manual. The material covered by this prohibition includes, without
limitation, any text, graphics or logos in this Service Manual. Copyright ©
2023 LG Electronics Inc. All rights reserved. Only training and service
purposes. P/NO.: MFL71409304_Rev00. 09152023