hager VF104TG Golf Recessed and Accessories Instruction Manual

June 4, 2024
hager

VF104TG Golf Recessed and Accessories
Instruction Manual

hager VF104TG Golf Recessed and Accessories

VF104TG Golf Recessed and Accessories

Mounting instructions

hager VF104TG Golf Recessed and Accessories - fig 8hager VF104TG Golf Recessed and Accessories - fig
7hager VF104TG Golf Recessed and
Accessories - fig 6hager VF104TG Golf Recessed
and Accessories - fig 5hager VF104TG Golf
Recessed and Accessories - fig 4hager VF104TG Golf Recessed and Accessories - fig
3hager VF104TG Golf Recessed and
Accessories - fig 2hager VF104TG Golf Recessed
and Accessories - fig 1

Attention!
It is critical that any enclosure is sized and selected to accommodate and dissipate heat rise generated from all installed devices. The table (right) provides maximum permissible heat dissipation for each golf enclosure size. Please ensure that you calculate the internal heat generated from your installation and select the correct enclosure accordingly.

Admissible thermal dissipation loss for flush mounted distribution boards at temperature rise ∆T*

Reference 10K W 15K W 20K W 25K W 30K W
VF104 2,5 4,1 5,9 7,7 9,7
VF108 2,8 4,6 6,5 8,6 10,8
VF112 4,4 7,2 10,4 13,7 17,2
VF212 5,7 9,5 13,5 17,9 22,4
VF312 7,1 11,7 16,8 22,1 27,8
VF412 8,7 14,4 20,5 27,1 34,0
VF118 5,8 9,6 13,8 16,2 22,8
VF218 7,6 12,6 17,9 23,7 29,7
VF318 9,2 15,3 21,9 28,9 36,2
VF418 11,2 18,5 26,5 35,0 43,9
VF122 6,8 11,2 16,0 21,1 26,5

*) ∆T is the temperature difference between the upper limiting temperature of the installed equipment and the ambient air temperature of the distribution board.

hager VF104TG Golf Recessed and Accessories - fig

The Assembly (DBO) designated markings must be completed as specified in IEC/EN 61439 – 3 clause 6.1.

34 93 842 47 30
F +34 93 842 24 64
info@hager.com
hager.com
– 05.2021

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals