Attention!
It is critical that any enclosure is sized and selected to accommodate and dissipate heat rise generated from all installed devices. The table (right) provides maximum permissible heat dissipation for each golf enclosure size. Please ensure that you calculate the internal heat generated from your installation and select the correct enclosure accordingly.

Admissible thermal dissipation loss for flush mounted distribution boards at temperature rise ∆T*

Reference 10K W 15K W 20K W 25K W 30K W
VF104 2,5 4,1 5,9 7,7 9,7
VF108 2,8 4,6 6,5 8,6 10,8
VF112 4,4 7,2 10,4 13,7 17,2
VF212 5,7 9,5 13,5 17,9 22,4
VF312 7,1 11,7 16,8 22,1 27,8
VF412 8,7 14,4 20,5 27,1 34,0
VF118 5,8 9,6 13,8 16,2 22,8
VF218 7,6 12,6 17,9 23,7 29,7
VF318 9,2 15,3 21,9 28,9 36,2
VF418 11,2 18,5 26,5 35,0 43,9
VF122 6,8 11,2 16,0 21,1 26,5

*) ∆T is the temperature difference between the upper limiting temperature of the installed equipment and the ambient air temperature of the distribution board.

hager VF104TG Golf Recessed and Accessories - fig

The Assembly (DBO) designated markings must be completed as specified in IEC/EN 61439 – 3 clause 6.1.