DELL S4100-ON Series PowerSwitch Installation Guide

June 14, 2024
Dell

S4100-ON Series PowerSwitch

Specifications

  • Date: September 2023
  • Revision: August 2023 Rev. A12

Product Information

This guide provides site preparation recommendations,
step-by-step procedures for rack mounting and desk mounting,
inserting modules, and connecting to a power source.

CAUTION: To avoid electrostatic discharge (ESD)
damage, wear grounding wrist straps when handling this
equipment.

NOTE: Only trained and qualified personnel can
install this equipment. Read this guide before you install and
power up this equipment. This equipment contains two power cords.
Disconnect both power cords before servicing.

NOTE: This equipment contains optical
transceivers, which comply with the limits of Class 1 laser
radiation.

NOTE: When no cable is connected, visible and
invisible laser radiation may be emitted from the aperture of the
optical transceiver ports. Avoid exposure to laser radiation. Do
not stare into open apertures.

Product Usage Instructions

1. Site Preparation Recommendations

Before installing the product, ensure that the site is prepared
according to the following recommendations:

  • Provide adequate space for the product
  • Ensure proper ventilation
  • Follow any additional guidelines mentioned in the site
    preparation section of the user manual

2. Rack Mounting

To rack mount the product, follow these steps:

  1. Ensure that the rack is properly grounded
  2. Align the product with the rack mounting brackets
  3. Secure the product to the rack using the provided screws

3. Desk Mounting

If you prefer to mount the product on a desk, follow these
steps:

  1. Place the product on the desk in the desired location

  2. Ensure that the desk is stable and can support the weight of
    the product

  3. Use the provided screws or adhesive to secure the product to
    the desk

4. Module Insertion

To insert modules into the product, use the following
procedure:

  1. Ensure that the product is powered off
  2. Locate the module slots on the product
  3. Align the module with the slot and gently push it in until it
    clicks into place

5. Power Connection

To connect the product to a power source, follow these
steps:

  1. Locate the DC power supply connection on the product

  2. Connect the appropriate power cords to the power supply
    connection

  3. Ensure that the power source is within the specified voltage
    range

  4. Plug in the power cords to a suitable power outlet

FAQ

Q: Where can I find more information about the product?

A: For more information about the S4100-ON Series, refer to the
following documents:

  • Dell SmartFabric OS10 Release Notes
  • Dell SmartFabric OS10 User Guide
  • Dell S4100-ON Series Setup Guide
  • Dell Open Networking Hardware Diagnostic Guide
  • S4100-ON Series Release Notes

Additionally, you can access product documentation and resources
on the Dell Networking OS10 Info Hub. For other resources, visit
Dell support at www.dell.com/support.

Dell PowerSwitch S4100­ON Series Installation Guide
September 2023
August 2023 Rev. A12

Notes, cautions, and warnings
NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid the problem. WARNING: A WARNING indicates a potential for property damage, personal injury, or death.
© 2018 – 2023 Dell Inc. or its subsidiaries. All rights reserved. Dell Technologies, Dell, and other trademarks are trademarks of Dell Inc. or its subsidiaries. Other trademarks may be trademarks of their respective owners.

Contents

Chapter 1: About this guide…………………………………………………………………………………………….. 5 Related documents…………………………………………………………………………………………………………………………………………. 5 Information symbols…………………………………………………………………………………………………………………………………………5
Chapter 2: S4100­ON Series switch…………………………………………………………………………………. 7 Introduction……………………………………………………………………………………………………………………………………………………… 7 Features………………………………………………………………………………………………………………………………………………………….. 11 Physical dimensions……………………………………………………………………………………………………………………………………….. 12 LED display…………………………………………………………………………………………………………………………………………………….. 12 LED behavior…………………………………………………………………………………………………………………………………………….. 12 Prerequisites……………………………………………………………………………………………………………………………………………………17 S4100-ON Series configurations…………………………………………………………………………………………………………………… 17 Luggage tag…………………………………………………………………………………………………………………………………………………….18
Chapter 3: Site preparations…………………………………………………………………………………………. 20 Site selection…………………………………………………………………………………………………………………………………………………. 20 Cabinet placement………………………………………………………………………………………………………………………………………… 20 Rack mounting……………………………………………………………………………………………………………………………………………….. 21 Switch ground…………………………………………………………………………………………………………………………………………………21 Fans and airflow…………………………………………………………………………………………………………………………………………….. 21 Power……………………………………………………………………………………………………………………………………………………………… 21 Storing components……………………………………………………………………………………………………………………………………… 22
Chapter 4: S4100­ON Series installation…………………………………………………………………………. 23 Unpack the switch………………………………………………………………………………………………………………………………………… 23 Unpack……………………………………………………………………………………………………………………………………………………… 23 Rack or cabinet installation…………………………………………………………………………………………………………………………… 24 ReadyRails installation…………………………………………………………………………………………………………………………………… 24 1U Tool-less mount installation…………………………………………………………………………………………………………………25 Two-post flush-mount installation………………………………………………………………………………………………………….. 26 Two-post center-mount installation……………………………………………………………………………………………………….. 26 Four-post threaded installation……………………………………………………………………………………………………………….. 27 S4100-ON Series installation………………………………………………………………………………………………………………………… 28 1U front-rack installation…………………………………………………………………………………………………………………………. 28 Optics installation…………………………………………………………………………………………………………………………………………..30 Optics removal………………………………………………………………………………………………………………………………………….. 31 Switch power-up…………………………………………………………………………………………………………………………………………….31 After switch installation………………………………………………………………………………………………………………………………….31 Switch replacement………………………………………………………………………………………………………………………………………..31
Chapter 5: Power supplies……………………………………………………………………………………………..33 Components………………………………………………………………………………………………………………………………………………….. 33 AC or DC power supply installation……………………………………………………………………………………………………………….34 AC or DC power supply replacement……………………………………………………………………………………………………… 35

Contents

3

DC power supply connection…………………………………………………………………………………………………………………………35
Chapter 6: Fans……………………………………………………………………………………………………………36 Components………………………………………………………………………………………………………………………………………………….. 36 Fan module installation…………………………………………………………………………………………………………………………………..37 Fan module replacement…………………………………………………………………………………………………………………………..37
Chapter 7: Management ports……………………………………………………………………………………….. 38 RS-232 console port access………………………………………………………………………………………………………………………….38 USB-B console port access………………………………………………………………………………………………………………………….. 39 USB storage………………………………………………………………………………………………………………………………………………….. 39
Chapter 8: Before you install an OS………………………………………………………………………………… 41 ONIE service discovery…………………………………………………………………………………………………………………………………. 42
Chapter 9: Specifications……………………………………………………………………………………………… 43 Chassis physical design………………………………………………………………………………………………………………………………….43 IEEE standards………………………………………………………………………………………………………………………………………………. 44 Agency compliance……………………………………………………………………………………………………………………………………….. 45 USA Federal Communications Commission statement……………………………………………………………………………….. 45 European Union directive conformance statement…………………………………………………………………………………….. 45 India……………………………………………………………………………………………………………………………………………………………….. 46 Japan VCCI compliance for class A equipment…………………………………………………………………………………………….46 Korean certification of compliance………………………………………………………………………………………………………………. 46 Safety standards and compliance agency certifications………………………………………………………………………………47 Electromagnetic compatibility………………………………………………………………………………………………………………………. 47 Product recycling and disposal…………………………………………………………………………………………………………………….. 48
Chapter 10: Dell support………………………………………………………………………………………………..49

4

Contents

1
About this guide
This guide provides site preparation recommendations, step-by-step procedures for rack mounting and desk mounting, inserting modules, and connecting to a power source.
CAUTION: To avoid electrostatic discharge (ESD) damage, wear grounding wrist straps when handling this equipment. NOTE: Only trained and qualified personnel can install this equipment. Read this guide before you install and power up this equipment. This equipment contains two power cords. Disconnect both power cords before servicing. NOTE: This equipment contains optical transceivers, which comply with the limits of Class 1 laser radiation.

Figure 1. Class 1 laser product tag
NOTE: When no cable is connected, visible and invisible laser radiation may be emitted from the aperture of the optical transceiver ports. Avoid exposure to laser radiation. Do not stare into open apertures.
NOTE: Read this guide before unpacking the switch. For more information, see Unpack the switch.
Topics:
· Related documents · Information symbols
Related documents
For more information about the S4100-ON Series, see the following documents: Dell SmartFabric OS10 Release Notes Dell SmartFabric OS10 User Guide Dell S4100-ON Series Setup Guide Dell Open Networking Hardware Diagnostic Guide S4100-ON Series Release Notes
NOTE: To access product documentation and resources that might be helpful to install, configure, and troubleshoot the specific Dell PowerSwitch, see the Dell Networking OS10 Info Hub. For all other resources, see Dell support: www.dell.com/ support.
Information symbols
This book uses the following information symbols: NOTE: The Note icon signals important operational information.

About this guide

5

CAUTION: The Caution icon signals information about situations that could result in equipment damage or loss of data. NOTE: The Warning icon signals information about hardware handling that could result in injury.
NOTE: The ESD Warning icon requires that you take electrostatic precautions when handling the device.

6

About this guide

2

S4100­ON Series switch

The following sections describe the Dell PowerSwitch S4100­ON Series (S4128F- ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch:
Topics:
· Introduction · Features · Physical dimensions · LED display · Prerequisites · S4100-ON Series configurations · Luggage tag

Introduction

The S4128F-ON, S4148F-ON, and S4148FE-ON switches are a one-rack unit (RU), full-featured fixed form-factor top-of-rack (ToR) 10/25/40/50/100GbE switch for 10G servers with small form-factor pluggable plus (SFP+), quad small form- factor pluggable plus (QSFP+), and quad small form-factor pluggable (QSFP28) ports. The S4148FE-ON also includes unified (Fiber channel and Ethernet) 10 GbE SFP+ and QSFP28 ports.
The S4128T-ON and S4148T switches are a one-rack unit (RU), full-featured fixed form-factor top-of-rack (ToR) 10/25/40/50/100GbE switch for 10GBaseT servers with copper BaseT RJ45, small form-factor pluggable plus (SFP+), quad small form-factor pluggable plus (QSFP+), and quad small form-factor pluggable 28 (QSFP28) ports.
The S4148U-ON switch is a one rack unit (RU), full-featured fixed form-factor top-of-rack (ToR) 10/25/40/50/100GbE switch for 10G servers with unified (Fiber channel and Ethernet) small form-factor pluggable plus (USFP+), Ethernet-only small form-factor pluggable plus (SFP+), Ethernet-only quad small form-factor pluggable plus (QSFP+), and unified (Fiber channel and Ethernet) quad small form-factor pluggable 28 (QSFP28) ports.
NOTE: For the S4148U-ON, for best optic performance, upgrade the Dell software to 10.4(0.0) or higher.

NOTE: For specific port profile details, see the OS10 Enterprise Edition User Guide.

The S4100F-ON Series supports the following configurations:

Table 1. S4128F-ON, S4148F-ON, and S4148FE-ON supported configurations

S4128F-ON

S4148F-ON

S4148FE-ON

28 x 10G + 2 x 100G

48 x 10G + 4 x 100G

48 x 10G + 4 x 100G

28 x 10G + 2 x 40G

48 x 10G + 6 x 40G

48 x 10G + 6 x 40G

28 x 10G + 4 x 50G

48 x 10G + 8 x 50G

48 x 10G + 8 x 50G

28 x 10G + 8 x 25G

48 x 10G + 16 x 25G

48 x 10G + 16 x 25G

36 x 10G

72 x 10G

72 x 10G

Table 2. S4128T-ON and S4148T-ON supported configurations

S4128T-ON

S4148T-ON

28 x 10GT + 2 x 100G

48 x 10GT + 4 x 100G

28 x 10GT + 2 x 40G

48 x 10GT + 6 x 40G

28 x 10GT + 4 x 50G

48 x 10GT + 8 x 50G

S4100­ON Series switch

7

Table 2. S4128T-ON and S4148T-ON supported configurations (continued)

S4128T-ON

S4148T-ON

28 x 10GT + 8 x 25G

48 x 10GT + 16 x 25G

28 x 10GT + 8 x 10G SFP+

48 x 10GT + 24 x 10G SFP+

Table 3. S4148U-ON supported configurations S4148U-ON 24 x 10G + 24 x FC8 + 4 x 100G 24 x 10G + 24 x FC16 + 4 x 100G 24 x 10G + 12 x FC16 + 4 x 100G 24 x 10G + 40 x FC8 + 2 x 40G 24 x 10G + 40 x FC16 24 x 10G + 28 x FC16 24 x 10G + 12 x FC16 + 16 x FC32 48 x 10G + 4 X 100G 48 x 10G + 6 x 40G 48 x 10G + 8 x 50G 48 x 10G + 16 x 25G 72 x 10G

Notes — All FC16 are oversubscribed. All FC16 linerate — 24 out of 40 FC16 are oversubscribed. All FC16 linerate All FC32 are oversubscribed. — — — — —

The following table lists the S4100-ON Series I/O-side details:

Table 4. S4100-ON Series I/O-side details

Platform

Description

S4128F-ON

28 fixed 10GbE SFP+ ports Two fixed 100GbE QSFP28 ports Seven-segment stacking indicator. One micro-USB-B console port One USB type-A port

S4148F-ON

48 fixed 10GbE SFP+ ports Two fixed 40GbE QSFP+ ports Four fixed 100GbE QSFP28 ports Seven-segment stacking indicator. One micro-USB-B console port One USB type-A port

S4148FE-ON

48 fixed 10GbE SFP+ ports Two fixed 40GbE QSFP+ ports Four fixed 100GbE QSFP28 ports Seven-segment stacking indicator. One micro-USB-B console port One USB type-A port Support for LRM optics

S4128T-ON

28 fixed 100M/1G/10GbE copper BaseT RJ45 ports Two fixed 100GbE QSFP28 ports Seven-segment stacking indicator. One micro-USB-B console port One USB type-A port

8

S4100­ON Series switch

Table 4. S4100-ON Series I/O-side details (continued)

Platform

Description

S4148T-ON

48 fixed 100M/1G/10GbE copper BaseT RJ45 ports Two fixed 40GbE QSFP+ ports Four fixed 100GbE QSFP28 ports Seven-segment stacking indicator. One micro- USB-B console port One USB type-A port

S4148U-ON

24 Ethernet SFP+ ports or Ethernet-only SFP+ ports 24 fixed Ethernet SFP+ optical ports Two fixed 40GbE QSFP+ ports Four fixed 100GbE QSFP28 ports Seven-segment stacking indicator. One micro-USB-B console port One USB type-A port

Figure 2. S4128F-ON I/O-side view 1. Twenty-eight SFP+ optical ports 3. Micro USB-B console port

2. Two QSFP28 optical ports 4. USB Type-A

Figure 3. S4148F-ON I/O-side view
1. Forty-eight SFP+ optical ports 3. Two QSFP+ optical ports 5. USB Type-A

2. Four QSFP28 ports 4. Micro USB-B console port

S4100­ON Series switch

9

Figure 4. S4148FE-ON I/O-side view
1. Twenty four each unified SFP+ and SFP+ optical ports 3. Two QSFP+ optical ports 5. USB Type-A

2. Four unified QSFP28 ports 4. Micro USB-B console port

Figure 5. S4128T-ON I/O-side view 1. Twenty-eight copper BaseT RJ-45 optical ports 3. Micro USB-B console port

2. Two QSFP28 optical ports 4. USB Type-A

Figure 6. S4148T-ON I/O-side view
1. Forty-eight copper BaseT RJ-45 optical ports 3. Two QSFP+ optical ports 5. USB Type-A

2. Four QSFP28 optical ports 4. Micro USB-B console port

10

S4100­ON Series switch

Figure 7. S4148U-ON switch I/O-side view
1. Unified Fibre channel and Ethernet SFP+ ports and Ethernet-only SFP+ optical ports
3. Ethernet QSFP+ optical ports 5. USB Type-A

2. Unified Fibre Channel and Ethernet QSFP28 ports 4. Micro USB-B console port

The S4100-ON Series PSU-side of the switch has two hot-swappable power supplies (PSUs) with integrated fans and four hot-swappable fan trays. The platforms include one RJ45 10/100/1000 Base-T Ethernet management port, one RJ45 console port, and one RS-232 serial console port on the PSU side of the switch.

Figure 8. S4100-ON Series PSU-side view
1. Four hot-swappable fan units 2. Two hot-swappable PSUs with integrated fans
Features
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) offers the following features:
S4128F-ON: 28 fixed 10GbE SFP+ ports, 2 fixed 100GbE QSFP28 ports S4148F-ON: 48 fixed 10GbE SFP+ ports, 2 fixed 40GbE QSFP+ ports, 4 fixed 100GbE QSFP28 ports S4148FE-ON: 48 fixed 10GbE SFP+ ports, 2 fixed 40GbE QSFP+ ports, 4 fixed 100GbE QSFP28 ports with support for LRM
optics S4128T-ON: 28 fixed copper 10GBase-T RJ-45 ports SFP+ ports, two fixed 40GbE QSFP+ ports S4148T-ON: 48 fixed copper 10GBase-T RJ-45 ports SFP+ ports, two fixed 40GbE QSFP+ ports, four 100GbE QSFP28
ports S4148U-ON: 24 10G unified Fibre channel and Ethernet SFP+ ports, 24 10G Ethernet SFP+ ports, two 40G Ethernet QSFP+
ports, four 100G unified Fibre channel and Ethernet QSFP28 ports One MicroUSB-B serial console management port One RJ-45 serial console management port One RS-232 serial console port One universal serial bus (USB) Type-A port for more file storage One 2 Core Rangeley C2338 central processing unit (CPU), with 4GB DDR3 SDRAM and one 16 GB mSATA/M.2 SSD
module

S4100­ON Series switch

11

Seven-segment stacking indicator Temperature monitoring Real time clock (RTC) support Hot-plug redundant power supplies Removable fans Standard 1U chassis
Physical dimensions
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON), has the following physical dimensions: 434 x 460 x 43.5 mm (W x D x H) 17.1 x 18.1 x 1.71 inches (W x D x H) Power supply unit (PSU) and fan module handle: 1.57 inches (40 mm)
LED display
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) contains LED displays on the I/O side and PSU side of the switch.
NOTE: If you are using third-party software, for more LED information, see their operating software documentation.
LED behavior
The following S4100­ON Series switch LED behavior displays during open networking installation environment (ONIE) operations:

Figure 9. S4128F-ON I/O-side LEDs
1. QSFP28 port activity LEDs 3. Master LED 5. Power LED 7. Locator LED/System beacon

2. Link (left), activity (right) port LEDs 4. System LED 6. Fan LED 8. Stack ID

12

S4100­ON Series switch

Figure 10. S4148F-ON and S4148FE-ON I/O-side LEDs
1. QSFP28 port activity LEDs 3. Master LED 5. Power LED 7. Locator LED/System beacon

2. Link/activity port LEDs 4. System LED 6. Fan LED 8. Stack ID

Figure 11. S4128T-ON I/O-side LEDs 1. QSFP28 port activity LEDs
3. Master LED 5. Power LED 7. Locator LED/System beacon

2. Link, activity, and beacon LED for top port (left), link, activity, and beacon LED for bottom port (right).
4. System LED 6. Fan LED 8. Stack ID

Figure 12. S4148T-ON I/O-side LEDs 1. QSFP28, QSFP+ port activity LEDs
3. Master LED 5. Power LED 7. Locator LED/System beacon

2. Link, activity, and beacon LED for top port (left), link, activity, and beacon LED for bottom port (right).
4. System LED 6. Fan LED 8. Stack ID

S4100­ON Series switch

13

Figure 13. S4148U-ON switch I/O-side LEDs
1. Unified QSFP28 and QSFP+ port LEDs–Link (right), activity (left)
3. Master LED 5. Power LED 7. Locator LED/System beacon

2. Unified SFP+ and SFP+ port LEDs–Link (right), activity (left)
4. System LED 6. Fan LED 8. Stack ID

Figure 14. S4100-ON Series PSU-side LEDs 1. Fan LED 3. PSU LED
Table 5. S4100­ON Series LED behavior LED System Status/Health LED

Power LED Master LED FAN LED

14

S4100­ON Series switch

2. Link LED 4. Activity LED
Description
Solid green–Normal operation Blinking green–Booting Solid yellow (amber)–Critical system error Blinking yellow–Noncritical system error, fan failure, or
power supply failure
Off–No power Solid green–Normal operation Solid yellow–POST is in process. Blinking yellow–Power Supply failure Off–Switch is in Stacking Slave mode. Solid green–Switch is in Stacking Master or Standalone
mode.
Off–No power

Table 5. S4100­ON Series LED behavior (continued)

LED

Description

Solid green–Normal operation; fan that is powered and running at the expected RPM
Solid yellow–Fan failed–including incompatible airflow direction when you insert the PSU or fan trays with differing airflows.

PSU LED

Off–No power Solid green–Normal operation Solid yellow–Power supply critical event causing a
shutdown.
Blinking yellow–PSU warning event; power continues to operate.
Blinking green, 1.0 Hz–Standby mode Blinking green, 0.5 Hz–AC power cable unplugged

Locator LED/System Beacon

Off–Locator function is disabled. Blinking blue–Locator function is enabled.

7-Segment LED for stacking

Off–No power Solid green–Hex digit representing the stack unit ID

RJ45 Ethernet LED

Off–no link and no activity detected On–Activity on the port Solid yellow–10 MHz activity Solid green–100 MHz activity Blinking green–1 GHz activity

Table 6. System management Ethernet port LEDs LED Link LED
Activity LED

Description
Off–No link Solid green–Link operating at a maximum speed–
autonegotiated/forced or 1G port Solid yellow–Link operating at a lower speed–
autonegotiated/forced or 10/100M port
Off–No link Flashing green–Port activity

Table 7. SFP+ and unified SFP+ port LEDs LED Link LED
Activity LED

Description
Off–No link Solid green–Link operating at maximum speed–10G port Solid yellow–Link operating at a lower speed–1G port Flashing yellow, 1 second on/off–Port beacon
Off–No link Flashing green–Port activity

NOTE: There are four LEDs for each QSFP+, QSFP28, and unified QSFP28 port. For each port, 100 GbE or 40 GbE uses only one LED, 2x50GbE uses two LEDs, and 4x25GbE or 4x10GbE uses all four LEDs.

Table 8. QSFP28 and unified QSFP28 port LEDs LED Link/Activity LED

Description Off–No link

S4100­ON Series switch

15

Table 8. QSFP28 and unified QSFP28 port LEDs LED

Description
Solid green–Link operating at maximum speed–100G for QSFP28 port
Flashing green–Link activity operating at maximum speed –100G port
Solid yellow–Link operating at a lower speed–40G or 10G port
Flashing yellow–Port activity at a lower speed–40G or 10G port
Flashing yellow, 1 second on/off–Port beacon

Table 9. QSFP28 and unified QSFP28 port LEDs: 4x25G or 4x10G mode

LED

Description

Link/Activity LED

Off–No link Solid green–Link operating at maximum speed–4x25G
port
Flashing green–Link activity operating at maximum speed –4x25G port
Solid yellow–Link operating at a lower speed–4x10G port Flashing yellow–Port activity at a lower speed–4x10G
port
Flashing yellow, 1 second on/off–Port beacon

Table 10. QSFP28 and unified QSFP28 port LEDs: 2x50G mode

LED

Description

Link/Activity LED

Off–No link Solid yellow–Link operating at a lower speed–2x50G
port
Flashing yellow–Link activity at a lower speed–2x50G port
Flashing yellow, 1 second on/off–Port beacon

Table 11. QSFP+ port LEDs LED Link/Activity LED

Description
Off–No link Solid green–Link operating at maximum speed–40G port Flashing green–Link activity operating at maximum speed
–40G port Flashing yellow, 1 second on/off–Port beacon

Table 12. QSFP+ port LEDs: 4x1G or 4x10G mode LED Link/Activity LED

Description
Off–No link Solid green–Link operating at maximum speed–10G port Flashing green–Link activity operating at maximum speed
–10G port Solid yellow–Link operating at a lower speed–1G port Flashing yellow–Port activity at a lower speed–1G port Flashing yellow, 1 second on/off–Port beacon

16

S4100­ON Series switch

Table 13. 10GBase-T RJ45 port LEDs LED Link LED
Activity LED

Description
Off–No link Solid green–Link operating at a maximum speed,
autonegotiated/forced or 10G Solid yellow–Link operating at a lower speed,
autonegotiated/forced or 1G/100M Solid blue–Port beacon
Off–No link Flashing green–10G port activity Flashing amber–1G/100M Port activity.

Prerequisites
The following is a list of required and optional components for the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch:
NOTE: Detailed installation instructions are provided in the Site preparations and S4100-ON Series installation sections.
S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, or S4148U-ON) switch, or multiple switches, if stacking
AC country- and regional-specific cables to connect the AC power source to each of the switches’ AC power supplies Mounting brackets for rack installation, included Screws for rack installation #1 and #2 Phillips screwdrivers, not included Torx screwdriver, not included Ground cable screws, included Copper or fiber cables Other optional components are:
Ground cable and lug for the frame-end of the ground cable Extra power supply unit Extra fan module Extra mounting brackets if installing in a four-post rack or cabinet
S4100-ON Series configurations
The S4100-ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switches are available in several different configurations.
All S4100-ON Series switches include the following configurations:
Fan with airflow from the I/O side to the PSU side–normal Fan with airflow from the PSU side to the I/O side–reverse. AC power supply with airflow from the I/O side to the PSU side–normal AC power supply with airflow from the PSU side to the I/O side–reverse. DC power supply with airflow from the I/O side to the PSU side–normal DC power supply with airflow from the PSU side to the I/O side–reverse. The following table lists each S4100-ON Series switch configuration:

S4100­ON Series switch

17

Table 14. S4100-ON Series configurations

S4100­ON Series Configuration Switch

S4128F-ON AC or DC Normal airflow

28 fixed SFP+ ports, 2 fixed QSFP28 ports, 7-segment stacking indicator, 1 microUSB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4128F-ON AC or 28 fixed SFP+ ports, 2 fixed QSFP28 ports, 7-segment stacking indicator, 1 microDC Reverse airflow USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet
management port, 2 AC or DC PSUs, and 4 fan trays.

S4148F-ON AC or DC Normal airflow

48 fixed SFP+ ports, 2 fixed QSFP+ ports, 4 fixed QSFP28 ports, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4148F-ON AC or DC Reverse airflow

48 fixed SFP+ ports, 2 fixed QSFP+ ports, 4 fixed QSFP28 ports, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4148FE-ON AC or DC Normal airflow

48 fixed SFP+ ports, 2 fixed QSFP+ ports, 4 fixed QSFP28 ports, support for LRM optics, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4148FE-ON AC or DC Reverse airflow

48 fixed SFP+ ports, 2 fixed QSFP+ ports, 4 fixed QSFP28 ports, support for LRM optics, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4128T-ON AC or DC Normal airflow

28 fixed 1-GBase-T JR-45 ports, 2 fixed QSFP28 ports, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4128T-ON AC or 28 fixed 1-GBase-T JR-45 ports, 2 fixed QSFP28 ports, 7-segment stacking DC Reverse airflow indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000
Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4148T-ON AC or DC Normal airflow

48 fixed 10GBase-T RJ45 ports, 2 fixed QSFP+ ports, 4 fixed QSFP28 ports, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4148T-ON AC or DC Reverse airflow

48 fixed 10GBase-T RJ45 ports, 2 fixed QSFP+ ports, 4 fixed QSFP28 ports, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4148U-ON AC or DC Normal airflow

24 unified fixed SFP+ ports, 24 fixed SFP+ ports, 2 fixed QSFP+ ports, 4 unified fixed QSFP28 ports, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

S4148U-ON AC or DC Reverse airflow

24 unified fixed SFP+ ports, 24 fixed SFP+ ports, 2 fixed QSFP+ ports, 4 unified fixed QSFP28 ports, 7-segment stacking indicator, 1 micro-USB-B console port, 1 USB type-A port, 1 RJ45 10/100/1000 Base-T Ethernet management port, 2 AC or DC PSUs, and 4 fan trays.

Luggage tag
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch has a pull-out tag, known as a luggage tag, on the PSU- side of the switch. The front of the luggage tag includes switch ID information. The back of the luggage tag includes a QRL that takes you to a How-To site where you watch videos about racking the switch, replacing components, configuring port channels, and so on.

18

S4100­ON Series switch

Figure 15. S4100­ON Series luggage tag 1. Front: MAC address 3. Back: Quick resource locator (QRL)

2. Front: Service tag and Express service code 4. Back: QRL

S4100­ON Series switch

19

3
Site preparations
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) is suitable for installation as part of a common bond network (CBN). You can install the switch in: Network telecommunication facilities Data centers Other locations where the National Electric Code (NEC) applies For more information about the S4100­ON Series specifications, see Specifications.
NOTE: Install the switch into a rack or cabinet before installing any optional components.
Topics:
· Site selection · Cabinet placement · Rack mounting · Switch ground · Fans and airflow · Power · Storing components
Site selection
Install Dell equipment in restricted access areas. A restricted access area is one where service personnel can only gain access using a special tool, lock, key, or other means of security. The authority responsible for the location controls access to the restricted area. Ensure that the area where you install switch meets the following safety requirements: Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local
electrical codes. S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON: Environmental–switch location–continuous temperature
range is from 5° to 40°C (50° to 104°F). S4148U-ON: Environmental–switch location–continuous temperature range is from 5° to 45°C (50° to 113°F). Operating humidity is from 5 to 85 percent noncondensing, continuous. In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot cooling vents or direct
sunlight. Away from sources of severe electromagnetic noise. Inside the restricted access area, position in a rack or cabinet, or on a desktop with adequate space in the front, back, and
sides for proper ventilation and access. Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA
75. For more information about switch storage and environmental temperatures, see Specifications.
Cabinet placement
Install the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) only in indoor cabinets designed for use in a controlled environment. Do not install the switch in outside cabinets. For cabinet placement requirements, see Site selection.

20

Site preparations

The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA) standard. Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.
Rack mounting
When you prepare your equipment rack, ensure that the rack is grounded. Ground the equipment rack to the same ground point the power service in your area uses. The ground path must be permanent.
Switch ground
Dell Technologies recommends grounding your switch. Use the S4100­ON Series switch in a CBN. NOTE: For AC-powered switches, although the third conductor of the AC power cable provides a ground path, Dell Technologies recommends grounding your switch with a dedicated ground wire.
NOTE: For DC-powered switches, the only way to safely ground your switch is to attach a dedicated ground wire.
Fans and airflow
The fans on the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) support two airflow options: normal and reverse.
Fan combinations
Fan installation is done as part of the factory install based on SKU type. The S4100­ON Series has stock keeping units (SKUs) that support the following configurations: AC PSU with fan airflow from the I/O to the PSU–normal AC PSU with fan airflow from the PSU to the I/O–reverse DC fan unit with airflow from the I/O to the PSU–normal DC fan unit with airflow from the PSU to the I/O–reverse Be sure to order the fans suitable to support your site’s ventilation. Use a single type of airflow fan in your switch. Do not mix reverse and normal airflows in a single switch. For proper ventilation, position the S4100­ON Series switch in an equipment rack or cabinet with a minimum of 5 inches (12.7 cm) of clearance around the exhaust vents. The fan speed varies based on internal temperature monitoring. The switch never intentionally turns off the fans. For more information, see Fans.
Power
Connect the switch to the applicable power source using the appropriate power cable. An AC power cable is included with each PSU. When installing AC or DC switches, follow the requirements of the National Electrical Code ANSI/NFPA 70, where applicable. The switch is powered-up when the power cable is connected between the switch and the power source. For more information, see Power supplies.
CAUTION: Always disconnect the power cable before you service the power supply slots. The switch has multiple power cords. Before servicing, ensure all power cords are disconnected. CAUTION: On the AC switch, use the power supply cable as the main disconnect device. Ensure that the socket-outlet is located/installed near the equipment and is easily accessible.

Site preparations

21

NOTE: You do not see module LEDs when the switch powers up in ONIE as the software controls the modules.
Storing components
If you do not install your S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch and components immediately, properly store the switch and all optional components following these guidelines: S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON: Storage location temperature must remain constant. The
storage range is from -40° to 65°C (-40° to 149°F). S4148U-ON: Storage location temperature must remain constant. The storage range is from -40° to 70°C (-40° to 158°F). Store on a dry surface or floor, away from direct sunlight, heat, and air conditioning ducts. Store in a dust-free environment.
CAUTION: ESD damage can occur when components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the S4100­ON Series switch and its accessories. After you remove the original packaging, place the switch and its components on an anti-static surface.

22

Site preparations

4
S4100­ON Series installation
To install the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON), complete the installation procedures in the order presented in this section. Always handle the S4100­ON Series switch and its components with care. Avoid dropping the switch or any field replaceable units (FRUs).
CAUTION: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the S4100­ON Series switch and its components. As with all electrical devices of this type, take all the necessary safety precautions to prevent injury when installing this switch.
NOTE: For more information, see the Open Networking Hardware Diagnostic Guide found at the following sites:
S4148F-ON, S4148T-ON, S4148FE-ON: www.dell.com/support/S4148F-ON/S4148T-ON /S4148FE-ON S4128T-ON, S4148T-ON: www.dell.com/support/S4128T-ON/S4148T-ON S4148U-ON: www.dell.com/support/S4148U
Topics:
· Unpack the switch · Rack or cabinet installation · ReadyRails installation · S4100-ON Series installation · Optics installation · Switch power-up · After switch installation · Switch replacement
Unpack the switch
NOTE: Before unpacking the switch, inspect the container and immediately report any evidence of damage.
When unpacking the S4100­ON Series switch, ensure that the following items are included: One S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, or S4148U-ON) switch One RJ45 to DB-9 female cable Two sets of rail kits, no tools required Two PSUs Four fan units Two country- and region- specific AC power cables Dell S4100­ON Series Setup Guide Safety and Regulatory Information Warranty and Support Information
Unpack
1. Place the container on a clean, flat surface and cut all straps securing the container. 2. Open the container or remove the container top. 3. Carefully remove the switch from the container and place it on a secure and clean surface. 4. Remove all packing material. 5. Inspect the product and accessories for damage.

S4100­ON Series installation

23

Rack or cabinet installation
You may either place the switch on a rack shelf or mount the switch directly into a 19″ wide, EIA-310- E-compliant rack. Rack mounting includes four-post, two-post, round threaded holes, or square holes. The ReadyRails system is provided for 1U front-rack and two-post installations. The ReadyRails system includes two separately packaged rail assemblies. To begin installation, separate each rail assembly by sliding the inside rail out of the outside rail.
WARNING: This guide is a condensed reference. Read the safety instructions in your Safety, Environmental, and Regulatory information booklet before you begin.
NOTE: The figures in this section are not intended to represent a specific switch.
NOTE: Do not the use the mounted ReadyRails as a shelf or a workplace.
Rack mount safety considerations
Rack loading–Overloading or uneven loading of racks may result in shelf or rack failure, possibly damaging the equipment and causing personal injury. Stabilize racks in a permanent location before loading begins. Mount the components starting at the bottom of the rack, then work to the top. Do not exceed the rack load rating.
Power considerations–Connect only to the power source specified on the unit. When you install multiple electrical components in a rack, ensure that the total component power ratings do not exceed the circuit capabilities. Overloaded power sources and extension cords present fire and shock hazards.
Elevated ambient temperature–If you install the switch in a closed rack assembly, the operating temperature of the rack environment may be greater than the room ambient temperature. Use care not to exceed the 45°C maximum ambient temperature of the switch.
Reduced air flow–Do not compromise the amount of airflow that is required for safe operation of the equipment. Install the equipment in the rack so that the equipment constantly has the correct amount of airflow surrounding it.
Reliable earthing–Maintain reliable earthing of rack-mounted equipment. Pay particular attention to the supply connections other than the direct connections to the branch circuit, for example: Use of power strips.
Do not mount the equipment with the fan panel facing downward.
ReadyRails installation
To easily configure your rack for installation of your S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch, use the ReadyRails rack mounting system provided. You can install the ReadyRails system using the 1U tool-less square-hole method or one of three possible 1U threaded round-hole methods. The tooled installation methods include two-post flush mount, two-post center mount, or four-post threaded mount. To begin installation, separate each rail assembly by sliding the inside rail out of the outside rail.
NOTE: For more installation instructions, see the installation labels attached to the rail assembly.

24

S4100­ON Series installation

Figure 16. Separate rails
1U Tool-less mount installation
NOTE: For more installation instructions, see the installation labels attached to the rail assembly. 1. Face the ReadyRails flange ears facing outward. Place one rail between the left and right vertical posts. Align and seat the
back flange rail pegs in the back vertical post flange. The center extractions show how the pegs appear in both the square and nonthreaded round holes.

Figure 17. 1U tool-less installation

S4100­ON Series installation

25

2. Align and seat the front flange pegs in the holes on the front side of the vertical post. NOTE: Be sure that the rails click into place and are secure.
3. Repeat this procedure for the second rail. 4. To remove each rail, pull on the latch release button on each flange ear and unseat each rail.
Two-post flush-mount installation
NOTE: For more installation instructions, see the installation labels attached to the rail assembly. 1. For this configuration, remove the latch castings from the front side of each ReadyRails assembly, item 1.
To remove the two screws from each front flange ear on the switch side of the rail and remove each latch casting, use a Torx screwdriver. Retain the latch castings for future rack requirements. It is not necessary to remove the back flange castings.

Figure 18. Two-post flush-mount installation
2. Attach one rail to the front post flange with two user-supplied screws, item 2. 3. Slide the plunger bracket forward against the vertical post and secure the plunger bracket to the post flange with two
user-supplied screws, see item 3. 4. Repeat this procedure for the second rail.
Two-post center-mount installation
NOTE: For more installation instructions, see the installation labels attached to the rail assembly. 1. Slide the plunger bracket rearward until it clicks into place and secure the bracket to the front post flange with two
user-supplied screws, item 1.

26

S4100­ON Series installation

Figure 19. Two-post center-mount installation
2. Slide the back bracket towards the post. Secure it to the post flange with two user-supplied screws, items 2 and 3. 3. Repeat this procedure for the second rail.
Four-post threaded installation
NOTE: For more installation instructions, see the installation labels attached to the rail assembly. 1. Remove the latch castings from each end of the ReadyRails assemblies. To remove the two screws each latch casting, use a
Torx driver. Retain the latch castings for future rack requirements.

S4100­ON Series installation

27

Figure 20. Four-post threaded installation

2. For each rail, attach the front and back flanges to the post flanges with two user-supplied screws at each end.

S4100-ON Series installation
You can mount the switch in the 1U front-rack two-post, flush or center configuration, or a four-post configuration. The following is an example of a front-rack configuration: For the 1U two-post configurations, slide the switch into the rails in the same manner as the four-post configurations.

1U front-rack installation

Configure the rails that are attached to the switch.

NOTE: For more information, see the installation instruction labels on the rail.

Attach the inner switch rails to the S4100F­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, or S4148U-ON) switch.
Line up the rail with the mounting heads and attach the rail to the chassis. Slide the rail back until it locks into place. The following shows the detail of the front standoff with the locking tab:

28

S4100­ON Series installation

Figure 21. Switch rail attachment
2. After you install both rails, line them up on the ReadyRails. Slide the switch in until it is flush with the front of rack. About three inches before you fully insert your switch, the rail locking feature engages to keep the switch from inadvertently sliding out and falling.

Figure 22. Front rack installation

S4100­ON Series installation

29

NOTE: Do not the use the mounted Ready-Rails as a shelf or a workplace.
3. Tighten the two thumb screws and rack screws. To remove the chassis from the rack or cabinet, press in the two side-release bars on the chassis at the same time and slide the chassis forward.

Optics installation

The S4100-ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch has the following optic configurations:
NOTE: For the S4148U-ON, for the best optics performance, upgrade the Dell software to 10.4(0.0) or higher.

Table 15. S4100-ON Series optic configurations

Platform

Description

S4128F-ON

28 fixed SFP+ optical ports 2 fixed QSFP28 optical ports

S4148F-ON

48 fixed SFP+ optical ports 2 fixed QSFP+ optical ports 4 fixed QSFP28 optical ports

S4148FE-ON

24 LRM-capable fixed unified SFP+ optical ports 24 LRM-capable fixed SFP+ optical ports 2 fixed QSFP+ optical ports 2 fixed unified QSFP28 optical ports 2 fixed QSFP28 optical ports

S4128T-ON

28 fixed 10GBase-T RJ45 optical ports 2 fixed QSFP28 optical ports

S4148T-ON

48 fixed 10GBase-T RJ45 optical ports 2 fixed QSFP+ optical ports 4 fixed QSFP28 optical ports

S4148U-ON

24 fixed unified Fibre channel or Ethernet SFP+ optical ports 24 fixed Ethernet SFP+ optical ports 2 fixed Ethernet QSFP+ optical ports 4 fixed unified Fibre channel or Ethernet QSFP28 optical ports

For a list of supported optics, see the S4100-ON Series data sheet at www.dell.com/support or contact your Dell representative.
WARNING: When working with optical fibers, follow all warning labels and always wear eye protection. Never look directly into the end of a terminated or unterminated fiber or connector as it may cause eye damage.
CAUTION: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the S4100-ON Series and its components.
CAUTION: To avoid damage to the switch, when you cable the ports, be sure not to interfere with the airflow from the small vent holes above and below the ports.
1. Position the optic so it is in the correct position. The optic has a key that prevents it from being inserted incorrectly.
2. Insert the optic into the port until it gently snaps into place. NOTE: When you cable the ports, be sure not to interfere with the airflow from the small vent holes above and below the ports.

30

S4100­ON Series installation

Optics removal
Remove an optic by pushing the tab on the optic and sliding the optic from the port. When removing optics with direct attach cables (DACs) from the port, pull the release tab firmly and steadily. Before pulling the release tab, you may need to gently push the optic into the port to ensure that it is seated properly. Do not jerk or tug repeatedly on the tab.
Switch power-up
Supply power to the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T- ON, S4148T-ON, and S4148U-ON) switch after you mount it in a rack or cabinet. Dell Technologies recommends reinspecting your switch before powering up. Verify the following: The equipment is properly secured to the rack. Dell Technologies recommends properly grounding the switch. The ambient temperature around the unit, which may be higher than the room temperature, is within the limits specified for
the S4100­ON Series, see Specifications. There is sufficient airflow around the unit. The input circuits are correctly sized for the loads and that you use sufficient overcurrent protection devices. All protective covers are in place. Blank panels are installed if you do not install optional modules.
CAUTION: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the S4100­ON Series switch and its components.
CAUTION: Do not power up the switch if you did not install a fan module.
NOTE: A US AC power cable is included for powering up an AC power supply. You must order all other power cables separately.
Power up sequence
When the switch powers up, the fans immediately come on at high speed. The fan speed slows as the switch continues to boot up.
After switch installation
To configure your switch, after you have securely installed and powered on the S4100­ON Series switch, see your open network installation environment (ONIE)-compatible operating system documentation at https://opencomputeproject.github.io/onie/. For more information about working with the ONIE environment, see your switch documentation at www.dell.com/support.
NOTE: If necessary, to upgrade your software or firmware images, go to the Drivers and Downloads page for your switch at www.dell.com/support.
Switch replacement
The following steps describe removing and replacing a switch. For further assistance when replacing a switch, contact your Dell support representative.
CAUTION: ESD damage can occur when components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the switch and accessories. After you remove the original packaging, place the switch and components on an anti-static surface.
NOTE: Some steps do not apply if you are replacing a different switch or non- Dell switch.
1. Back up the switch configuration to your back-up system or laptop TFTP server. OS10# copy config://startup.xml config://

S4100­ON Series installation

31

2. Disconnect the power source. 3. Label and remove all cables. 4. Remove the switch from the rack.
Simultaneously, press in the two side-release bars on the switch and slide the switch forward. If you are using the fan trays or PSUs in the replacement switch, remove them from the switch.
5. Unpack the new switch. For more information, see Unpack.
6. Install the new switch in your rack or cabinet. For detailed installation instructions, see S4100F-ON series installation. If you are using the fan trays or PSUs from the removed switch, reinsert them in the replacement switch.
7. Connect all the cables. 8. Power on the switch.
For more information, see Switch power up. 9. Establish a connection to the switch CLI. 10. Confirm that the software version of the replacement switch is the same as the previously installed switch.
show version If the software versions do not match, upgrade the replacement switch software using the procedure that is included with the firmware download. 11. Copy the backed-up switch configuration to the new switch. copy tftp://hostip/filepath running-config

32

S4100­ON Series installation

5
Power supplies
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch ships with two AC or DC power supplies. The power supplies have two air-flow directions, normal and reverse. Normal is from the I/O-side to the PSU-side. Reverse is from the PSU-side to the I/O-side. The PSUs are field replaceable. When running with full redundancy–two power supplies installed and running, you can remove and replace one PSU without disrupting traffic.
CAUTION: To prevent electrical shock, ensure that the switch is grounded properly. If you do not ground your equipment correctly, excessive emissions may result. Use a qualified electrician to ensure that the power cables meet your local electrical requirements.
NOTE: Connect the power supply to the appropriate branch circuit protection as defined by your local electrical codes and verify that the remote power source complies with the switch input power specifications.
NOTE: If you use a single PSU, install a blank plate in the other PSU slot. Use power supply 2 (PSU2) as the blank plate slot. To install the blank plate, use a #1 Philips screw driver.
NOTE: ESD damage can occur if components are mishandled. Always wear an ESD- preventive wrist or heel ground strap when handling the S4100­ON Series switch and its components.
Topics:
· Components · AC or DC power supply installation · DC power supply connection
Components
The following power supply options are available for the S4100-ON Series switch: AC or DC power supply with integrated fan AC or DC power supply with integrated reverse flow fan Power supply 1 (PSU1) is on the left side of the switch; power supply 2 (PSU2) is on the right side of the switch.

Figure 23. S4100-ON Series PSUs 1. PSUs The PSUs have an integrated fan that you cannot replace individually; if the fans integrated in a PSU fail, you must replace the entire PSU. You can replace the fan trays individually. For fan tray replacement procedures, see Fans.
WARNING: Prevent exposure and contact with hazardous voltages. Do not attempt to operate this switch with the safety cover removed.

Power supplies

33

CAUTION: Remove the power cable from the PSU before removing the PSU. Also, do not connect the power cable before you insert the PSU in the switch.
NOTE: To comply with the GR-1089 Lightning Criteria for Equipment Interfacing with AC Power Ports, use an external surge protection device (SPD) at the AC input of the router.
PSU LEDs
Solid green–Input is OK. Flashing yellow (amber)–There is a fault with the PSU. Flashing green blink at 1Hz–Switch is in standby/CR state. Off–PSU is off.
AC or DC power supply installation
NOTE: The PSU slides into the slot smoothly. Do not force a PSU into a slot as this action may damage the PSU or the S4100­ON Series switch.
NOTE: Ensure that you correctly install the PSU. When you install the PSU correctly, the power connector is on the right side of the PSU.
NOTE: If you use a single PSU, install a blank plate in the other PSU slot. If you are only using one power supply, Dell Technologies recommends installing the power supply in the first slot, PSU1. Install a blank plate in the second slot, PSU2. 1. Remove the PSU slot cover using a small #1 Phillips screwdriver. 2. Remove the PSU from the electro-static bag. 3. Insert the PSU into the switch PSU slot. Insert the exposed printed circuit board edge connector first. The PSU slot is keyed so that the PSU can only be fully inserted in one orientation. When you install the PSU correctly, it snaps into place and is flushed with the back of the switch.

Figure 24. PSU installation a. Left PSU is PSU1 and right PSU is PSU2. 4. Plug in the appropriate AC 3-prongs cord from the switch PSU to the external power source. 5. Repeat steps 1 through 4 if you have a redundant PSU slot.
NOTE: The switch powers up when you connect the cables between the power supply and the power source.

34

Power supplies

AC or DC power supply replacement
CAUTION: Disconnect the power cable before removing the power supplies. Also, disconnect all power cables before servicing. NOTE: The PSU slides into the slot smoothly. Do not force a PSU into a slot as this action may damage the PSU or the S4100­ON Series switch. NOTE: If a PSU fails, you must replace the entire unit. There are no field serviceable components in the PSU. To request a hardware replacement, see Dell support. NOTE: If you use a single PSU, install a blank plate in the other PSU slot. If you are only using one power supply, Dell Technologies recommends installing the power supply in the first slot, PSU1. Install a blank plate in the second slot, PSU2. 1. Disconnect the power cable from the PSU. 2. Use the grab handle to slide the PSU out of the power supply bay. 3. Use the grab handle on the replacement PSU to slide it into the power supply bay. 4. Attach the power cable to the replacement PSU.
NOTE: The switch powers up when the cables are connected between the power supply and the power source.
DC power supply connection
Each DC PSU kit, sold separately, comes with a connector cable.

Figure 25. DC power supply and connector cable
1. DC PSU power socket 3. Cable connector wires–black, green, and blue 5. DC power source wires–black, green, blue

2. Cable connector with thumb screws 4. Wiring block

1. Strip 1/2 inches of insulation from each of the site’s DC power source wires, item 5. 2. Insert each of the site’s DC power source’s bare wire lengths into the wiring block, matching the wire colors, items 3 and 4.
WARNING: Do not cross the wires–in the wiring block, blue aligns with blue, green aligns with green, and black aligns with black.
3. Use a flat-blade screwdriver to tighten the screws that secure the bare wires into the wiring block. 4. Insert the DC power connector cable end into the power socket of the DC PSU and tighten the thumb screws, items 1 and 2.
WARNING: Never force the power connector into or out of the DC PSU power socket.

NOTE: To remove the power connector from a DC PSU, unscrew the thumb screws and pull the power connector from the DC PSU socket.

Power supplies

35

6
Fans
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch comes from the factory with two PSUs and four fan modules installed in the chassis. The fan modules and the power supplies are hotswappable. In addition to the power supply modules, you can order and install fan modules separately.
NOTE: The S4100­ON Series switch supports two airflow direction options–normal and reverse. All fans and PSUs MUST have the same airflow direction. If you mix the airflow direction, to avoid heat damage to the switch components, you must correct the mixed airflow direction. Airflow is from the I/O panel to the PSU–normal. Airflow is from the PSU to the I/O panel–reverse. Environmental factors can decrease the amount of time required between fan replacements. Check the environmental factors regularly. An increase in temperature and particulate matter in the air might affect performance–for example, new equipment installation. CAUTION: Check the fans at six-month intervals, and replace them as necessary. Regularly monitor the speeds of the fans to accurately determine replacement intervals.
Topics:
· Components · Fan module installation
Components
The following are the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) fan components. S4100­ON Series Fan module S4100­ON Series Fan module–reverse

Figure 26. S4100-ON Series fan modules 1. Fan units
Fan LEDs
Solid green–fan function is normal. Flashing yellow (amber)–there is a fan fault. Off–fan is off.

36

Fans

Fan module installation
The fan modules in the S4100­ON Series switch are field replaceable. When looking at your switch, Slot 1 is on the left side of the switch and Slot 4 is on the right side of the switch.
CAUTION: DO NOT mix airflow directions. All fans must use the same airflow direction–reverse or normal. If you mix the airflow direction, to avoid overheating the switch, correct the mixed airflow. 1. Take the fan module out of the shipping box. 2. Slide the module into the bay.
Figure 27. S4100­ON Series fan modules installation 1. Fan unit
Fan module replacement
To request a hardware replacement, see Dell support. CAUTION: Complete the following steps within one minute or the switch temperature could rise above safe thresholds and the switch could shut down:
1. Slide the fan module out of the bay. 2. Slide the replacement module into the bay.

Fans

37

7
Management ports
Besides the 10/100/1000Base-T RJ-45 ports, the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch provides several ports for management and storage.
NOTE: The output examples in this section are for reference only. Your output may vary.
Topics:
· RS-232 console port access · USB-B console port access · USB storage
RS-232 console port access
The RS-232 console port is on the PSU-side of the switch, as shown.

Figure 28. RS-232 console port 1. RJ-232 console port
CAUTION: Ensure that any equipment attached to the serial port can support the required 115200 baud rate.
NOTE: When connecting the RJ45 console to the patch panel or terminal server using Cat5e or Cat6 Ethernet cables, the maximum cable length is 100m. However, if the Ethernet cable is disconnected from the patch panel or terminal server but connected to the RJ45 console, the maximum cable length is 6m. If the cable is longer than 6m when disconnected from the panel or server, your switch may not boot.
NOTE: Before starting this procedure, ensure your PC has a 9-pin serial port. You must have a terminal emulation program already installed and running on your PC.
NOTE: If your PC’s serial port cannot accept a female DB-9 connector, use a DB-9 male-to-male adaptor.
1. Install the provided RJ-45 connector side of the provided cable into the S4100-ON Series console port. 2. Install the DB-9 female side of the provided copper cable into your PC’s serial port. Or install the DB-9 cable into other data
terminal equipment (DTE) server hardware that you intend to use. 3. Keep the default terminal settings on the console as follows:
115200 baud rate No parity 8 data bits 1 stop bit No flow control

38

Management ports

USB-B console port access
The USB-B console port is on the I/O side of the switch.
NOTE: The S4100-ON Series switches use the Silicon Labs CP2109 USB-B chip. To find the correct USB-B universal asynchronous receiver-transmitter (UART) driver, see https://www.silabs.com/products/development-tools/software/ usb- to-uart-bridge-vcp-drivers.
The terminal settings are the same for the serial console port and the RS-232/RJ-45 console port:
115200-baud rate No parity Eight data bits One stop bit No flow control
When you connect the USB-B port, it becomes the primary connection and, while connected, all messages are sent to the USB-B port.
NOTE: Before starting this procedure, be sure that you have a terminal emulation program that is already installed on your personal computer. Install the appropriate drivers to support the USB-B port. To download Dell drivers, see www.dell.com/ support. If your system requires non-Dell drivers, contact Dell Technical Support for assistance.
To access the USB-B console port:
1. Power on the personal computer. 2. Connect the USB-A end of cable into an available USB port on the personal computer. 3. Connect the USB-B end of cable into the USB-B console port on the S4100-ON Series switch. 4. Power on the S4100-ON Series switch. 5. Install the necessary USB device drivers.
To download Dell drivers, see www.dell.com/support. If your system requires non-Dell drivers, contact Dell Technical Support for assistance. 6. Open your terminal software emulation program to access the S4100-ON Series switch. 7. Confirm that the terminal settings on your terminal software emulation program are as follows: 115200-baud rate No parity Eight data bits One stop bit No flow control

USB storage

USB storage does not automatically mount. The supported file system is FAT. To use USB storage, first mount the device using the following steps: 1. Create a mount directory for the USB.
ONIE:/ # mkdir /mnt/usb
2. View the fixed disks using fdisk. ONIE:/mnt # fdisk -l For internal storage:

Disk /dev/sda: 15.8 GB, 15829303296 bytes 255 heads, 63 sectors/track, 1924 cylinders Units = cylinders of 16065 * 512 = 8225280 bytes

Device Boot /dev/sda1

Start 1

End 1925

Blocks Id System 15458303+ ee EFI GPT

Management ports

39

For USB storage:

Disk /dev/sdb: 30.9 GB, 30942946304 bytes 64 heads, 32 sectors/track, 29509 cylinders Units = cylinders of 2048 * 512 = 1048576 bytes

Device Boot

Start

End

Blocks Id System

3. Mount the device /dev/sdb to the /mnt/usb directory. ONIE:/ # mount -t vfat /dev/sdb /mnt/usb NOTE: The following message displays if the /mnt/usb directory is missing: mount: mounting /dev/sdb on /mnt/usb failed: No such file or directory.
NOTE: The following message displays if the USB device is not seen: mount: mounting /dev/sdb on /mnt/usb failed: No such device or address.

40

Management ports

8

Before you install an OS

After powering on the S4100­ON Series switch, it goes through a power-on self- test (POST).
POST runs every time that the switch is initialized and checks the hardware components to determine if the switch is fully operational before booting. After POST, the switch uses the Grub bootloader.
To select an entry, use the up and down arrow keys. Press Enter to select an operating software (OS) or enter e to edit the commands before booting. Enter c for a command line. The selected entry runs automatically in the operating system.

Grub bootloader example

GNU GRUB version 2.02~beta2+e4a1fe391

+————————————————–+

|*ONIE: Install OS

|

| ONIE: Rescue

|

| ONIE: Uninstall OS

|

| ONIE: Update ONIE

|

| ONIE: Embed ONIE

|

| EDA-DIAG

|

|

|

|

|

|

|

|

|

|

|

|

|

+————————————————–+

Your switch comes with ONIE installed. NOTE: To access ONIE, use the RJ45 console port.

ONIE example
ONIE: Install OS For downloading and installing an OS from a URL Starts ONIE with ONIE Discovery Service (factory default boot)
ONIE: Rescue Starts ONIE without ONIE Discovery Service Useful for running Diagnostics manually
ONIE: Uninstall OS Restore to factory defaults erases any installed OS
ONIE: Update ONIE For downloading and updating ONIE from a URL
ONIE: Embed ONIE For downloading and updating ONIE from a URL and erases any installed OS
During the initial setup, the switch boots to ONIE Install. ONIE Install boots with ONIE Discovery to the console (ONIE:).
NOTE: For more information, see the Open Networking Hardware Diagnostic Guide found at the following sites:
S4148F-ON, S4148T-ON, S4148FE-ON: www.dell.com/support/S4148F-ON/S4148T-ON /S4148FE-ON
S4128T-ON, S4148T-ON: www.dell.com/support/S4128T-ON/S4148T-ON
S4148U-ON: www.dell.com/support/S4148U

Before you install an OS

41

After you have securely installed and powered on the switch, to configure your switch, see your third-party ONIE-compatible OS or the Dell OS documentation.
Topics:
· ONIE service discovery
ONIE service discovery
ONIE attempts to locate the installer through several discovery methods.
To download and run an installer, the ONIE Service Discovery feature follows these steps in order and uses the first successful method found: 1. Search locally attached storage devices for one of the ONIE default installer filenames–for example, onie self update
from the USB. 2. Query to the IPv6 link-local neighbors using HTTP for an installer. 3. Discover TFTP-based image from the DHCP server.
If none of the ONIE Service Discovery methods are successful, you can disable this using the onie-discovery-stop command.
You can install an operating system manually from HTTP, FTP, or TFTP using the onie-nos-install command.
NOTE: If you have a recovery USB plugged into your switch, remove it before using the onie-nos-install command.
The ONIE Install environment uses DHCP to assign an IP address to the management interface–eth0. If that fails, it uses the default IP address 192.168.3.10/255.255.255.0.
To display the IP address, use the ifconfig eth0 command, as shown.
ONIE:/ # ifconfig eth0 eth0 Link encap:Ethernet HWaddr 90:B1:1C:F4:9C:76
inet addr:10.11.53.33 Bcast:10.255.255.255 Mask:255.0.0.0 inet6 addr: fe80::92b1:1cff:fef4:9c76/64 Scope:Link UP BROADCAST RUNNING MULTICAST MTU:1500 Metric:1 RX packets:18 errors:0 dropped:0 overruns:0 frame:0 TX packets:24 errors:0 dropped:0 overruns:0 carrier:0 collisions:0 txqueuelen:1000 RX bytes:1152 (1.1 KiB) TX bytes:6864 (6.7 KiB) Interrupt:21 Memory:ff300000-ff320000
To assign an IP address to the management interface, eth0, and verify network connectivity, use the ifconfig eth0 command, as shown.
ONIE:/ # ifconfig eth0 10.11.53.33/16
Verify the network connection with ping. ONIE:/ # ping 10.11.8.12 PING 10.11.8.12 (10.11.8.12): 56 data bytes 64 bytes from 10.11.8.12: seq=0 ttl=62 time=1.357 ms 64 bytes from 10.11.8.12: seq=1 ttl=62 time=0.577 ms ^C

42

Before you install an OS

9

Specifications

This section lists the S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch specifications.
CAUTION: Operate the product at an ambient temperature not higher than 113°F–45°C.
CAUTION: Lithium Battery Caution: There is a danger of explosion if the battery is incorrectly replaced. Replace only with same or equivalent type of battery. Dispose of the batteries according to the manufacturer’s instructions.
NOTE: For RoHS information, see Restricted Material Compliance.
Topics:
· Chassis physical design · IEEE standards · Agency compliance · USA Federal Communications Commission statement · European Union directive conformance statement · India · Japan VCCI compliance for class A equipment · Korean certification of compliance · Safety standards and compliance agency certifications · Electromagnetic compatibility · Product recycling and disposal
Chassis physical design

Table 16. Chassis physical design Parameter Height Width Depth Chassis weight with factory-installed components
Rack clearance required

Specifications
1.71 inches (43.5 mm)
17.1 inches (434 mm)
18.1 inches (460 mm) PSU/fan tray handle: 1.57 inch (40 mm)
S4128F-ON: 19.66 lbs/8.92 kg (2 PSUs) S4148F-ON: 20.15 lbs/9.14 kg (2 PSUs) S4148FE-ON: 20.15 lbs/9.14 kg (2 PSUs) S4128T-ON: 19.66 lbs/8.92 kg (2 PSUs) S4148T-ON: 20.15 lbs/9.14 kg (2 PSUs) S4148U-ON: 21.63 lbs/9.81 kg (2 PSUs)
Front: 5 inches (12.7 cm) Back: 5 inches (12.7 cm)

Specifications

43

Table 17. Environmental parameters Parameter Operating temperature
Operating humidity
Storage temperature
Storage humidity Maximum thermal output Maximum operational altitude Maximum non-operational altitude Shock Table 18. AC power requirements Parameter Power supply Maximum current draw per switch Maximum power consumption Typical power consumption Table 19. DC power requirements Parameter Minimum and maximum input voltage range Input power at full load
Input current at full load

Specifications S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148TON: 5° to 40°C (50°F to 104°F), continuously S4148U-ON: 5°C to 45°C (50°F to 113°F), continuously -5°C to 45°C (23°F to 113°F) short-term Short term is </= 1% of operational hours per year.
NOTE: Reduce maximum temperature by 1°C/125 meters (1°F/228 feet) above 950 meters (3,117 feet).
5% to 85% (RH), non-condensing, continuously 5% to 90% (RH), non-condensing, short term Short term is </= 1% of operational hours per year. S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148TON: ­40° to 65°C (­40°F to 149°F) S4148U-ON: ­40° to 70°C (­40°F to 158°F) 5% to 95%, non-condensing 470 W = 1260 BTU/Hr 10,000 feet (3,048 meters) 39,370 feet (12,000 meters) Dell Spec SV0115
Specifications 100­240 VAC 50/60 Hz 4.7A/3.9A at 100/120V AC 2.35A/1.95A at 200/240V AC 370 Watts 200 Watts
Specifications -40.5V, ­48V, -60V -40.5V/970W -48V/930W -60V/ 950W, without fan -40.5V/980W -48V/940W -60V/ 960W, with fan -40.5V/23.8A -48V/19.0A -60V/ 15.6A, without fan -40.5V/24.0A -48V/19.2A -60V/ 16.0A, with fan

IEEE standards
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch complies with the following IEEE standards:
802.1ab (LLDP) 802.1ax (Layer 2) 802.1d, 802.1w, 802.1s, 802.1x (Mgmt/Security), 802.3x (Layer 2) 802.3 (1000BASE-KX) 802.3ba (40GbE and 100GbE ports)

44

Specifications

Agency compliance
The S4100­ON Series (S4128F-ON, S4148F-ON, S4148FE-ON, S4128T-ON, S4148T-ON, and S4148U-ON) switch complies with the following safety and agency requirements:
USA Federal Communications Commission statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designated to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installed and used in accordance to the instructions, it may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case users will be required to take whatever measures necessary to correct the interference at their own expense. Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. Dell is not responsible for any radio or television interference caused by using other than recommended cables and connectors or by unauthorized changes or modifications in the equipment. Unauthorized changes or modification could void the user’s authority to operate the equipment. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Figure 29. Canadian department of communication statement
European Union directive conformance statement
This product is in conformity with the protection requirements of EU Council Directive 2004/30/EC on the approximation of the laws of the Member States relating to electromagnetic compatibility. Dell cannot accept responsibility for any failure to satisfy the protection requirements resulting from a nonrecommended modification of this product, including the fitting of non-Dell option cards. This product has been tested and found to comply with the limits for Class A Information Technology Equipment according to CISPR 32/CISPR34 and EN55032/EN55034. The limits for Class A equipment were derived for commercial and industrial environments to provide reasonable protection against interference with licensed communication equipment.
NOTE: This is a Class A product. In a domestic environment, this device may cause radio interference, in which case, you may be required to take adequate measures. European Community Contact Dell, EMEA – Central Dahlienweg 19 66265 Heusweiler Germany Tel: +49 172 6802630 Email: EMEA Central Sales

Specifications

45

India
This product conforms to the relevant Essential Requirements of TEC, Department of Telecommunications, Ministry of Communications, Govt of India, New Delhi-110001.
Japan VCCI compliance for class A equipment
Figure 30. Japan: VCCI compliance for class A equipment This is Class A product based on the standard of the Voluntary Control Council For Interference by Information Technology Equipment (VCCI). If this equipment is used in a domestic environment, radio disturbance may arise. When such trouble occurs, the user may be required to take corrective actions.
NOTE: Use the AC power cords with Dell equipment only. Do not use Dell AC power cords with any unauthorized hardware.
Figure 31. Japan: warning label
Korean certification of compliance
Figure 32. Korean certification of compliance

46

Specifications

Figure 33. Korean package label
Safety standards and compliance agency certifications
IEC 62368-1, 2nd Edition CUS UL 60950-1, 2nd Edition
Meets or exceeds Hi Pot and Ground Continuity testing per UL 60950-1. AS/NZS 60950 CSA 60950-1-03, 2nd Edition EN 60950-1, 2nd Edition EN 60825-1, 1st Edition EN 60825-1 Safety of Laser Products–Part 1: Equipment Classification Requirements and User’s Guide EN 60825-2 Safety of Laser Products–Part 2: Safety of Optical Fibre Communication Systems FDA Regulation 21CFR 1040.10 and 1040.11 IEC 60950-1, 2nd Ed, including all National Deviations and Group Differences
Electromagnetic compatibility
Emissions
International: CISPR 32: Class A Australia/New Zealand: AS/NZS CISPR 32, Class A Canada: ICES-003, Issue-4, Class A Europe: EN55032:2015 (CISPR 32), Class A EN55032 Japan: VCCI Class A Korea: KN32, Class A Taiwan: CNS13438, Class A USA: FCC CFR47 Part 15, Subpart B, Class A
Immunity
EN 300 386 for Network Equipment EN 55024 EN 61000-3-2 Harmonic Current Emissions EN 61000-3-3 Voltage Fluctuations and Flicker EN 61000-4-2 ESD EN 61000-4-3 Radiated Immunity EN 61000-4-4 EFT

Specifications

47

EN 61000-4-5 Surge EN 61000-4-6 Low Frequency Conducted Immunity
Product recycling and disposal
You must recycle or discard this system according to applicable local and national regulations. Dell encourages owners of information technology (IT) equipment to responsibly recycle their equipment when it is no longer needed. Dell offers various product return programs and services in several countries to assist equipment owners in recycling their IT products.
Waste Electrical and Electronic Equipment (WEEE) directive for recovery, recycle, and reuse of IT and telecommunications products
Dell switches are labeled in accordance with European Directive 2002/96/EC concerning waste electrical and electronic equipment (WEEE). The Directive determines the framework for the return and recycling of used appliances as applicable throughout the European Union. This label is applied to various products to indicate that the product is not to be thrown away, but rather reclaimed upon end of life per this Directive.
Figure 34. The European WEEE symbol
In accordance with the European WEEE Directive, electrical and electronic equipment (EEE) is to be collected separately and to be reused, recycled, or recovered at end of life. Users of EEE with the WEEE marking per Annex IV of the WEEE Directive, as shown above, must not dispose of end of life EEE as unsorted municipal waste, but use the collection framework available to customers for the return, recycling and recovery of WEEE. Customer participation is important to minimize any potential effects of EEE on the environment and human health due to the potential presence of hazardous substances in EEE. Dell products, which fall within the scope of the WEEE, are labeled with the crossed-out wheelie-bin symbol, as shown above, as required by WEEE. For information about Dell product recycling offerings, see the WEEE Recycling instructions on the Support page. For more information, contact the Dell Technical Assistance Center.

48

Specifications

10
Dell support
The Dell support site provides documents and tools to help you use Dell equipment and mitigate network outages. Through the support site you can obtain technical information, access software upgrades and patches, download available management software, and manage your open cases. The Dell support site provides integrated, secure access to these services. To access the Dell support site, go to www.dell.com/support/. To display information in your language, scroll down to the bottom of the web page and select your country or region from the drop-down menu. To obtain product-specific information, enter the 7-character service tag, found on the luggage tag, or the 11-digit express
service code of your switch and click Submit. To view the switch service tag or express service code, pull out the tag or enter the show chassis command from the CLI. The luggage tag is on the PSU-side of the switch. To receive more technical support, click Contact Us. On the Contact Information web page, click Technical Support. To access product documentation and resources to install, configure, and troubleshoot the Dell PowerSwitch, see the Dell Networking OS10 Info Hub. To search for drivers and downloads, go to www.dell.com/drivers/. To participate in Dell community blogs and forums, go to www.dell.com/community.

Dell support

49

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals