Haier HP200M1-U1 Monoblock Heat Pump Water Heater Instruction Manual
- June 14, 2024
- Haier
Table of Contents
- Haier HP200M1-U1 Monoblock Heat Pump Water Heater
- Product Information
- Product Usage Instructions
- Product Safety Statement
- Safety warnings
- Technical specifications
- Description of parts and components
- Installation Instructions
- Operating functions
- Checking and maintenance
- Faults and protection
- Contacts
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Haier HP200M1-U1 Monoblock Heat Pump Water Heater
Product Information
Model | HP200M1-U1 | HP250M1-U1 |
---|---|---|
Standards | SAA-230239-EA AS/NZS 2712 SMK41331 AS 3498 WMK26822 | SAA-230239-EA |
AS/NZS 2712 SMK41331 AS 3498 WMK26822
Please read this manual carefully prior to the installation and use of this appliance. The appearance of the water heater given in this manual is for reference only. This product must be installed outdoors.
Product Usage Instructions
- Please read the instructions carefully before installation and use of this appliance.
- Do not puncture or ignite this product.
- The environment-friendly refrigerant R290 used in this product is odorless.
- This product must be installed outdoors.
- This product cannot be discarded or scrapped without correct retrieval of the refrigerant.
- If necessary, please contact Haier Customer Service to obtain the correct disposal method.
- The product must not be stored in an area containing an open flame such as an open fire, gas appliance, or electric heater.
- Before the refrigeration system is repaired, the refrigerant must be removed by a qualified professional.
- Do not use any method to accelerate the defrosting process or clean frosted components of the appliance.
Warning: Risk of damage to the environment. This heat pump contains R290 refrigerant. This refrigerant must not escape into the atmosphere. Refrigerant must be removed and disposed of by a qualified professional.
Interpretation of Marks and Symbols
Symbol | Meaning |
---|---|
Instructions marked with this symbol must be followed. | Failure to do so may |
lead to product damage and harm to the
user.
Information marked with this symbol are forbidden.| Failure to follow this
instruction may lead to product damage
and harm to the user.
Installation Guidelines
- The water heater shall be installed in strict accordance with local wiring regulations.
- The ground line shall not be connected to gas or water pipes, lightning arresters, or telephone lines.
- The water heater must be installed in a location where suitable water drainage is possible.
- The water heater must be installed outside.
- This appliance must be fitted with the pressure-temperature relief valve (PTR valve) supplied with the appliance.
- The PTR valve must be fitted directly to the appliance.
- While bathing, children must be under the guidance of an adult. Children must not play with the appliance.
- The outlet water temperature of a water heater is typically higher than the temperature indicated on the display. Ensure that contact with hot water directly leaving the appliance cannot occur.
- This appliance must be installed with an isolation switch to the power supply. This switch must ensure full disconnection and be in accordance with the wiring rules.
Please read this manual carefully prior to the installation and use of this
appliance.
The appearance of the water heater given in this manual is for reference only.
This product must be installed outdoors.
Dear users of Haier,
Thank you for choosing Haier products.
Please read this manual carefully and follow the operation and safety
instruction to ensure best installation and utilisation of the product.
Product Safety Statement
- This appliance is not intended for use by persons with reduced physical, sensory or mental capabilities, persons with a lack of experience and knowledge, or children under the age of 8 years. Persons in this group must be supervised while using the appliance by a person responsible for their safety.
- Children should be supervised to ensure that they do not play with the appliance.
- Installation must be carried out by qualified professionals. Do not open the cover or panel unless qualified to undertake this work. Contact Haier Customer Service if service or repair work is required.
- This appliance must be permanently connected to mains water supply and continuous electrical supply.
Warning: flammable hazard!
- Please read the instructions carefully before installation and use of this appliance.
- Do not puncture or ignite this product.
- The environment-friendly refrigerant R290 used in this product is odorless.
- This product must be installed outdoors.
- This product cannot be discarded or scrapped without correct retrieval of the refrigerant.
- If necessary, please contact Haier Customer Service to obtain the correct disposal method.
- The product must not be stored in an area containing an open flame such as an open fire, gas appliance or electric heater.
- Before the refrigeration system is repaired, the refrigerant must be removed by a qualified professional.
- Do not use any method to accelerate the defrosting process or clean frosted components of the appliance.
Warning: Risk of damage to the environment
This heat pump contains R290 refrigerant. This refrigerant must not escape
into the atmosphere.
Refrigerant must be removed and disposed of by a qualified professional.
Safety warnings
Safety warnings: To be followed at all times
Interpretation of marks and symbols
Failure to follow these instructions may lead to serious malfunctions of the device and danger to the user.
Instructions marked with this symbol must be followed. Failure to do so may
lead to product damage and harm to the user.
Information marked with this symbol are forbidden. Failure to follow this
instruction may lead to product damage and harm to the user.
The water heater shall be installed in strict accordance with local wiring regulations. The power supply must have a grounding line. Ensure an effective ground connection.| Ground and neutral lines of the power supply must not be connected. The ground line shall not be connected to gas or water pipes,
lightning arresters or telephone lines.
---|---
The water heater must be installed in a location where suitable water drainage
is possible.| The water heater must be installed outside.
This appliance must be fitted with the pressure temperature relief valve (PTR
valve) supplied with the appliance.
The PTR valve must be fitted directly to the appliance.
| While bathing, children must be under guidance of an adult. Children must
not play with the appliance.
The outlet water temperature of a water heater is typically higher than the
temperature indicated on the display.
Ensure that contact to hot water directly leaving the appliance cannot occur.
| This appliance must be installed with an isolation switch to the power
supply. This switch must ensure full disconnection and be in accordance with
the wiring rules.
---|---
Install the water heater in strict accordance with these installation
instructions.| If the power cord is damaged, it must be replaced by a
qualified professional.
Do not put hands or other items into the air grid. This may cause injury or
damage to the appliance.| Risk of damage to the environment. This heat pump
contains the refrigerant R290.
The PTR valve drain must be installed in a continuously downward direction, be open to the atmosphere, be free from blockages, and the potential to frost.
| The PTR valve must be operated every six months to remove lime deposits, and to ensure that it is free from blockages.
Safety warnings: To be followed at all times
- Installation, service, or maintenance of this appliance must be carried out by a qualified professional. Failure to adhere to this may result in damage to the appliance or other property, or cause injury.
- Fit the appliance in accordance with this installation manual.
- Be sure to use only certified parts and accessories in the installation of this appliance.
- Install the product on a base that can hold the filled weight of the appliance.
- Electrical work must be performed in accordance with all local standards and regulations, including AS/NZS3000, and the instructions in this manual.
- This appliance must be connected to a dedicated electrical circuit.
- During installation, ensure that the ground wire is disconnected last.
- If a refrigerant leak occurs, ventilate the area immediately. The refrigerant is flammable, so damage or injury is possible if it reaches an open flame.
- Be aware that the refrigerant contained in this appliance does not have an odour.
- Do not accelerate the defrosting process or clean the evaporator when frosted. Only a qualified person should clean the evaporator.
- Do not pierce or burn this appliance.
- This appliance must be installed outside and be well ventilated. A gas leak in a poorly ventilated area could create an explosion risk.
- Prevent insects and small animals entering the appliance. This may cause electrical shorts, malfunctions or fire.
- Only qualified personnel can handle, fill, purge and dispose of the refrigerant in this appliance.
- If installed in a coastal or high sulfate gas region, corrosion will occur shortening the appliance life.
Safety warnings: To be followed at all times
Loading and unloading requirements
- This appliance shall be carefully handled during transport loading and unloading.
- Ensure that the appliance is not dropped, bumped, or rolled during transportation as this could cause damage to the appliance, potentially creating a refrigerant leak.
Transport requirements
- Local transport regulations should be consulted to determine the maximum allowable appliance quantity or refrigerant (R290) volume that can be transported at any one time.
Storage requirements
- As this appliance contains a flammable refrigerant R290, its storage must be in accordance with local regulations.
- The storage should ensure that there is no potential for damage to the appliance. Any damage could result in a refrigerant leak.
Scrapping and recovery requirements
- Scrapping must only be carried out by a qualified professional. This professional must safely recover the appliance’s refrigerant before the appliance is scrapped. Contact Haier Customer Service to correctly dispose of this appliance.
Technical specifications
Functioning principles of heat pump water heaters
Air source heat pump water heaters mainly consist of a compressor, an expansion valve, a filter, an evaporator, a condenser, and a fan. Powered by electricity, the compressor absorbs low-temperature and low-pressure refrigerant gas from the evaporator. It compresses the gas into high- temperature and high-pressure gas, which is passed through the condenser to transfer heat to the water. The condensed refrigerant is then throttled and depressurized by the expansion valve. It then absorbs heat from the surrounding air via the evaporator.
Technical specifications
Model | HP200M1-U1 | HP250M1-U1 |
---|
Tank
Total water capacity| 195L| 246L
Rated voltage/ frequency| 220-240V/50Hz| 220-240V/50Hz
Tank max pressure| 700kPa| 700kPa
Corrosion protection| Magnesium rod| Magnesium rod
Waterproof grade| IPX4| IPX4
Performance (20°C/15°C Ambient air temperature, 15°C -55°C water temperature)
COP@ 20°C/15°C| 4.49| 4.48
Power input of electric element| 1500W| 1500W
Rated power input of heat pump| 430W| 430W
Maximum power input of heat pump| 750W| 750W
Maximum power input| 2250W| 2250W
Average heating capacity by heat pump| 2000W| 2000W
Heating water capacity| 42L / h| 42L / h
Heating up time (15℃-55℃)| 4.6h| 5.8h
Default temperature setting| 60°C| 60°C
Temperature setting range- with heater| 35°C – 75°C| 35°C – 75°C
Max temperature of the heat pump only| 65°C| 65°C
Max working pressure of refrigerant| 1.0/3.3MPa| 1.0/3.3MPa
Refrigerant type / weight| R290/0.34kg| R290/0.34kg
Sound pressure level @ 1m| 43dB(A)| 43dB(A)
Ambient temperature for heat pump and element| -7~45°C| -7~45°C
Ambient temperature of heat pump| -7~45°C| -7~45°C
Dimension and connections| |
Water inlet and outlet connection| Rp ¾”| Rp ¾”
TPR valve connection| Rp ¾”| Rp ¾”
Drain & Water inlet connection| Rp ¾”| Rp ¾”
Product Dimensions| 6006301658mm| 6006301951mm
Packing dimension with pallet| 7366951940mm| 7366952250mm
Net/Gross weight| 91/116kg| 106/128kg
Filled weight of the appliance| 286kg| 352kg
-
The COP was measured under test conditions with an ambient air temperature of 20˚C/15˚C (Dry Bulb/Wet Bulb) and heating of the water from 15˚C to 55˚C during water heater operation.
-
The noise level was measured at 1 m from the water heater during a Noise Test conducted to Standard GB/T 23137 in a hemi-anechoic chamber within a laboratory.
Description of parts and components
Heat pump layout
Carton contents
Part name| Heat pump water heater| TPR valve|
Instruction manual
---|---|---|---
Quantity| 1| 1| 1
Exploded view of the heat pump
S/N | Description |
---|---|
1 | Display panel & Cover |
2 | Front shell |
3 | Electrical box cover |
4 | Control panel |
5 | Electrical box |
6 | Electronic expansion valve |
7 | Four-way valve |
8 | Compressor |
9 | Evaporator |
10 | Top cover |
11 | Support |
12 | DC motor |
13 | Fan blade |
--- | --- |
14 | Diversion air duct |
15 | Rear shell |
16 | Compressor capacitance |
17 | Thermal cut-out |
18 | Decorative cover |
19 | Waterproof cover |
20 | Heating element |
21 | Sensor pocket |
22 | Magnesium anode |
23 | Communication cable |
24 | Power cable |
Installation Instructions
Transporting the appliance
- During transport or storage, the heat pump water heater should remain in undamaged packaging to prevent damage to the appliance.
- During long periods of transport or storage, the heat pump water heater must be in an upright position.
- For short distance transportation (under one hour), this product may be laid down within 1 hour as per indication on packaging. If laid down, the appliance must be at an upright position for 4 hours prior to its initial startup.
Selection of installation site
- Ensure the install location is stable and level, and that air can flow in and out freely, and will be minimally affected by wind.
- The base or surface can support the filled weight of the appliance and the condensate water can be drained freely.
- If installed on a base, ensure that this base is level to allow correct drainage via the condensate drain at the rear of the appliance.
- The location or position of the appliance will not create nuisance noise for the homeowners or neighbors, especially through proximity to bedrooms.
- Ensure that the location allows condensate and PTR valves to be drained into an area that will not cause damage to the surrounding area.
- There is sufficient space left for installation and maintenance of the appliance.
- There is no strong electromagnetic interference around the appliance that may affect its control functions.
- There are no corrosive vapors such as aerosol sprays, stain removers or household chemicals near the install location. These vapors may corrode the appliance and its fittings.
- Considerations have been made to prevent water pipes from freezing in colder regions.
Installation dimensions
unit: mm
Model | A | B | C | D |
---|---|---|---|---|
HP200M1-U1 | 630 | 267 | 979 | 1658 |
HP250M1-U1 | 630 | 267 | 1272 | 1951 |
Installation clearances
Note: This appliance must be installed in a location where it can be quickly and easily drained and moved to a location with 1000mm clearance above the appliance. This is so the anode to be removed for checking and replacing during the 5 yearly service.
Plumbing installation
WARNING
- FOR CONTINUED SAFETY OF THIS APPLIANCE IT MUST BE INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTUCTIONS.
- THIS APPLIANCE MAY DELIVER WATER AT HIGH TEMPERATURES. REFER TO THE PLUMBING CODE OF AUSTRALIA (PCA), AND ALL LOCAL REGLATIONS ON ADDITIONAL DELIVERY TEMPERATURE CONTROL MUST BE FOLLOWED.
- The water heater must be installed:
- by licensed trades people.
- in accordance with all local codes and regulations and standards including AS/NZS3500.4, AS/NZS 3000, and the Plumbing Code of Australia (PCA).
- The inlet water pressure of water supply must be between 100kPa – 500kPa.
- Inlet water connections: An isolating and non-return valve must be installed on the inlet to the appliance. If the supply pressure could exceed 500kPa, a pressure limiting valve must be installed on the cold-water inlet. If a cold water expansion control valve (ECV) is required by local regulations, a valve of a maximum of 600kPa can be fitted. The correctly sized pressure limiting valve should also be fitted as per the ECV manufacturers specifications. If no ECV is fitted, a pressure limiting valve of a maximum of 500kPa should be fitted.
- The cold-water inlet to the appliance must have a line filter, non- return valve and isolating valve fitted. Combination valves of these functions are also suitable.
- Outlet water connections: A thermostatic mixing or tempering valve must be used when hot water is supplied to fixtures used for sanitary use (i.e. bathrooms) according to AS/NZS 3500.4 requirements.
- For ease of assembly and disassembly of the appliance, it is recommended that mechanical joints are used to connect to the water heater.
- The water inlet and outlet pipes must be fitted to as per the labels at the hot and cold-water connections.
- To avoid damage to the appliance, the inlet water temperature should remain between 10-40°C.
- Before filling the tank, make sure that the cold-water inlet and hot- water outlet of the appliance are open, along with the farthest hot water fixture are opened. The appliance will be correctly filled once water flows continuously from this fixture without air bubbles. Venting through the PTR could cause premature failure of the valve.
- If there is a risk of freezing, hot and cold water pipes connected to the appliance must be insulated with 20mm insulation. Failure to adhere to this may result in a voided warranty if damage due to freezing occurs.
- In accordance with safety rules, a PTR valve (700kPa, 99°C, Rp3/4”) must be installed directly into the PTR valve connection on the appliance. Never block the outlet of the safety valve or its drain line for any reason.
Electrical installation
CAUTION: In order to avoid inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility (off-peak electrical line).
Electrical Safety Requirements
- The installation, service or repair of the electrical components of this appliance must be completed:
- by licensed trades people.
- in accordance with all local codes and regulations and standards AS/NZS 3000.
- The surrounding conditions (ambient temperature, direct sunlight and rainwater) shall be considered during electrical wiring, with effective protective measures taken to suit the environment.
- Materials that are certified to local standards must be used in the installation of this appliance.
- The appliance must be reliably earthed.
- This appliance must be connected to a dedicated circuit. This circuit must be fitted with a circuit breaker that is no greater than 20 A. It is recommended that a residual current device (RCD) is also fitted.
- The circuit to the appliance should be a minimum of 2.5mm² 2-core and earth.
Seismic strapping
FOR NEW ZEALAND INSTALLS ONLY
- The Plumbing and Drainage standard (AS/NZS 3500.4) requires all storage water heaters in New Zealand to be installed with seismic restraints to avoid damage or personal injury if a seismic event should occur.
- To meet this requirement this appliance should be fitted with three stainless steel straps, 25mm wide x 1mm thick.
These straps should be fitted as per the following instructions:
- Top strap: Under the front cover, and no more than 100mm from the top the painted cylinder section of the appliance
- Middle strap: Under the front cover, at the center of the painted cylinder section of the appliance
- Bottom strap: Below the front cover, and no more than 100mm from the bottom the painted cylinder section of the appliance.
Wiring diagram
Commissioning checklist
Installers should check that the following tasks have been completed correctly during the commissioning of this appliance.
- The electrical connection is correctly hard wired.
- Water connections have been fitted correctly and are leak free after the appliance is filled.
- The control panel is operational.
- The supplied PTR valve has been correctly fitted to the appliance, and releases water when the lever is pulled.
- All hot water lines are correctly insulated.
Operating functions
Display
Functions & Protections
- A. Electrical leakage protection
- This appliance features an electricity leakage protection function.
- B. Compressor protection
- When switched on, the appliance will take approximately 3 minutes to start the compressor for heat pump heating.
- C. Automatic defrosting function
- The defrosting mode is automatically activated if the outdoor temperature is low and the compressor has run for some time.
- D. Overload protection
- The working load of the compressor will be high in warm ambient air temperatures.
- To meet hot water requirements and to lengthen appliance life, this product automatically adjusts the fan speed to ensure reliable operation of the compressor.
- E. Anti-freezing function
- The heat pump maintains a minimum temperature to avoid damage to the appliance caused by freezing.
Description of the icons
Note: Under certain conditions, ECO mode may result in shortages of hot water if the ambient air temperature is low.
Installer settings & WIFI connection
WIFI connection
Your appliance can be connected to your home wireless network and operated remotely using the app.
Getting started:
- Ensure your home Wi-Fi network is turned on.
- Press and hold “-” to enter the distribution network status. At this time, the WIFI icon () will flash. If the connection is successful the WIFI icon () will always be on.
- If the connection is not successful, the WIFI icon () will always be flashing.
- It may take up to 10 minutes to connect your appliance.
On your mobile device:
- Download the app from www.fisherpaykel.com/connect
- Register and create an account.
- Add your appliance and set up the Wi-Fi connection.
Checking and maintenance
Warning
- Installation and maintenance of the appliance must be undertaken by a qualified professional.
- Before working on the appliance, shut down the machine and isolate the power supply at the switch.
- Do not touch with wet hands.
- Maintenance operations are important to guarantee optimal performance and extend the life of the appliance.
Checking the PTR valve
- Operate the PTR valve at least once every six months to ensure it is functioning correctly. If the valve fails to release water when the lever is activated, check for blockages. If none exist, call Haier Customer Care or a qualified professional to resolve the issue.
Checking the pipework
- Check the watertightness of the water connections and piping.
Cleaning the fan
- The fan should be checked for dust annually. If cleaning is required call Haier Customer Service or a qualified professional.
- Checking and cleaning the evaporator must be completed by a qualified professional.
Warning
- The evaporator fins are sharp and are a potential injury risk.
- Avoid damaging the evaporator fins as this can affect the performance of the appliance.
- It is recommended that the evaporator is cleaned every two years.
- Clean the evaporator with a soft brush and water if required. Do not use cleaners on the evaporator fins.
Checking the condensate drain
- Check the condensate drain for blockages as they have the potential to flood the appliance.
Checking the anode
- Checking and replacing the anode must be carried out by a qualified professional.
- To avoid irreversible corrosion of the cylinder, it is recommended to check the anode every five years, and replaced if required.
Faults and protection
Water Quality
- A breach of this condition may void the warranty in the event of damage caused by water quality exceeding these characteristics.
- Water supply from an unfiltered water source that may be highly conductive or have a high mineral content may void the system warranty.
- The following characteristics should not be exceeded in order for the warranty to be conditions not to be breached.
Water Properties/ Acceptable Levels
- Total hardness: 200 mg/litre or ppm
- Total Dissolved Solids (TDS): 600 mg/litre or ppm
- Chloride: 250 mg/litre or ppm
- Magnesium: 10 mg/litre or ppm
- Sodium: 150 mg/litre or ppm
- pH: Min 6.5 to Max 8 .5
- Electrical conductivity: 850 μS/cm
Faults and protection
Fault type | Action | Digital indication | Release |
---|---|---|---|
Communication fault | Communication failure between Wi-Fi module and control | ||
board |
F0
|
Please call Haier Customer Service to resolve the issue.
Compressor protection
| Operating temperature protection| F2
Air exhaust temperature protection| F3
Evaporation high-temperature protection| F5
Compressor over-current protection| Over-current protection| F6
Electricity leakage alarming| The system will automatically cut off
power supply if any line fault occurs
| E1|
Please call Haier Customer Service to resolve the issue.
Over temperature alarming| The actual water temperature≥85℃| E2
Fault of the inner temperature sensor| If short circuit or circuit break
occurs to the sensor| E3
Fault of the ambient temperature sensor| If short circuit or circuit break
occurs to the sensor| E4
Fault of the evaporation temperature sensor| If short circuit or circuit break
occurs to the sensor| E5
Fault of the air exhaust temperature sensor| If short circuit or circuit break
occurs to the sensor| E6
Fault of the air intake temperature sensor| If short circuit or circuit break
occurs to the sensor| ED
Communication fault| Communication of main controlpanel and the display panel
is abnormal| E7
Pressure switch protection| Action of the pressure switch at the exhaust
outlet| E8
Ambient temperature protection| Ambient or outdoor temperature
<-7℃ or>45℃
| E9
Fault of the Off-peak power switching signal| If not received the Off-peak
signal when selecting switch signals by power companies|
EF
Fault of the fan| Fan blade is stuck or fan and control panel communication failure| L7
The symbol on the product or on its packaging indicates that this product is not to be treated as regular household waste. It must be taken to a recycling collection point for electronic equipment. By properly disposing of this product, you are contributing to the preservation of the environment and the wellbeing of your fellow citizens. Improper disposal is hazardous to health and the environment. You can obtain further information on how to dispose of this product correctly by calling Haier Customer Service.
Contacts
Haier Appliances
- Australia: 1300 729 948
- haier.com.au
- New Zealand: 0800 424 372
- haier.co.nz
Fisher & Paykel Australia Pty Ltd,
- Level 1, 1 Eden Park Drive, Macquarie Park, NSW 2113.
- Phone Customer Care: 1300 729 948
- Email: customer.care@haier.com.au
Fisher & Paykel Appliances Ltd,
- 78 Springs Road, East Tamaki, Auckland 2013.
- Phone Customer Care: 0800 424 372.
- Email: customer.care@haier.co.nz
References
- Home Appliances | Haier New Zealand
- Home Appliances | Haier Australia
- Connected Appliances | Smart Home | Fisher and Paykel US
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>