ELTIME CONTROLS RN Series Earth Leakage Relay Instruction Manual
- June 13, 2024
- ELTIME CONTROLS
Table of Contents
ELTIME CONTROLS RN Series Earth Leakage Relay
Product Information
The EARTH LEAKAGE RELAY – RN SERIES is a device designed to detect and protect against electrical leakage and faults. It is commonly used in electrical systems to prevent electric shock hazards and damage to equipment caused by ground faults.
Connections
The relay has the following wiring connections for general MCB (Miniature Circuit Breaker) with shunt trip coil:
- EARTH
- S
- U
- L1
- P
- L2
- P
- L3
- LN
- Y
It also has wiring connections for general MCB with under voltage opening coil. The relay requires auxiliary power and can be connected to a Core Balance Transformer. It has inputs and outputs labeled as 56, 78, S1, S2, NO (Normally Open), NC (Normally Closed), and C (Common).
RN-R Switch Settings
The RN-R Switch Settings allow you to configure the trip point and time delay of the relay:
Trip Point, In (Amps) | Time Delay (seconds) |
---|---|
0.03 (30mA) | 0.02 (20ms) |
0.1 (100mA) | 0.1 (100ms) |
0.3 (300mA) | 0.3 (300ms) |
0.5 (500mA) | 0.5 (500ms) |
1 | 1 |
3 | 3 |
5 | 5 |
The trip point, In, represents the current at which the relay will trip and activate its protection mechanism. The time delay determines how long the relay will wait before tripping after detecting a fault.
Specification (Relay)
- Trip Point, In: 30mA (RN-0.03), 300mA (RN-0.3), and customizable from 30mA to 5A (RN-R)
- Reset value: < 50%In
- Accuracy: < 2%
- Time Delay: RN-0.03 & RN-0.3 Instant
Product Usage Instructions
To use the EARTH LEAKAGE RELAY – RN SERIES, follow these steps:
- Ensure the relay is properly wired according to the provided connections for your specific setup. Refer to the user manual for detailed wiring instructions.
- Connect the relay to an auxiliary power source and, if required, to a Core Balance Transformer.
- Set the desired trip point and time delay using the RN-R Switch Settings. Refer to the table provided in the user manual for available options.
- Once the relay is properly configured, it will continuously monitor the electrical system for ground faults and leakage.
- If a fault is detected and the current exceeds the trip point, the relay will activate its protection mechanism.
- The relay will initiate a trip signal and may open the circuit, disconnecting power to the affected area or equipment.
- After the fault is resolved, the relay will automatically reset once the current drops below the reset value.
It is important to regularly inspect and test the EARTH LEAKAGE RELAY – RN SERIES to ensure proper functionality and reliability. Consult the user manual for maintenance guidelines and recommended testing procedures.
Connections
Wiring connections for general MCB with shunt trip coil
Wiring connections for general MCB with undervoltage opening coil
More Information
RN-R Switch Settings
Trip Point, In (Amps) | Time Delay (seconds) |
---|---|
0.03 (30mA) | 0.02 (20ms) |
0.1 (100mA) | 0.1 (100ms) |
0.3 (300mA) | 0.3 (300ms) |
0.5 (500mA) | 0.5 (500ms) |
1 | 1 |
3 | 3 |
5 | 5 |
LED Indication
Power LED | Trip LED | Indication |
---|---|---|
On | Off | System OK |
Blinking | On | Transformer continuity failure |
On | On | Relay tripped – earth fault |
On | Blinking every 2 sec | Current 25-50% of trip level (RN-R only) |
On | Blinking every 1 sec | Current 50-75% of trip level (RN-R only) |
On | Blinking every 0.5 sec | Current 75-100% of trip level (RN-R only) |
Specifications
Specification (Relay)
- Trip Point, In:
- 30mA (RN-0.03), 300mA (RN-0.3)
- 30mA to 5A (RN-R) – see table
- Reset value < 50%In
- Accuracy:
- < 2%
- Time Delay:
- RN-0.03 & RN-0.3 Instant (<40ms)
- RN-R 0.02 to 5 seconds – see table
- LED Indication:
- Green: ‘On’, Red: ‘Trip’
- Test Circuit:
- Manual push button
- Relay Output:
- Single pole changeover contact
- 5A at 250Vac (cosØ=1) or 30Vdc
- 3A at 250Vac (cosØ=0.4)
- Isolation:
- 2.5kV rms 50Hz for 1 minute between input / output / auxiliary
- Power Supply:
- 110 or 230Vac ±20% (4VA)
- Operating Temperature:
- -5ºC to 50ºC
- Enclosure:
- Mount: 35mm DIN rail (DIN-EN 50022)
- Screw type terminals (4mm² entry)
- Weight:
- 200g
- Markings:
- CE marked
Specification (Core Balance Trans.)
- Maximum Operating Voltage:
- 720Vac
- Test Voltage:
- 3kV rms 50Hz for 1 minute
- Calibration Temperature:
- 20ºC ± 5ºC
- Operating Temperature:
- -5 to 50ºC
- Weight:
- See table
- Markings:
- CE marked
Specification subject to change without notice.