INTERMATIC P40000 Series Pool Spa Equipment Controls Instruction Manual

June 13, 2024
Intermatic

INTERMATIC logo P40000 SERIES
POOL/SPA EQUIPMENT CONTROLS
INSTALLATION
OPERATION & SERVICE MANUAL

P40000 Series Pool Spa Equipment Controls

INTERMATIC P40000 Series Pool Spa Equipment Controls

CONTROL PANEL FOR INDOOR/OUTDOOR USE
Suitable for Pool Equipment Control and for Direct Connection of Underwater Lights ELECTRICAL RATINGS: See inside Enclosure Door

WARNING

Risk of electric shock!
Test ground fault protection regularly. If it fails, do not use Pool or Spa. Contact qualified service professional for help.
Do not use this control as a power disconnect, it could turn ON unexpectedly.
Disconnect electricity at the main Panel before servicing this control or the equipment(s) connected to it.

GENERAL INFORMATION

Intermate Pool and Spa load centers are complete in construction and shall be installed in accordance with NEC requirements as applicable. These enclosures are provided with provisions for single-gang certified switching devices and an extra low voltage transformer certified for use with underwater pool lights with a breaker base. Enclosures with breaker bases are certified as industrial controls for specific use.
The Transformers supplied in these panels are specifically designed to supply 12 volts to underwater pool/spa lights. A grounded shield between the primary and secondary winding assures safe operation and the built-in circuit protection  will disconnect power to the transformer in case of overload. These transformers are suitable for direct connection to underwater Pool and Spa lights.
The all-weather enclosure contains provisions to install a switch inside as well as a switch or GFCI receptacle on the outside.

Transformer Rating| Input
60 Hz.| Secondary Output
---|---|---
Lamp Watts*| Volts
100W
300W| 120V. 1 Amp Max.
120V. 3 Amp Max.| 100 Max.
300 Max.| 12, 13 or 14
12, 13 or 14

  • Any combination of bulbs, any tap.

CAUTION

Risk of injury or property damage!
Do not install or operate this equipment and other associated equipment without basic safety precautions.
Read and follow the safety instructions listed below and other basic safety precautions before installation or operation of this control and other associated equipment.

  1. This control must be installed by a qualified person, according to the national and local electrical codes.
  2. Install this control not less than 5 feet (3 meters in Canada) from inside edge of pool and 1 foot (30cm) above ground.
  3. USE COPPER CONDUCTORS ONLY rated 90˚C minimum.
  4. Do not exceed maximum ratings of individual components, wiring devices and current carrying capacity of conductors.
  5. For control grounding, bonding, installing and the wiring of underwater lights, refer to Article 680 of the National Electrical Code or Article 68 of the Canadian Electrical Code.
  6. The control should not operate any equipment which would cause bodily injury or property damage should it be activated unexpectedly.

INSTALLATION

  1. Remove the four #10 hex head screws from the back of the enclosure and attach mounting brackets to enclosure.
  2. Select the proper location for the Control Panel and hang enclosure on a flat vertical surface or other support, using hardware suitable for the purpose.
  3. Prepare the necessary conduit runs, terminate them at both ends and pull in the conductors as specified by the installation layout.
  4. If external bonding is required, install a bonding lug at bottom of enclosure and bond installation according to code requirements.
  5. The enclosure must be grounded as required by NEC, Article 680 and any applicable local codes. For Canadian installations, the transformer supply circuit must be protected by a ground fault circuit interrupter.
  6. If this enclosure is used for direct connection of underwater lights, refer to 1999 NEC 68021(b), 2002 NEC 680-24(b) or CEC 68-060, 062 and 066 for further details.INTERMATIC P40000 Series Pool Spa Equipment Controls - Figure
  7. Make sure that all unused transformer taps (leads) are separately insulated.
  8. Use the tables at the top of page 3 as a guide to determine the correct wire size.
  9. Check voltage at lamp terminals after installation. It should be 12+ 0.3 volts. 10. Install front panel over wiring compartment. The control is now ready for programming, see OPERATION section on Page 3.

Transformer Cable – Voltage Selection Chart


Length of Cable| 100 W Transformer
10 ft| 13 V| 12 V| 12 V| 12 V| 12 V| 12 V
25 ft| 13 V| 13 V| 12 V| 12 V| 12 V| 12 V
50 ft| 14 V| 13 V| 13 V| 12 V| 12 V| 12 V
75 ft| | 14 V| 13 V| 13 V| 12 V| 12 V
100 ft| | | 13 V| 13 V| 13 V| 12 V
125 ft| | | 14 V| 13 V| 13 V| 12 V
150 ft| | | 14 V| 13 V| 13 V| 13 V
175 ft| | | 14 V| 14 V| 13 V| 13 V
200 ft| | | | 14 V| 13 V| 13 V
250 ft| | | | 14 V| 13 V| 13 V
Wire Gauge (AWG)| #16*| #14| #12| #10| #8| #6

  • Minimum Gauge Cable
    **Blank fields indicate conditions not suited for wiring

Transformer Cable – Voltage Selection ChartINTERMATIC P40000 Series Pool Spa
Equipment Controls - Featured Image


Length of Cable| 300 W Transformer
10 ft| 12 V| 12 V| 12 V| 12 V
25 ft| 13 V| 13 V| 12 V| 12 V
50 ft| 13 V| 13 V| 13 V| 13 V
75 ft| | 14 V| 13 V| 13 V
100 ft| | 14 V| 14 V| 13 V
125 ft| | | 14 V| 13 V
150 ft| | | 14 V| 14 V
175 ft| | | | 14 V
200 ft| | | | 14 V
250 ft| | | | 14 V
Wire Gauge (AWG)| #12*| #10| #8| #6

  • Minimum Gauge Cable
    **Blank fields indicate conditions not suited for wiring

LIMITED WARRANTY

Warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.intermatic.com. This warranty is made by: Intermate Incorporated, 1950 Innovation Way, Suite 300, Libertyville, IL 60048.
For additional product or warranty information go to: http://www.Intermatic.com or call 815-675-7000.
Because of our commitment to continuing research and improvements, Intermate Incorporated reserves the right to make changes, without notice, in the specifications and material contained herein and shall not be responsible for any damages, direct or consequential, caused by reliance on the material presented.

INTERMATIC logoINTERMATIC INCORPORATED,
LIBERTYVILLE, IL 60048

http://www.intermatic.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Intermatic User Manuals

Related Manuals