KIPP ZONEN DustIQ PV Soiling Monitoring Instruction Manual
- June 13, 2024
- KIPP ZONEN
Table of Contents
KIPP ZONEN DustIQ PV Soiling Monitoring Instruction Manual
Requirements
-
Allen key 6 mm
-
USB to RS-485 converter
-
Spanner 13 mm
Cable connection
Wire | Function | Connect with |
---|---|---|
Yellow | Modbus® RS-485 | Data + |
Grey | Modbus® RS-485 | Data – |
White | Power 12 to 30 VDC | |
Black | Power ground | |
Blue | Modbus® common / Ground | Ground* |
Shield | Housing | Ground* |
- Connect to ground if DustIQ is not grounded
Default
- Modbus® baud rate 19200
- Data bits 8
- Parity even
- Stop bits 1
- Address 1
- Factory dust profile Common desert dust
Push-Pull: Connect the supplied cable to the socket labelled ‘Host’
Positions and options
Dimensions
TARE INSTRUCTIONS
Needed before tare
- Connected, working clean DustIQ with software version 2.15 or higher
- DustIQ must be operative for minimal 3 minutes
- Modbus registers 20-40 must be read and logged for soiling ratio’s, transmission losses, status flags, dust slopes etc. (see manual section 4.2)
- A person on-site and a remote person reading DustIQ data and the manual .
- If moving from the back of the DustIQ to the front takes more than 20 seconds, then consider adding a third person, just to push the button
Time needed is 15 minutes
No clouds
Clear, sunny
Between 2 hours before and after solar noon
Clean, demineralised water and
a sponge
Clean, dry cloth
DustIQ LED light interpretation
Regular operation, 5 seconds of blue led light with a 60 second interval
Feedback during the Tare or field calibration are given by the 2 sensors and the calibration button. There are 2 cases:
- Slow blinking is 1x per second, confirmation and DustIQ awaiting next input
- Fast blinking is 10x per second, this is the error signal for further information see error code in register 27
Both signals last 30 seconds in total, before normal operation restarts.
On-Site
Validate installation| During the procedure:
Do not cast a shadow on the DustIQ
Do not cover the sensors
- The DustIQ is mounted properly as per instructions.
- Power cable is connected to the DustIQ.
- DustIQ is cleaned.
|
No action needed
---|---|---
Wait| Wait 3 full minutes for the DustIQ to stabilize| No action needed
Push button 3 times| Push the Calibration button on the underside of the
DustIQ 3 times in rapid succession.
Do NOT block the sunlight on the DustIQ| No action needed
Wait| Sensors and button light up continuously for 1 minute.| No action
needed
Check sensors or button| Slow blinking = OK and finished. Inform person
2 of successful completion.| Confirm successful calibration in register 27
(manual section 4.2.2.)
| Fast blinking = error. Inform person 2 .| If unsuccessful read error code in
register 27 for possible reasons and solutions.
BEFORE CALIBRATION
Needed before calibration
- Connected, working, soiled DustIQ (3% transmission loss) with software version 2.15 or higher
- DustIQ must be operative for minimal 3 minutes
- Modbus registers 20-40 must be read and logged for soiling ratio’s, transmission losses, status flags, dust slopes etc. (see manual section 4.2)
- A person on-site and a remote person reading DustIQ data and the manual .
- If moving from the back of the DustIQ to the front takes more than 20 seconds, than consider adding a third person, just to push the button.
- A clear sunny sky
Time needed is 15 minutes
No clouds
Clear, sunny day
Between 2 hours before and after solar noon
Clean, demineralised water and a sponge
Clean, dry cloth
The sky must be free of clouds and airplane contrails for at least 10 minutes.
| On-Site
During the procedure:
- Do not cast a shadow on the DustIQ
- Do not cover the sensors
| Remote office
Remote office
---|---|---
Contact Remote Office| Contact Remote Office| Check register 26 for enough
soiling and sun and inform on-site person 1. (the expected value is 3), for
further details check the cheat sheet
Local Check| Check for clear sky and no clouds. Inform person of start of
calibration when OK. Do not cast a shadow on the DustIQ during the calibration
process!| No action needed.
Push calibration button for 3 seconds| | No action needed.
Check sensors or button flash| Slow blinking = proceed with next step Fast
blinking = stop and inform person| During calibration 0 will be presented in
register 27. If an error occurs register 27 is updated with a specific code.
(manual section 4.2.2)
Push button again (for 3 sec.)| Do NOT block the sunlight on the DustIQ!
| No action needed
Wait| Sensors and button light up continuously for 1 minute Do not cast a
shadow on the DustIQ Do not touch the DustIQ| No action needed. Wait for
update from on-site person .
Check sensors or button| Slow blinking = OK and finished Inform person of
successful completion| Confirm successful calibration in register 27 (manual
section 4.2.2). and optionally read and use new dust slopes. (manual section
4.1).
| Fast blinking = error
Inform person| If unsuccessful read error code in register 27 for possible
reasons and solutions.
REMOTE OFFICE cheat sheet
Value | Meaning | Remarks |
---|---|---|
0 | There is not enough sun light and not enough soiling on the sensors | On- |
site check for clear sky and local time is between 2 hours before and after
local solar noon. Check if there is >3% transmission loss in registers 21 and
25.
1| Enough sunlight| There is > 500 W/m² solar irradiation on the DustIQ. But
not (yet) enough soiling so wait for more soiling
2| Enough soiling on both sensors| There is >3% transmission loss in registers
21 and 25. But not enough sunlight (yet).
3| Enough sunlight and soiling on both sensors. Calibration possible| Contact
people on-site to check readiness, time window and sky conditions and if OK
they can start the 2 minute waiting time followed by pushing the button and
cleaning.
4| Unstable soiled measurements| Before calibration the DustIQ, must have had
2 minutes of stable sunlight 4 and the two sensors must have had 2 minutes of
stable soiling.
Register 27 after tare
Value | Meaning | Remarks |
---|---|---|
3000 | Tare successful | Tare procedure is completed. |
3006 | Attempted to start tare procedure without waiting the required |
2minutes to allow for stabilization
3010| Hardware error| Signal is to low possible hardware failure.
Register 27 after calibration
Value | Meaning | Remarks |
---|---|---|
1 | Successful calibration | The dust slopes in registers 36 and 38 have |
changed. Refer to chapter 4.1 to see how older data or data from other DustIQs
on the same PV plant can be updated with the new calibration values. Valid
values for register 36 and 38 are from 30 (extreme white soiling) to 300 (very
dark soiling)
1000| Attempted to start without enough sun| Calibration was halted. Nothing
has been changed. Register 26 should be checked before pushing the button.
1001| Attempted to start without enough soiling| Calibration was halted.
Nothing has been changed. Register 26 should be checked before pushing the
button. 1002
1002| Attempted to start with unstable sunlight on PV cell| Clouds or a person
has blocked the sunlight. the sunlight in the 2 minutes before pushing the
button.
1003| Attempted to start with unstable dust measurement| On-site personnel
touched the glass area of sensor 1 or 2 during the 2 minutes before pushing
the button.
1004| Button pushed but too short. This prevents accidental start| Push the
button 3-5 seconds for the calibration to start.
1005| Time out. The button hasn’t been pushed a second time within 2 minutes
from first push.| Could be by accident. Not pushing the button a second time
is also a safe escape from the calibration procedure.
1006| Field calibration started withing 3 minutes of start-up (without
waiting)|
2010| Sensor 1 showed too little soiling change.| Sensor 1 not properly
cleaned or dried
2020| Sensor 2 showed too little soiling change.| Sensor 2 not properly
cleaned or dried.
2030| PV cell showed unreliable little change.| PV cell not properly cleaned
or dried. Or PV cell much cleaner than the sensors by e.g. accidental
cleaning. OR Clouds or a person has blocked the sunlight.
2040| Clean measurement unstable| Disturbance during clean measurement.
2050| Dustslope out of range| Dustslope is higher than expected but procedure
was correct.
2060| Dustslope factor out of range| Dustslope is higher than expected but
procedure was correct.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>