HITACHI PC-ALHZ5Q IR Receiver Kit Installation Guide
- June 13, 2024
- Hitachi
Table of Contents
- HITACHI PC-ALHZ5Q IR Receiver Kit
- Product Information
- Product Usage Instructions
- Operation & Installation Manual for IR Receiver Kit
- Foreword
- Safety Summary
- Installation
- Compatible Indoor Unit Models
- Before Installation
- Key Points for Installation
- Set the IR Receiver Kit
- Adjacent Unit Setting Mode
- About Simultaneous Control of Multiple Units
- Method for Test Running with the Wireless Remote Controller
- Alarm Code Indication
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HITACHI PC-ALHZ5Q IR Receiver Kit
Product Information
- The IR Receiver Kit is a general control product that requires support from an air conditioning system. It is designed to receive signals from a wireless remote controller and provide control functions for the air conditioning system. Please consult your dealer for more information on the specific functions and compatibility of this product.
- It is important to note that this product should not be installed in certain locations to avoid potential damage or safety hazards. These include places with oil splash or vapor, areas with high sulfur gas content (such as hot springs), coastal regions with high salt content, alkaline or acidic environments, places accessible to children, humid areas, places facing the air outlet of the air conditioner, places with excessive dust, and areas under construction.
- To ensure proper functioning of the product, it is advised not to position any devices that emit waves directly towards it, as this can cause malfunction.
Product Usage Instructions
Installation:
- Read the operation and installation manual in detail before starting the installation process.
- Ensure that the product is installed strictly according to the instructions provided in the manual to prevent accidents such as electric shock, fire, and falling objects.
- Choose a location that can bear the weight of the product to avoid potential injuries from falling objects.
- Avoid installing the product in areas where combustible gases may be present to prevent accidents such as electric shock and fire.
- If the product with the IR Receiver Kit is interfered by external light sources (such as fluorescent lamps), it may not receive signals from the wireless remote controller properly.
Electrical Installation:
- It is recommended to hire a qualified dealer to handle the electrical installation to prevent electric shock.
- Follow the instructions provided in the manual and ensure that a dedicated circuit is used to avoid accidents such as electric shock and fire.
- Avoid exposing the product to heated wires, as it may cause fire and electric shock.
- Before performing any maintenance or inspections related to electrical wiring, ensure that the power supply is completely disconnected to prevent electric shock.
- Avoid routing the power cable near other cables to prevent interference and malfunctions.
Compatible Indoor Unit Models:
The IR Receiver Kit (Model: PC-ALHZ5Q) is compatible with the following indoor unit models:
- Ducted Type: PPIM-2.0~6.0UFA1NQ, PPIH-3.0~6.5UFA1NQ
Please refer to the manual for any additional instructions or safety precautions related to the installation and usage of the IR Receiver Kit.
Operation & Installation Manual for IR Receiver Kit
Model: PC-ALHZ5Q
Please read this document in detail before installation.
Note: This document must be used in the following installation operations and
therefore must be well kept by the user.
(Handling and installation) → (wiring) → (trial running) → (user)
Foreword
This product is a general control product, and its functions need support of the air conditioning system. Please consult your dealer for further details.
-
When selecting the installation place, first consideration shall be given to the convenience of users and the place must be approved by the user.
Please do not install this product at the following places:- Places where there is oil splash (including mechanical oil) and vapor, and places where more sulfide gases, such as hot springs, exist (which possibly results in fire and deforming, corroding and damaging the product);
- Coastal regions with high salt content, and alkaline or acidic environment (possibly result in the product being corroded);
- Places where children are accessible;
- Humid places;
- Places facing towards the air outlet of the air conditioner;
- Places where there is much flying dust or dust;
- Places under construction.
-
When using devices like certain medical equipment that produce electromagnetic waves, make sure not to position the device in a way where the waves it creates are pointed directly at this product. This helps prevent the device from malfunctioning.
Safety Summary
- Please read this manual carefully before using the product and file it for future reference.
- After installation, conduct trial running; after confirming that there is no anomaly, please introduce the operation and maintenance methods to the user and ask the user to keep the manual well.
Signal Words
-
WARNING
Indicates a hazardous situation that, if not avoided, could result in death or serious injury. -
CAUTION
Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury. -
Indicates a mandatory issue, instructing behaviors of non-specific general users.
-
Indicates a forbidden issue.
Installation
-
Please install the product in strict accordance with this manual. Otherwise, accidents such as electric shock, fire and falling may happen.
Please install the product at the place capable of bearing its weight. Otherwise, falling object may cause injury. -
WARNING
Please do not install the product at any place where combustible gas may be generated or come in. Otherwise, accidents such as electric shock and fire may happen.
Install the product only after the power supply is disconnected. Otherwise, electric shock may happen. -
CAUTION
If the product with the IR Receiver Kit is interfered by external light source such as fluorescent lamp (frequency-varying fluorescent lamp), it may not receive wireless remote controller signals normally.
Electrical Installation
WARNING
- The electrical installer shall have qualifications for such activity. Please appoint a qualified dealer to do the job. Otherwise, electric shock may happen.
- During electric installation, please comply with applicable national standards and the Instructions for Use and make sure a dedicated circuit is used. Otherwise, accidents such as electric shock and fire may happen.
- Please use the required connecting cable. Otherwise, fire and electric shock may happen.
- Cable shall be connected securely and firmly. Any loose connection may lead to heated wires which may cause fire and electric shock.
- When the control board of the product or its related device must be taken out due to electrical wiring and spot inspection etc., please completely disconnect the power supply first. Otherwise, electric shock may happen.
CAUTION
The routing of communication cable shall not be in parallel with that of power cable. Otherwise, it may generate interference causing malfunctions.
Compatible Indoor Unit Models
Types of indoor devices compatible with the IR Receiver Kit
Model of IR Receiver Kit | Model of Compatible Indoor Unit |
---|---|
PC-ALHZ5Q | Ducted Type |
CAUTION
Do NOT turn ON the power source, unless the preparation for test running is completed.
- Read this manual carefully before installation work for correct performance.
- Read this manual together with the instruction manual for the indoor unit and wireless remote controller.
Before Installation
Please confirm the following accessories are in the package before installation.
Key Points for Installation
NOTES:
- Install the IR Receiver Kit onto the wall or ceiling near the indoor unit.
- Install the IR Receiver Kit and indoor unit at the same time.
- In case that the IR Receiver Kit is installed after installing the indoor unit, turn OFF the power source of the indoor unit.
- Check to ensure that the distance between the IR Receiver Kit and the indoor unit is shorter than 5m.
- Check to ensure that the distance between the IR Receiver Kit and the EMI Source is larger than 3m.
- Remove the cover by using slotted screwdriver.
Install the IR Receiver Kit onto the wall or ceiling as follows:
A. In Case of Exposing Cable
- Fix the fixing bracket of kit by using screw (A) at 4 locations.
- Cut one of the knockout holes at the cover.
- Lead the cable though the groove and draw out the cable from the knockout hole.
- Attach the cover.
Do not clamp the cable when attaching the cover.
B. In Case of Concealed Cable
- Prepare the following box (Field-Supplied).
- Insert the cable into the rigid metal conduit.
- Fix the fixing bracket of kit by using screw (Field-Supplied).
This figure shows the case of Switch Box for 1 Controller.
- Attach the cover same as A-(4).
Remove the cover of indoor unit electrical control box and connect the cable to the terminals A and B of the terminal board (white).
NOTE:
After connecting the cable, bind up the remaining cable length portion by band
(Factory-Supplied) and put them in the electrical control box.
Set the IR Receiver Kit
-
Optional function setting
-
Buttons are for emergency operation. It is used for operating the unit directly without using the wireless remote controller.
Button to start cooling operation; Press again to stop.
Button to start heating operation. Press again to stop.
NOTE:
During emergency operation, the yellow indicating light on the IR Receiver Kit is flashing in the cycle of 0.5 second on/0.5 second off. -
The dip switch (DSW1 & DSW2) are optional for function setting and when needed, shall be set as per the following requirements.
DSW1 1st digit| Primary/Secondary setting
---|---
ON| When using 2 remote controllers, set as secondary remote controller.
OFF| When using 2 remote controllers, set as primary remote controller.
DSW1 2nd digit| DSW1 3rd digit| Adjacent unit setting mode
---|---|---
OFF| OFF| mode A
ON| OFF| mode B
OFF| ON| mode C
ON| ON| mode D
DSW1 4th digit| Elevator griller setting
ON| Elevator griller Up/Down is enabled.
OFF| Elevator griller Up/Down is disabled.
DSW2 1st digit| Emergency operation setting
ON| Emergency operation is enabled
OFF| Emergency operation is disabled.
DSW2 2nd digit| Reserved
ON| –
OFF| –
Adjacent Unit Setting Mode
When two indoor units are set adjacently, sometimes, both indoor units may receive signals from the wireless remote controller simultaneously. To ensure both indoor units operate properly, the IR Receiver Kit of one of them may be set at the mode [adjacent unit setting]. For example, for two indoor units A and B shown in the right figure, set B at the mode [adjacent unit setting].
a. Method to set the adjacent unit setting mode
- Set the IR Receiver Kit
Set 2nd digit and 3rd digit of the dip switch (DSW1) on the IR Receiver Kit of the indoor device B (object to be set) to another mode.
Set the wireless remote controller
For setting, please refer to wireless remote controller’s Operation Manual.
b. Method to cancel the adjacent unit setting mode
-
Set the IR Receiver Kit
The adjacent unit setting mode can be cancelled just by setting 2nd digit and 3rd digit of the dip switch (DSW1) on the IR Receiver Kit to OFF. -
Set the wireless remote controller
For canceling, please refer to wireless remote controller’s Operation Manual.
About Simultaneous Control of Multiple Units
One IR Receiver Kit can be used to control simultaneously a number of indoor units (up to 16 devices). When a number of indoor devices are installed in a large room, one single wireless remote controller can be used to run and stop all these devices.
NOTE:
When a number of units are under simultaneous control, all their indoor
devices shall be placed in the same room. If using one wireless remote
controller to control air conditioners in more than two rooms, it is possible
to forget to close one.
Set the IR Receiver Kit
In case of simultaneous operation of multiple (up to 16) indoor units by the
wireless remote controller, install the IR Receiver Kit only to the unit to be
operated. Other units should be the standard units without the IR Receiver
Kit. If multiple IR Receiver Kits are required to install, 2 IR Receiver Kits
are available at a maximum.
Methods for wire connection and setting for the purpose of simultaneous control of multiple units
-
Method to connect wires between indoor unit
Perform the connection work as following figure. -
The signal cable of all units shall not be in parallel with the power cable within the device and shall be fixed with wire buckle at key places. The distance between the signal cable and the power cable shall be at least 30 mm outside the devices. Or, put the signal cable through the protective sleeve, one end of which shall be grounded. When a shielded signal cable is used, one end of the shielding net shall be grounded.
-
Set addresses of all indoor devices.
Method for Test Running with the Wireless Remote Controller
Please test it in accordance with the wireless remote controller’s Operation Manual.
Alarm Code Indication
-
In case that some trouble occurs because of activation of safety device, etc., (red lamp) flashes (0.5 second ON / 0.5 second OFF).
-
Refer to the Technical Catalogue of airCore 700 unit about Alarm Code List.
-
Alarm Code indicates the flashing times of (green lamp) and (yellow lamp) as shown below.
- (green lamp): The flashing is shown at the 2 digit of Alarm Code
- (yellow lamp): The flashing is shown at the 1 digit of Alarm Code
(Alphabet Code: A=10 times, B=11 times, C=12 times, …..)
-
Example****
-
(red lamp) flashing (1 second ON / 1 second OFF) indicates abnormal transmitting between Indoor Units and Outdoor Unit.
Hitachi-Johnson Controls Air Conditioning, Inc.
Add.: 1-16-1, Kaigan Minato-ku, Tokyo, Japan
P02270Q 2023.09 V00 Printed in China