Aprilaire S84N 1H1C Programmable Single Stage Universal Thermostat Owner’s Manual
- June 13, 2024
- Aprilaire
Table of Contents
- Aprilaire S84N 1H1C Programmable Single Stage Universal Thermostat
- ABOUT YOUR NEW THERMOSTAT
- QUICK REFERENCE TO CONTROLS & DISPLAY
- POWER OPTIONS
- OPERATION
- INDOOR AIR QUALITY FUNCTIONS
- PROGRAM SCHEDULE AND HOLDS
- SETUP MENU
- LIMITED WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Aprilaire S84N 1H1C Programmable Single Stage Universal Thermostat
ABOUT YOUR NEW THERMOSTAT
THERMOSTAT FEATURES
- Heat Blast® raises the room temperature 3°F to 5°F.
- Easy to read, color display.
- 7 day programmability.
- Displays room temperature and temperature setting.
- Air filter and HVAC service reminders.
- Programmable fan control with fan circulation mode.
- Easy-to-use temperature control can override the program schedule at any time.
- Progressive recovery ensures proper temperature at the start of a program event.
QUICK REFERENCE TO CONTROLS & DISPLAY
HOME SCREEN
MAIN MENU
SCREEN SAVER
Starts 45 seconds after inactivity, press any button to wake the screen.
NOTE: Screen saver is not available on thermostat installations that are not connected to C wire and run on battery power only.
POWER OPTIONS
The thermostat is dual power. It can either use 24 VAC, 2 “AA” batteries or both (to provide backup power for the clock). Batteries are optional if the thermostat was connected to AC power when installed. For model S84N SU, 24 VAC must be connected in order for the system fault to operate. The thermostat has a memory backup that saves the thermostat’s settings in case of a power interruption.
OPERATION
SELECT SYSTEM MODE (EM HEAT / HEAT / COOL / AUTO / OFF)
- Press SELECT to enter the Main Menu.
- Use to select the Mode option.
- Press SELECT to enter the Mode menu:
- Use to select the desired mode.
- Heat: The thermostat controls only the heating system. Cool: The thermostat controls only the cooling system. Auto: (if enabled in installer setup) Thermostat automatically selects heating or cooling depending on the indoor temperature. Emergency Heat: (only for heat pumps with auxiliary heat) Thermostat controls auxiliary heat. Heat pump will not operate in Em Heat mode. Off: Heating and cooling systems are off.
- Press SELECT to save the mode and return to the home screen, or BACK to exit without saving.
CHANGE TEMPERATURE SETTING
- From the Home screen press or to adjust the current temperature setting.
- The temperature setting will enlarge during adjustment.
- The temperature setting will take effect 3 seconds after the last adjustment or press SELECT to save and return to the home screen.
See HOW TO MODIFY PROGRAM SCHEDULES on pages 16-17 for more information.
SELECT FAN SETTING (AUTO / ON / CIRCULATE)
When the fan mode is changed during a program event, it remains in that mode until the next event starts. The fan must be programmed to Fan On in the schedule to run continuously through all events.
- Press SELECT to enter the Main Menu.
- Use or to select the Fan option.
- Press SELECT to enter the Fan menu:
- Use or to select the desired fan mode. On: Fan runs continuously. Use this mode for maximum air circulation/filtering. Auto: Fan runs only when the heating or cooling system is on. Circulate: Same as Auto, but ensures the fan is on for at least 30 minutes per hour. Use this mode for a balance of energy savings and air circulation/cleaning.
- Press SELECT to save the fan mode and return to the home screen, or BACK to exit without saving.
MAINTENANCE REMINDERS
Maintenance reminders are set up by the installer to indicate when the
equipment is due for service. If a maintenance reminder is displayed, call
your HVAC dealer for service. They can be reset by selecting the Reset option
on the reminder message or in the Reset Service Reminders option found in the
Settings menu.
INDOOR AIR QUALITY FUNCTIONS
EVENT-BASED™ AIR CLEANING (IF INSTALLED)
-
Select Air Cleaning from the Main Menu. Air Cleaning has two temporary events and three persistent modes that can be set. Air cleaning will activate the fan for the purpose of air cleaning.
-
Events (temporary) 3 Hrs: When selected, the air cleaner will run for 3 hours continuously and then return to the most recent mode of Auto, Continuous, or Off. This option only cleans the air when needed; an example would be after vacuuming. 24 Hrs: When seasonal allergies spike and outside air quality is at its worst, choose this option. Your air cleaner will run continuously for 24 hours, then return to the most recent mode of Auto, Continuous, or Off.
NOTE: The thermostat will manage fan and air cleaning selections when the selections overlap. -
Modes (persistent)
- Auto: The air cleaner will run a minimum of 30 minutes every hour. The air cleaner will monitor the amount of time your heating and cooling system runs; if 30 minutes is not reached the air cleaner will automatically turn on. This will maximize the amount of air cleaning while minimizing energy consumption.
- Continuous: This option will provide the maximum amount of air cleaning available. The air cleaner will be active for 24 hours a day, seven days a week.
- Off: The air cleaner will not run the fan for the sole purpose of air cleaning.
- NOTE: If air cleaning is installed, air cleaning will still occur during normal fan operation during heating, cooling or other indoor air quality events.
PROGRAM SCHEDULE AND HOLDS
SET TIME AND DATE
- Select Settings from the Main Menu.
- From the Settings menu, select Clock the to set the time, or Date to set the date.
UNDERSTANDING PROGRAM SCHEDULES
The daily schedule is split into four sections:
- Wake: Temperature you would prefer to wake up to.
- Leave Temperature when you are away from the house.
- Return: Temperature you would prefer to return home to.
- Sleep: Temperature you would prefer while sleeping.
The times and temperatures shown in TABLE 1 are the defaults. The start time and temperature of each section can be changed to fit your schedule. We recommend these settings, since they can reduce your heating/cooling expenses. The fan program is pre-set to Auto for all events.
TABLE 1 – DEFAULT SCHEDULE
Event Designator
|
Start Time
| Set Temperature|
Fan
Heat| Cool
Wake| 6:00 AM| 70°F (21°C)| 78°F (25 5°C)| Auto
Leave| 8:00 AM| 62°F (16 5°C)| 85°F (29 5°C)| Auto
Return| 5:00 PM| 70°F (21°C)| 78°F (25 5°C)| Auto
Sleep| 10:00 PM| 62°F (16 5°C)| 82°F (27 5°C)| Auto
PROGRESSIVE RECOVERY
The Progressive Recovery feature allows Pre-Heating or Pre-Cooling PRIOR to
a scheduled event in order to reach the desired temperature at the start of
that scheduled event. Example: According to TABLE 1, the Wake time is 6:00 am,
the Wake heat set point is 70°F and the Sleep set point is 62°F. The heat will
turn on prior to 6:00 am so that the temperature reaches 70°F by the time the
Wake event begins.
HOW TO MODIFY PROGRAM SCHEDULES
-
From the Schedule option in the Main Menu, you can turn the schedule On or Off, and make changes to the schedule. Modify: The event start time, temperature, and fan mode can be adjusted for each event of each day. On/Off: When the Schedule is turned Off the thermostat will continue to control at the current temperature setting until adjusted with .
-
Select Modify to change the default schedule settings.
-
Select the group of days or days you would like to modify.
-
Adjust Wake details (Start, Heat, Cool, Fan, and/or select Next to proceed.
-
Adjust Leave details and/or select Next to proceed.
-
Adjust Return details and/or select Next to proceed.
-
Adjust Sleep details and/or select Next to proceed.
- If you modified a group of days you can Save & Exit back to the Home screen.
- Or if you modified a single day you can copy the settings to another day or group of days.
-
If you choose to copy, you will see this confirmation message, then you can return to the Modify menu to make changes to another day by selecting Edit More Days or return to the Home screen by selecting Save and Exit.
HEAT BLAST® (IF INSTALLED)
Heat Blast® will raise the current room temperature 3°F to 5°F based on the installer set-up, and then resume normal operation. To activate Heat Blast, select Heat Blast from the Menu, and use the Select button to set the toggle to ON.
NOTE: Heat Blast button is only available if it is enabled in the Installer Setup and the thermostat is in Heat or Emergency Heat mode. To cancel Heat Blast, select Heat Blast from the Menu, and use the Select button to set the toggle to OFF.
PROGRAM SCHEDULE HOLDS
TEMPORARY HOLD
Press to immediately adjust the temperature when the schedule is running. This will temporarily hold the temperature setting until the next scheduled event. A temporary hold can also be set from the Hold option in the Menu. The end time of the hold can also be adjusted from here. The temporary hold can be canceled from the Hold option in the Menu, or by adjusting the temperature back to the scheduled temperature.
SETUP MENU
TABLE 2 – USER SYSTEM SETTINGS TABLE
Clock| Set time
Date| Set date
Display| Display can be disabled during sleep for light-sensitive
locations (Not available when battery-only powered )
Scale| Change the temperature scale from Fahrenheit to Celsius
About| Contains thermostat model number and software/hardware version
Reset Reminder| Reset expired service reminders
LIMITED WARRANTY
Your Research Products Corporation AprilAire® Thermostat is expressly warranted for five (5) years from the date of installation to be free from defects in materials or workmanship. Research Products Corporation’s exclusive obligation under this warranty shall be to supply, without charge, a replacement for any thermostat which is found to be defective within such five-year period and which is returned, together with the date of installation, no later than thirty (30) days after said five (5) year period by you to either your original supplier or to Research Products Corporation, Madison, Wisconsin 53701. THIS WARRANTY SHALL NOT OBLIGATE RESEARCH PRODUCTS CORPORATION FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE THERMOSTAT ITSELF. IMPLIED WARRANTIES OF MERCHANTABILITY OF FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID FIVE-YEAR PERIOD. RESEARCH PRODUCTS CORPORATION’S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE-LIMITED WARRANTY IS EXPRESSLY EXCLUDED. THIS LIMITED WARRANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS THERMOSTAT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR. IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES WILL BE EFFECTIVE UPON INSTALLATION . Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above exclusions or limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
WARRANTY REGISTRATION
Visit us online at www.aprilaire.com to register your Aprilaire product. If
you do not have online access, please mail a postcard with your name, address,
phone number, email address, product purchased, model number, date of
purchase, and dealer name and address to: Research Products Corporation, P.O.
Box 1467, Madison, WI 53701.
Your warranty registration information will not be sold or shared outside of
this company. B2208794B • 61001858 • 1.22 © 2022 AprilAire |
aprilaire.com | 800.334.6011 U.S. Patent Numbers
8,146,376, 8,596,078, 9,874,366, and other patents pending. Aprilia reserves
the right to change specifications without notice.