INSTRUCTION MANUAL
RFLS-53N High Frequency Level Switch
High frequency level switch
RFLS-53N
**** Read carefully the instructions published in this manual before the first use of the sensor. Keep the manual at a safe place. The manufacturer reserves the right to implement changes without prior notice.
Used symbols
To ensure maximum safety of control processes, we have defined the following safety instructions and information. Each instruction is labelled with the appropriate pictogram.
Alert, warning, danger
This symbol informs you about particularly important instructions for
installation and operation of equipment or dangerous situations that may occur
during the installation and operation. Not observing these instructions may
cause disturbance, damage or destruction of equipment or may cause injury.
Information
This symbol indicates particularly important characteristics of the device.
Note
This symbol indicates helpful additional information.
safety
All operations described in this instruction manual have to be carried out by
trained personnel or by an accredited person only. Warranty and post warranty
service must be exclusively carried out by the manufacturer.
Improper use, installation or set-up of the sensor can lead to crashes in the
application.
The manufacturer is not responsible for improper use, loss of work caused by
either direct or indirect damage, and for expenses incurred at the time of
installation or during the period of use of the level sensors.
basic description
The RFLS-53 sensor uses the principle of the capacity measurement on high
frequency.
This means that the sensor reacts to the mass of material and ignores the
deposits and remnants of material that remain on the measuring part – the
active surface of the sensor.
Thus, the sensor can be used in demanding applications to indicate powder,
dust and hygroscopic materials and can replace mechanical rotary level
switches or standard capacitive level switches.
The sensor is manufactured in several versions with extra low (24 V DC) or low
supply voltage (230 V DC). With different types of outputs (PNP, relay, SSR)
and electrical connection (M 12, valve connectors, cable).
RFLS-53 fully replaces the older CLS-53, but its electrical connection of the
230 VAC version is different (3 wires).
range of application
Detection of various kinds of bulk-solid materials (pellets, wood chips,
sawdust, granulates, cereals, sand, gravel, …) and other powder materials
(flour, cement, fine mineral powders, metallic powders, …) in hoppers,
containers, silos, etc.
The sensor is not intended to be used for liquids or pasty media.
The sensor cannot be used in explosive atmospheres.
dimensional drawing
installation and pUtting into operation
This procedure has the following three steps:
- installation – chapter 5
- electrical connection – chapter 6
- settings – chapter 7
installation instrUctions
- The sensor should be mounted to a slant or vertical wall of the hopper using a weldon fitting with G1 ½” thread or appropriate fixing nut (PUM-G1,5). The front (active surface) of the sensor should remain 2-5 mm in front of the inner wall (inwards) or in front of the fixing nut – Fig. 1a, 1b.
- Although the influence of the build-ups is strongly eliminated, thick sediments might cause false activation (blocking) of the sensor (see Fig. 2). The function of the sensor is safe with a maximum sediment thickness of ca. 5 – 10 mm depending on the dielectric properties of the material.
- The sensor must not be installed in places with direct solar radiation and must be protected against weather conditions. In case the installation at places with direct solar radiation is inevitable, it is necessary to mount a shielding cover above the sensor (Fig. 3).
- If possible, mount the cable from the sensor down and let there a draining loop to avoid intrusion of humidity (Fig. 4). The cable gland as well as the connector’s safety screw have to be tightened sufficiently.
- The placement of the sensor must be carried out in such a way that the material flow from the filling point does not interfere with the sensor’s scanning field.
Othrewise false activation (blocking) of the sensor could occur (Fig. 5).
electrical connection
Electrical connection can only be made in a voltage – free state!
In the event that the level meter (sensor) is installed in an outdoor
environment at a distance greater than 20 m from the outdoor switchboard, or
from an enclosed building, it is necessary to supplement the electrical cable
leading to the level meater (sensor) with suitable overvoltage protection.
In the event of strong ambient electromagnetic interference, paralleling of
conductors with power distribution, or for distribution to distances over 30
m, we recommend using a shielded cable.
RFLS-53N--P-
The source of the power voltage must comprise of a stabilised safe low
power source with galvanic separation. In the event that a switch-mode power
supply is used, it is essential that its construction effectively suppresses
common mode interference on the secondary side. In the event that the switch-
mode power supply is equipped with a PE safety terminal, it must be
unconditionally grounded!
RFLS-53N--RE(SSR)- The device may only be connected to the power supply via
an easy to reach switch with marked turned off / on positions and must be
protected by a fuse or circuit breaker with a value of max. 6 A! The switch or
circuit breaker used as the disconnect device must be in accordance with the
IEC60947-1 and IEC60947-3, must be marked and must not be in the network
inlet.
RFLS-53N--RE(SSR)-
The output wire of the device is not separated from hazardous circuits. It
must not be connected to secondary accessible safety circuits.
6.1. Connection through valve connector
6.2. Connection through connector M12
6.3. Connection via standard cable gland or gland for protective hoses
setting
Setting-up can be performed with a “MP–8” magnetic pen that is a part of of the delivery. Settings are performed by touching a magnetic pen on sensitive spot indicated as or located beside the connector or cable gland.
-
Setting the Normally Open or Normally Closed switching mode:
Factory default mode is Normally Open. If the setting mode satisfies, you can skip next steps.
Setting the sensor to Normally Closed mode:
1. Disconnect the sensor from the power source (e.g. by disconnecting the connector).
2. Place the magnetic pen on spot in the voltage-free state and hold it.
3. Connect the power supply. Green and Orange LED lights up.
4. Take the magnetic pen away.
• Other settings of the sensor remain unchanged.
• Repeating this procedure will set the switching mode Normally Open again. -
Adjusting sensitivity by short touch of magnetic pen (approx. 0,5 sec) to:
1. spot: increase sensitivity (every step is confirmed by 3-times flashing green LED)
2. spot: decrease sensitivity (every step is confirmed by 3-times flashing green LED)
• When the end of sensitivity range is reached (min or max sensitivity), the frequency of green LED flashing slows down.
• Verify the function by activation of the sensor and watch the sensor behavior.
• The sensor is factory default set to basic sensitivity. -
Factory default mode:
factory mode is Normally Open, setting of sensitivity is for materials about εr = 2.
1. Disconnect the sensor from the power source (e.g. by disconnecting the connector).
2. Place the magnetic pen on spot in the voltage-free state and hold it.
3. Connect the power supply. Green and Orange LED lights up.
4. Take the magnetic pen away.
5. Now is Factory default mode set. spot marked LED indicators Valve connector Safety screw spot marked Cable gland
Setting modes
he sensor can be set to normally closed “O-mode” or to normally open “C-mode” switch types
For safety reasons, for scanning min. level, we recommend you to use the “O” mode setting (sensor closes when submerged). A faulty sensor or wiring will take effect here in the same way as level emergency conditions by opening the sensor. Analogously for the max. level, we recommend you to set the “C” mode (sensor opens when submerged).
order cod
accessories
standard – included in the price of the sensor
- 1 pcs. MP–8 magnetic pen
- 1 pcs. Seal
- 1 pcs. Connector with IP67 coverage (for version with valve connector)
safety, protection and compatibility
RFLS-53N-_-P-
Protection against dangerous contact is provided by low safety voltage
according to ČSN 33 2000–4–41 and degree of coverage IP 65.
**RFLS-53N--RE(SSR)-
** Equipment of protection class II. Protection against dangerous contact
with live parts is ensured by the degree of protection IP 65. Electrical
safety is ensured in accordance with the requirements of the standard EN
61010-1.
The operator of the equipment must be demonstrably acquainted with the
operation and maintenance of the equipment.
Electromagnetic compatibility is provided by conformity with standards:
EN 55 011 (A), EN 61326-1, EN 61000-4-2 (A, 8 kV),
EN 61000-4-3 (A, 10 V), EN 61000-4-4 (A, 2 kV),
EN 61000-4-5 (A, 1 kV), EN 61000-4-6 (A, 10 V),
EN 61000-4-8 (A, 30 A), EN 61000-4-11 (A, B)
The sensor is equipped with protection against polarity reversal of the supply
voltage and voltage peaks. RFLS-53N -- RE (SSR) - sensors are not equipped
with current overload protection! RFLS-53N -- P-_ sensors are equipped with
overload and short circuit protection at the output.
Use, manipUlation and maintenance
The sensor does not require any personnel for its operation.
Maintenance of this equipment consists in verification of sensor’s and supply
cable’s integrity.
In case any visible defects are discovered, the manufacturer or reseller of
this equipment must be contacted immediately.
Any changes or interventions without the permission of the manufacturer are forbidden to be performed on the RFLS-53 level sensor. Any repairs must be carried out only at the manufacturer site or by a service organization authorizedby the manufacturer. The assembly, installation, commissioning, operation, and maintenance of the RFLS-53 level sensor must be performed following this manual and must comply with the provisions of the applicable standards for the installation of electrical equipment.
Technical specifications
Supply voltage| RFLS-53N- -P-
RFLS-53N- -RE-
RFLS-53N- -SSR-| 7 … 34 V DC
95 … 230 V AC (± 10 %) / 50 … 60 Hz
95 … 230 VAC (± 10 %) / 50 … 60 Hz
---|---|---
Supply current| RFLS-53N- -P-
RFLS-53N- -RE-
RFLS-53N- -SSR-| 10 mA DC
60 mA AC
60 mA AC
Output| RFLS-53N- -P-
RFLS-53N- -RE-
RFLS-53N- -SSR-| open collector PNP output, max. 300 mA
relay contact 1 A / 250 V / 250 VA AC
solid state relay, max. 130 mA / 250 V AC
Tightening torque of cable gland| RFLS-53N-1- -G| 1 … 2 Nm
Recommended cable| RFLS-53N-1--G external dimension
RFLS-53N-1--G wire size| ø 4 … 9 mm
3x 1,5 mm2 max.
Cable| RFLS-53N- -P-B (H)
RFLS-53N- -RE-B (H)
RFLS-53N- -SSR-B (H)| 3x 0,5 mm2, PVC
4x 0,75 mm2, PVC
4x 0,75 mm2, PVC
Max. remanent voltage (ON state)| RFLS-53N- -P-| max. 1,5 V
Max. switching frequency| 0.5 Hz
Ambient temperature range| -20 … +60° C
Protection class| IP65
Housing material| PP and PVC-U
Weight approx.| 0,13 kg
Marking of labels
Label for device of the type RFLS–53N
Symbol of producer: logo Dinel®
Internet address: www.dinel.cz, Country of origin: Made
in Czech Republic
Connection scheme and labelling of wires:
Cable length: Cable: = m
Serial number: Ser. No.: — (from the left: production year, serial production
number)
Supply voltage: U=… V
Supply current: l=… mA
Maximum switching current: |out=… mA (A)
Ambient temperature range: ta= … °C
Impact rating: IKO6
Protection class: |P6
The character of double insulation (device of protection class II):
Compliance mark:
Electro-waste take-back system mark:
industrial electronics
Dinel, s. r. o.
U Tescomy 249
760 01 Zlín
Czech Republic
phone: +420 577 002 002
e-mail: sale@dinel.cz
www.dinel.cz
06/2021
Find the updated version at www.dinel.cz
version: 08/2017