POWEREX SES0508 2 HP or 5 HP Scroll Enclosure Air Compressors Instruction Manual
- June 4, 2024
- POWEREX
Table of Contents
2 HP or 5 HP Scroll Enclosure Air Compressors
Instruction Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Description
GENERAL
The Powerex Oilless Rotary Scroll Air Compressor has advanced scroll
compressor technology through the development of a completely oilless
compressor. The Powerex Scroll Compressor offers a dynamically balanced air
end which ensures vibration-free operation. The rotary design permits a
continuous 100% duty cycle. Other standard features on the Powerex Scroll
Compressor include a Magnetic Starter, Motor Overload Protection, a High-
Temperature Shutdown Switch, an Air Cooled Aftercooler, and a Single Phase or
Three Phase 4 Pole ODP motor.
Safety Guidelines
A SEPARATE SAFETY BOOKLET IS PROVIDED ALONG WITH THIS MANUAL. READ AND
UNDERSTAND The SAFETY BOOKLET.
This manual contains information that is very important to know and
understand. This information is provided for SAFETY and to PREVENT EQUIPMENT
PROBLEMS. To help recognize this information, observe the following symbols.
MAKE SURE EVERYONE OPERATING OR SERVICING THE COMPRESSOR READS AND UNDERSTANDS
ALL The INFORMATION PROVIDED.
DANGER
Danger Indicates an Imminently hazardous situation that, if not avoided, WILL
result In death or serious Injury.
WARNING
Warning indicates a potentially hazardous situation that, if not avoided,
COULD result in death or serious injury. Caution indicates a potentially minor
or moderate injury.
CAUTION
Installation
INSTALLATION SITE
- The scroll compressor must be located in a clean, well-lit, and well-ventilated area.
- The area should be free of excessive dust, toxic or flammable gases, moisture, water, and direct sunlight.
- Never install the compressor where the ambient temperature is higher than 104° F or where humidity is high.
- Clearance must allow for safe, effective inspection and maintenance. 20 inches of clearance for sides is recommended.
- If necessary, use metal shims or leveling pads to level the compressor. Never use wood to shim the compressor.
Specifications
Product | SES Series Powerex Simplex Air Compressors |
---|---|
Performance Specifications | See Page 2 |
Lubrication | Grease-filled Bearing |
Operating Voltages | 10 230 Volts, 60 Hz; 230 Volts, 50 Hz |
30 208-230/460/575 Volts, 60 Hz
Compression Cycle| Scroll
Motor Overload Protection| IEC Motor Overload Relay
Pressure Settings| Cut-In: 95 psig / Cut-Out: 115 psig
Cut-In: 115 PSIG / Cut-Out: 145 PSIG (High-Pressure Unit)
Overpressure Protection| ASME Safety Valve Factory Set and Sealed
Outlet Air Connections| 3/8 inch NPT
Tank Size| 13 Gallon ASME Rated 175 PSIG
California Ordinance 462 (L) (2)| Meets Requirements of this Ordinance
Tank Isolation| Standard All Units
Drive| 3V Belt
Control Panel| UL508A Listed
Compressor Specifications
Model| SES02| SES12| SES03| SES13| SES05|
SES15
---|---|---|---|---|---|---
HP| 2| 3| 5
Phase| 30| 10| 30| 10| 30| 10
Voltage| 208-230/460/575| 230| 208-230/460/575| 230| 208-230/460/575| 230
Amps| See wiring diagram for amp rating
Air End| SLAEO3EB| SLAEO3EB| SLAEO5E (SLAEO5EHP)
Control System| Pressure Switch| Pressure Switch| Pressure Switch
Discharge Pressure(PSIG)| 95 – 115 (115 – 145 optional)| 95 – 115 (115 – 145
optional)| 95 – 115 (115 – 145 optional)
Air Delivery| 6.0 @ 100 PSIG and (4.6 @ 145 PSIG)| 8.8 @ 100 PSIG and (7.1 @
145 PSIG)| 15.2 @ 100 PSIG and (12.5 @ 145 PSIG)
Compress Speed(RPM)| 2200 (1850)| 3140 (2770)| 3250 (3250)
Discharge Temp.| Ambient temp. + 30 °F| Ambient temp. + 30 °F| Ambient temp. +
30 °F
Noise level dB(A)
[1.5m from the front]| 49| 49| 51
Dimensions In Inches(L x W x H)| 34 x 21 x32.5| 34 x 21 x32.5| 34x 21x 32.5
(Items in parenthesis are high-pressure information)
6. Never install the compressor outside.
7. For 3 and 5 HP single phase models it is recommended that additional tank
volume be added. 3 HP single-phase models need a minimum of 30 gallons of air
capacity to limit the number of starts-per-hour to 14 maximum. 5 HP single-
phase models need a minimum of 60 gallons of air capacity to limit the number
of starts-per-hour to 10 maximum.
VENTILATION
- If the scroll compressor is located in a totally enclosed room, an exhaust fan with access to outside air must be installed.
- Never restrict the cooling fan exhaust air.
- Vent the exhaust air outside to prevent the compressor from operating at high temperatures and shutting down.
- Never locate the compressor where hot exhaust air from other heat-generating units may be pulled into the unit.
WIRING
All electrical connections must be performed by a qualified electrician.
Installations must be in accordance with local and national electrical codes.
- Make sure the power source is the same voltage as the unit’s required voltage
- Use solderless terminals to connect the electric power source.
- Remove the two left panels.
- Pull the electric cable through the electric source inlet and connect to the primary side of the contact blocks.
- Since the loosening of wires is possible in shipment, tighten all wire terminals prior to starting the unit.
PIPING
General Guidelines
- Make sure the piping is lined up without being strained or twisted when assembling the piping for the scroll compressor.
- Appropriate expansion loops or bends should be installed at the compressor to avoid stresses caused by changes in hot and cold conditions.
- Piping supports should be anchored separately from the compressor to reduce noise and vibration.
- Never use any piping smaller than the compressor connection.
- Use a flexible hose to connect the outlet of the compressor to the piping so that the vibration of the compressor does not transfer to the piping.
Remote Intake Piping
Powerex Compressor Systems with pipe thread connectors on the intake filters
are intended for installation with remote air intake. Piping for the remote
intake system must be installed at the final operating site.
Under some conditions, the intake piping may facilitate the condensation of
humidity in the intake air stream into liquid water.
NOTICE
The intake filters supplied by Powerex will not stop the ingestion of liquid
water by the pumps. Liquid water going into the pumps will damage the pumps
and void the warranty. Always install drip legs with sufficient capacity to
capture liquid water in the intake piping before the air filters. Drip legs
must be sized with low enough air velocity to make sure they are effective at
capturing liquid water in the intake air and must be maintained (drained) at
frequent intervals to make sure they remain effective.
SAFETY VALVES
Tank-mounted compressors are shipped from the factory with safety valves
installed in the air receiver manifold. The flow capacity of the safety valve
is equal to or greater than the capacity of the compressor.
- The pressure setting of the safety valve must be equal to or less than the maximum working pressure of the air receiver.
- Safety valves should be placed ahead of any possible blockage point in the system, i.e. shutoff valve.
- Avoid connecting the safety valve with any tubing or piping. 4. Manually operate the safety valve every six months to avoid sticking or freezing.
Operation
BEFORE START-UP
- Make sure all safety warnings, labels, and instructions have been read and understood before continuing.
- Remove any shipping materials, brackets, etc.
- Confirm that the electric power source and ground have been firmly connected.
- Check the belts for tightness.
- Be sure all pressure connections are tight.
- Check to be certain all safety relief valves, etc., are correctly installed.
- Securely mount all panels and guards.
- Check that all fuses, circuit breakers, etc., are the proper size.
- Make sure the inlet filter is properly installed.
- Confirm that the drain valve is closed.
START-UP AND OPERATION
- Visually check the rotation of the compressor pump. The rotation should be counterclockwise if viewing the compressor from the belt side. If the rotation is incorrect, have a qualified electrician correct the supply wiring.
- Follow all the procedures under”Before start-up” before attempting the operation of the compressor.
- Make sure the compressor switch is in the OFF position.
- Switch the electric source breaker on.
- Open the 3/8 inch discharge valve completely.
- Turn the compressor switch to the ON position and check that the compressor operates without excessive vibration, unusual noises, or leaks.
- Close the discharge valve completely.
- If the pressure does not rise on a three-phase unit, turn the unit off. Have a qualified electrician switch the breaker OFF and exchange the L1 and L2 connections (two out of three phases of electric source) on the control panel
- Check the discharge pressure. Also, make sure the air pressure rises to the designated pressure setting by checking the discharge pressure gauge.
- Check the operation of the pressure switch by opening the outlet valve and confirming the compressor starts at approximately 95 psi for low-pressure units and 115 PSIG or high-pressure units.
DAILY OPERATION
-
Stop the compressor by turning the switch to the OFF position.
NOTE: If the compressor rotates in reverse for more than five seconds, the check valve needs to be cleaned or replaced. -
Switch the breaker OFF if the compressor is not to be used for a long period of time.
STOPPING THE COMPRESSOR DURING NORMAL OPERATION
- Close the discharge valve.
- Allow the air pressure to build and the compressor to stop.
- Turn the compressor off by turning the switch to the OFF position.
BELT ADJUSTMENT PROCEDURE
- Remove the top panel by removing the two slotted 1/4-20 screws on the rear of the enclosure.
- Loosen the four (4) motor slide bolts.
- Tighten the belt by adjusting the belt adjustment bolt. Belt tension for new belts should be 57 to 65 lbs for the loosest belt in the set, then 45-50 lbs after run-in. If the belt tension falls below 25 lbs or chirping is heard as a start-up, re-tension belts. (If using the deflection method for belt tension, 3.8-4.3 lbs force at mid-span should give 7/32 inch belt deflection for a new belt 3.0-3.38 for a used belt for 7/32 inch belt deflection.
- Tighten the four (4) motor slide bolts. Tighten the two electrical panel side slide bolts first then tighten the two pulley side slide bolts.
Figure 1
Scroll Unit Parts Breakdown –
Models SES02, SES12, 5E503, SES13, 5E505, SES15, SF120_PHA, and SF130_PHA
Figure2
Ref.No.
| Description| SES02/SES12| SES03/SES13| SESOS /SES15|
Qty.
---|---|---|---|---|---
1
| Air end
(low pressure)
(high pressure)| –
SL014003AJ
SL014003AJ| –
SL014003AJ
SL014003AJ| –
SL016502AJ
SL016511AJ| –
1
1
2| 13-gallon tank| AR234800WH| AR234800WH| AR234800WH|
1
3
| Unit base| SL303600AV| SL303600AV| SL303600AV| 1
4| Front panel| SL304500AV| SL304500AV| SL304500AV|
1
5
| Right panel| SL304400AV| SL304400AV| SL304400AV| 1
6| Back panel| SL304600AV| SL304600AV| SL304600AV|
1
7
| Top panel| SL304800AV| SL304800AV| SL304800AV| 1
8| Utility panel| SL305200AV| SL305200AV| SL305200AV|
3
9
| Internal duct| SL304901AV| SL304901AV| SL304901AV| 1
10| Left panel| SL304300AV| SL304300AV| SL304300AV|
1
11
| Maintenance panel 1| SL305000AV| SL305000AV| SL305000AV| 1
12| Inside panel| SL304700AV| SL304700AV| SL304700AV|
1
13
| Pump base| SL304101AV| SL304101AV| SL304101AV| 1
14| Mounting foot| IP630300AV| IP630300AV| IP630300AV|
4
15| Support| SL305100AV| SL305100AV| SL305100AV|
2
16
| Inlet filter assembly| ST073925AV| ST073925AV| ST073925AV| 1
17| Filter element| ST073921AV| ST073921AV| ST073921AV|
1
18
| Motor pulley
2HP (low pressure, 2-3V4.45)
–
2HP (high pressure, 2-3V3.65)
–
3HP (low pressure, 2-3V6.0)
3HP (high pressure, 2-3V5.3)
5HP (low pressure, 2-3V6.9)
5HP (high pressure, 2-3V6.9)| –
3Ø PU202633AV
1Ø PU202623AV
3Ø PU202632AV
1Ø PU202622AV
–
–
–
–| –
–
–
–
–
PU202625AV
PU202624AV
–
–| –
–
–
–
–
–
–
PU009754AV
PU009754AV|
–
1
–
1
–
1
1
1
1
20
| 1 /4 T x 1 /4 P x90 push connect| ST119702AV| ST119702AV| ST119702AV| 1
21| 1/4 inch drain tube| PS010300AV| PS010300AV| PS010300AV|
2.0 ft.
22
| Corner angle| ST185500AV| ST185500AV| ST185500AV| 4
23| Temperature switch @ 115 psi
Temperature switch @ 145 psi| AM003033AV
AM003034AV| AM003033AV
AM003034AV| AM003033AV
AM003034AV|
1
1
24
| Sub panel| SL305300AV| SL305300AV| SL305300AV| 1
25| 1/4 inch bulk head fitting| PS006701AV| PS006701AV| PS006701AV|
1
26
| 3/8 inch bulk head fitting| PS006702AV| PS006702AV| PS006702AV| 1
27| Safety valve
(Low-pressure unit)
(High-pressure unit)| –
V-215100AV
V-215401AV| –
V-215100AV
V-215401AV| –
V-215100AV
V-215401AV|
–
1
1
28
| Maintenance panel 2| SL306500AV| SL306500AV| SL306500AV| 1
29| Motor slide base| SL306701AV| SL306701AV| SL306701AV|
1
30
| Pressure switch
(Low-pressure unit)
(High-pressure unit)| –
CW207573AV
CW207595AV| –
CW207573AV
CW207595AV| –
CW207573AV
CW207595AV|
–
1
1
31
| Lighted off/on the switch| PE000560AV| PE000560AV| PE000560AV| 1
32| 3/8 inch ball valve| ST079802AV| ST079802AV| ST079802AV|
1
33
| 1 /4-inch ball valve| ST079806AV| ST079806AV| ST079806AV| 1
34| Electrical strain relief| ST188106AV| ST188106AV| ST188106AV|
1
35
| Motor
2hp 1 phase
2hp 3 phase
3hp 1 phase
3hp 3 phase (208- 230 / 460V)
3hp 3 phase (575V)
5hp 1 phase
5hp 3 phase (208- 230 / 460V)
5hp 3 phase (575V)| –
MC301594AV
MC3034501 AV
–
–
–
–
–
–| –
–
–
MC301594AV
MC304201AV
MC304202AV
–
–
–| –
–
–
–
–
–
MC022393AV
MC304203AV
MC304204AV|
–
1
1
1
1
1
1
1
1
36
| Check valve| IP087700AV| IP087700AV| IP087700AV| 1
37| Fan| IP632400AV| IP632400AV| IP632400AV|
1
Scroll Unit Parts Breakdown –
Models SES02, SES12, SES03,0 SES13, SES0S, SES15, SF120_PHA, and SF130_PHA
Figure 2 (Continued)
Ref.No.| Description| SES02/SES12| SES03/SES13| SESOS
/SES15| Qty.
---|---|---|---|---|---
38| Fan guard| IP632401AV| IP632401AV| IP632401AV| 1
39| 3/8 inch PTFE tube| PS001800AV| PS001800AV| PS001800AV| 2.5 ft.
40| Belt
2hp low pressure
2hp high pressure
3hp low pressure
3hp high pressure
5hp low/high pressure| –
BT009001AV
BT009001AV
–
–
–| –
–
–
BT012001AV
BT012001AV
–| –
–
–
–
–
BT010701AV| –
2
2
2
2
2
41| High temp light| PE000538AV| PE000538AV| PE000538AV| 1
42| Unit pressure gauge| IP632603AV| IP632603AV| IP632603AV| 1
43| Hourmeter| PE001004AV| PE001004AV| PE001004AV| 1
44| JIC fitting| ST186422AV| ST186422AV| ST186422AV| 1
45| Braided hose| SM001502AV| SM001502AV| SM001502AV| 1
46| Rubber mounting block| AG007501AV| AG007501AV| AG007501AV| 3
47| Aftercooler| SL300101AV| SL300101AV| SL300101AV| 1
48| ♦ Cabinet screw| ST129304AV| ST129304AV| ST129304AV| 32
49| Fan cord| IP632800AV| IP632800AV| IP632800AV| 1
50| Intake adaptor plate| IP088400AV| IP088400AV| IP088400AV| 1
51| Adaptor plate gasket| IP088200AV| IP088200AV| IP088200AV| 1
52| 1/4-20 screw| ST074003AV| ST074003AV| ST074003AV| 8
53| 3/8 inch PTFE tube| PS001800AV| PS001800AV| PS001800AV| 1ft.
54| 3/8 x 3/8 x 90 push connect| ST119705AV| ST119705AV| ST119705AV| 2
Parts unique to:| SF120 PHA| SF130 PHA| |
2| 13-gallon tank| AR234800LN| AR234800LN| –| 1
3| Deep base| SL305401AV| SL305401AV| –| 1
18| Motor pulley (SO Hz)| PU202623AV| PU202626AV| –| 1
35| Motor (60 Hz)
Motor (SO Hz)| MC301594AV
MC301578AV| MC301594AV
BT012001AV| –
–| 1
1
40| Belt (SO Hz)| BT012001AV| BT010701AV| –| 2
42| Unit Pressure Gauge
♦ Swivel caster| GA032201AV
ST187901AV| GA032201AV
ST187901AV| –
–| 1
4
Parts unique to:| | SF1309| –| 1
16| Inlet filter assembly| –| VP000541AV| –| 1
17| Filter element| –| VP000540AV| –| 2
23| Temperature switch| –| AM003017AV| –| 1
30| Pressure switch (low-pressure unit)| –| CW207560AV| –| 1
35| Motor (60 Hz)| –| MC022309AV| –| 1
44| JIC fitting (aftercooler side)
JIC fitting (pump side)| –
–| ST186402AV
ST186419AV| –
–| 1
1
45| Braided hose| –| SM001504AV| –| 1
♦ = Not shown|
Maintenance Schedule {see Pump Manual for “How To” Instructions)
Operating Hours
Item| Action needed| 500| 2500| 5000| 10,000|
20,000| Remarks
---|---|---|---|---|---|---|---
Receiver| Drain moisture| Daily| | | | | If equipped with an Electric Drain,
test daily
Cartridge Filter| Clean, Replace| •| | | | | Part# ST073921 AV
Ventilation Screen| Clean| •| | | | |
Blower Fan| Clean| | | •| | |
Fan Duct| Clean| | | •| | |
Compressor Fins| Clean| | | •| | |
Compressor| Regrease| | | (Every 5000
hours for 145
psig units)| | | Use genuine Powerex grease
Tip Seal Set| Replace| | | (Every 5000
hours for 145
psig units)| | |
Heat Insulation Pipe| Replace| | | (Every 5000
hours for 145
psig units)| | |
Check Valve| Inspect, Replace| •| | | | |
V-belt| Inspect, Replace| | Readjust •| | | |
Temperature Sensor| Confirm operation| | | | | •|
Pressure Switch| Confirm operation| | | | •| |
Magnetic Starter| Inspect| | | | •| | Replace if the contact point
deteriorates
Safety Valve| Confirm operation| | | | •| |
Pressure Gauge| Inspect| | | | •| |
Ventilation Fan| Inspect| | | | •| | Replace if malfunctions
• Inspect
Replace
Notes:
- Inspect and perform maintenance periodically according to the maintenance schedule.
- The maintenance schedule relates to the normal operating conditions. If the circumstances and load conditions are adverse, shorten the interval time and perform maintenance accordingly.
- Marked “Readjust” means the tension of the V-belt should be adjusted during the initial stage and inspected every 2,500 hours afterward; 57-65 lbs initially, then 45-50 lbs after run-in.
Maintenance Log
Date | Maintenance Required | Maintenance Performed |
---|---|---|
Electrical Diagram – Single Phase Units 230 Volts
Figure3
NOTES
-
RECOMMENDED TIGHTENING TORQUES FDR WIRE TERMINALS:
208-575 VLT POWER
35 POUND INCHES
115 VOLT POWER, CONTROL, AND LOW VOLTAGE
20 POUND INCHES -
PANEL GROUND MUST BE CONNECTED TO TD EARTH GROUND
-
INST ALLER TD PROVIDES THE MAIN DISCONNECTING DEVICE WITH SHORT CIRCUIT PROTECTION FDR FOR EACH MOTOR CIRCUIT IN THIS ELECTRICAL ASSEMBLY. SEE TABLE 1
-
ALL WIRES MUST BE LABELED ON BOTH ENDS
Electrical Diagram – Three Phase Units 208 – 230 – 460 – 575 Volts
Figure4
NOTES
-
RECOMMENDED TIGHTENING TORQUE FIR WIRE TERMINALS
208-575 VOLT POWER
35 POUND INCHES
115 VOLT POWER, CONTROL
AND LOW VOLTAGE
20 POUND INCHES -
PANEL GROUND MUST BE CONNECTED TO TD EARTH GROUND
-
INSTALLER TO PROVIDE MAIN DISCONNECTING DEVICE WITH SHORT CIRCUIT PROTECTION FOR EACH MOTOR CIRCUIT IN THIS ELECTRICAL ASSEMBLY. SEE TABLE 1
-
ALL WIRES MUST BE LABELED ON BETH ENDS
2 HP – 5 HP Scroll Enclosure Air Compressors
Figure 5
Scroll Electrical Panel Replacement Parts
Key# | 1 | 2 | 3 | 4 | 5 | 6 | |
---|---|---|---|---|---|---|---|
Model | HP | Motor Starter/ | |||||
Overload Relay | Control | ||||||
Transformer | Fuse1/Fuse2 | ||||||
(2 REQUIRED) | Fuse 3 | Pressure Switch | Control Relay | ||||
115 PSI | 145 PSI |
SES02082
208V,3P| 2| PE000101AV/
PE000205AV| PS005834AV| JP007716AV| JP007711AV| CW207573AV| CW207595AV|
PE000403AV
SES02083
230V3P| PE000102AV/
PE000210AV| PS005834AV| JP007716AV
SES02084
460V,3P| PE000101AV/
PE000204AV| PS005834AV| JP007702AV
SES12086
230V,1P| PE000103AV/
PE000207AV| PS005834AV| JP007716AV
SES03082
208V,3P| 3| PE000102AV/
PE000206AV| PS005834AV| JP007716AV
SES03083
230V,3P| PE000102AV/
PE000210AV| PS005834AV| JP007716AV
SES03084
460V,3P| PE000101AV/
PE000204AV| PS005834AV| JP007702AV
SES03085
575V,3P| PE000101AV/
PE000203AV| PS005847AV| JP007702AV
SES13086
230V,1P| PE000103AV/
PE000207AV| PS005834AV| JP007716AV
SF13087
230V, 1P| PE000102AV/
PE000207AV| PS005834AV| JP007716AV
5E13085
230V,1P| PE000102AV/
PE000207AV| JP007716AV
SF13097
230V,1P| PE000103AV/
PE000208AV| JP007716AV| CW207560AV
5E13095
230V, 1P| PE000102AV/
PE000207AV| CVV207560AV JP007716AV
SES05082
208V,3P| 5| PE000102AV/
PE000207AV| PS005834AV| JP007716AV| CW207573AV
SES05083
230V,3P| PE000102AV/
PE000207AV| PS005834AV| JP007716AV
SES05084
460V,3P| PE000101AV/
PE000205AV| PS005834AV| JP007702AV
SES05085
575V,3P| PE000101AV/
PE000204AV| PS005847AV| JP007702AV
SES15086
230V,1P| PE000104AV/
PE000209AV| PS005834AV| JP007716AV
Troubleshooting Guide
PROBLEM | CAUSE | CORRECTIVE ACTION |
---|---|---|
Power ON light does not appear | 1. The Main disconnect is not ON |
2. Blown fuse or circuit breaker at the customer-provided power supply
3. Blown fuse at the transformer
4. Lighted switch is burned out| 1. Switch disconnect to ON
2. Inspect for any fault replace fuse or trip disconnect to ON
3. Replace fuse – be sure to use the same type and size
4. Replace the lighted switch
Power ON light is on but the unit will not start| 1. Motor overload has
tripped
2. Wrong or low voltage
3. Starter has failed
4. Motor has failed| 1. See the last entry of the Troubleshooting Guide
2. Check the incoming power supply and unit power rating
3. Replace contactor assembly
4. Replace motor
The compressor is running but will not make pressure| 1. Drive belts came off
or were too loose
2. Clogged intake filter element
3. Pressure relief valve has opened
4. Excessive tip seal wear
5. Electric tank drain is open continuously
6. Unit running in the wrong direction
7. Discharge air is leaking| 1. Replace drive belts and (or) tighten
2. Replace intake filter element
3. Pressure switch needs to be replaced or motor contacts welded shut
4. Replace tip seals
5. Replace tank drain
6. Correct power connections
7. Check discharge piping
Excessive noise or vibration| 1. Drive belt has a separated or flat spot
2. Motor has failed
3. Pump is damaged
4. Cooling air fan is touching fan guard| 1. Replace the drive belt
2. Replace motor
3. Fix or replace the pump
4. Check the air fan daily
Compressor shuts down on high temperature| 1. Room temperature is above 104°F
2. Inlet air duct is obstructed
3. Cooling air fan not running
4. Aftercooler fins clogged
5. Intake filter damaged
6. Compressor is dirty
7. Tip seals worn| 1. Add ventilation or air conditioning to the room
2. Remove obstruction or reposition unit to allow for cooling air
3. Replace cooling air fan
4. Clean aftercooler
5. Check intake filter
6. Clean unit
7. Replace tip seals
Compressor turns on/off rapidly| 1. Receiver tank has a high level of water
2. Compressor check valve has failed
3. Defective pressure switch| 1. Replace electric tank drain/drain tank
2. Replace the check valve
3. Replace the pressure switch
Safety valves blow off| 1. Pressure switch has failed to open
2. Motor starter contacts welded shut| 1. Replace the pressure switch
2. Replace motor starter
Motor Overload has tripped| 1. Pump has failed
2. Motor has failed
3. Improper wiring
4. Wrong overload setting
5. Low voltage| 1. Fix or replace the pump
2. Replace motor
3. Check wiring
4. Check overload setting
5. Check incoming power supply
Notes
………………………………….
Powerex Limited Warranty – Applicable to Non-OEM Customers in the U.S. &
Canada Only
Warranty and Remedies.
(a) General. Powerex warrants each Compressor System, Vacuum System, Vacuum
Pump, Compressor Air-End, or Powerex branded Accessory (collectively
“Products’; individually each a “Product”) to be free from defects in material
and workmanship (“Defects”) at the date of shipment. This warranty shall apply
only to Products that are purchased and used in the United States of America
and in Canada. EXCEPT AS SET FORTH BELOW, NO OTHER WARRANTY, WHETHER EXPRESS
OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE, SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF SUCH
PRODUCTS. TO THE EXTENT PERMITTED BY LAW, ANY AND ALL IMPLIED WARRANTIES ARE
EXCLUDED. All warranty claims must be made in writing and delivered to Powerex
in accordance with the procedures set forth on its website
(www.powerexinc.com), or such claim shall be barred. Upon timely receipt of a
warranty claim, Powerex shall inspect the Product claimed to have a Defect,
and Powerex shall repair, or, at its option, replace, free of charge, any
Product which it determines to have had a Defect; provided, however, that if
circumstances are such as to preclude the remedying of Defect by repair or
replacement, Powerex shall, upon return of the Product, refund to the buyer
any part of the purchase price of such Products paid to Powerex. Freight for
returning Products to Powerex for inspection shall be paid by the buyer. The
warranties and remedies herein are the sole and exclusive remedy for any
breach of warranty or for any other claim based on any Defect, or non-
performance of the Products, whether based upon contract, warranty, or
negligence.
(b) (i) Standard Period of Warranty- Parts and Labor -The purchase of any
system includes our standard warranty. Powerex warrants and represents all
Products shall be free from defects for the first eighteen (18) months from
the date of shipment by Powerex, or twelve (12) months from the documented
date of a startup, or five thousand (5,000) hours of use, whichever occurs
first. During the such warranty period, Powerex shall be fully liable for all
Defects in the Products (the “Product Defects”), i.e., all costs of repair or
replacement, which may include “in and out” charges, so long as the Products
are located in the United States or Canada, and the Products are reasonably
located and accessible by service personnel for removal. “In and out” charges
include the costs of removing a Product from the buyer’s equipment for repair
or replacement.
(ii) Premium Period of Warranty- Parts and Labor – In order to be
eligible for premium warranty coverage, a premium warranty for each system
must be purchased when the order is placed. Powerex warrants and represents
all Products shall be free from defects for the first thirty (30) months from
the date of shipment y Powerex, or twenty-four (24) months from the documented
date of a startup, or seven thousand five hundred (7,500) hours of use,
whichever occurs first. During the such warranty period, Powerex shall be
fully liable for all Defects in the Products (the”Product Defects”), i.e., all
costs of repair or replacement, which may include “in and out” charges, so
long as the Products are located in the United States or Canada, and the
Products are reasonably located and accessible by service personnel for
removal. “In and out” charges include the costs of removing a Product from the
buyer’s equipment for repair or replacement.
(c) Additional Period of Warranty- Parts Only (No Labor). In addition to
the above, Powerex warrants each Powerex branded Compressor Air- End and
Vacuum Pump shall be free of Defects for a period of forty-two (42) months
from the date of shipment by Powerex, or thirty-six (36) months from the
documented date of a startup, or ten thousand (10,000) hours of use, whichever
occurs first. Supplier’s repair or replacement of any Product shall not extend
the period of any warranty of any Product. This warranty applies to the
exchange of part(s) found to be defective by an Authorized Powerex Service
Representative only.
(d) Replacement Pumps–Parts Only (No Labor). For any replacement Air-End
or Vacuum Pumps installed on a Powerex manufactured system or unit after any
initial warranty period has expired or where another warranty does not apply
for any reason, Powerex warrants that the Air-End or Vacuum Pumps shall be
free of Defects for a period of thirty-six (36) months from the date of
shipment by Powerex or ten thousand (1 0,000)hours of use, whichever comes
first. For any replacement Air-End or Vacuum Pumps installed on a system that
was not manufactured by Powerex after any initial warranty period has expired
or where another warranty does not apply for any reason, Powerex warrants that
the Air-End or Vacuum Pumps shall be free of Defects for the first twelve (12)
months from the date of shipment by Powerex. Supplier’s repair or replacement
of any Product shall not extend the period of any warranty of any Product.
This warranty applies to the exchange of part(s) found to be defective by an
Authorized Powerex Service Representative only.
(e) Replacement Motors — Parts Only (No Labor). For any replacement motor
installed on a Powerex manufactured system or unit after any initial warranty
period has expired or where another warranty does not apply for any reason,
Powerex warrants that the replacement motor shall be free of Defects for the
first twelve (12) months from the date of shipment by Powerex. For any
replacement motor installed on a system or unit that was not manufactured by
Powerex after any initial warranty period has expired or where another
warranty does not apply for any reason, Powerex warrants that the replacement
motor shall be free of Defects for the first ninety (90) days from the date of
shipment by Powerex. Supplier’s repair or replacement of any Product shall not
extend the period of any warranty of any Product. This warranty applies to the
exchange of part(s) found to be defective by an Authorized Powerex Service
Representative only.
(f) Replacement Parts- Parts Only (No Labor). For other replacement parts
besides motors, Air-End or Vacuum Pumps installed on a Powerex manufactured
system or unit after any initial warranty period has expired or where another
warranty does not apply for any reason, Powerex warrants that such replacement
parts will be free from Defects for the first twelve (12) months from the date
of shipment by Powerex. For other replacement parts besides motors, Air-End,
or Vacuum Pumps installed on a system or unit that was not manufactured by
Powerex after any initial warranty period has expired or where another
warranty does not apply for any reason, Powerex makes no warranties.
Supplier’s repair or replacement of any Product shall not extend the period of
any warranty of any Product. This warranty applies to the exchange of part(s)
found to be defective by an Authorized Powerex Service Representative only.
(g) Coverage. The warranty provided herein applies to Powerex
manufactured units or systems only.
(h) Exceptions. Notwithstanding anything to the contrary herein, Powerex
shall have no warranty obligations with respect to Products:
- that have not been installed in accordance with Powerex’s written specifications and instructions;
- that have not been maintained in accordance with Powerex’s written instructions;
- that have been materially modified without the prior written approval of Powerex; or
- that experience failure resulting from operation, either intentional or otherwise, in excess of rated capacities or in an otherwise improper manner.
(i) The warranty provided herein shall not apply to:
- any defects arising from corrosion, abrasion, use of insoluble lubricants, or negligent attendance to or faulty operation of the Products;
- ordinary wear and tear of the Products;
- defects arising from abnormal conditions of temperature, dirt, or corrosive matter; or
- any OEM component which is shipped by Powerex with the original manufacturer’s warranty, which shall be the sole applicable warranty for such component.
Limitation of Liability. NOTWITHSTANDING ANYTHING TO THE CONTRARY HEREIN,
TO THE EXTENT ALLOWABLE UNDER APPLICABLE LAW, UNDER NO CIRCUMSTANCES SHALL
POWEREX BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, PUNITIVE, SPECULATIVE, OR
INDIRECT LOSSES OR DAMAGES WHATSOEVER ARISING OUT OF OR IN ANY WAY RELATED TO
ANY OF THE PRODUCTS OR GOODS SOLD OR AGREED TO BE SOLD BY POWEREX TO BUYER. TO
THE EXTENT ALLOWABLE UNDER APPLICABLE LAW, POWEREX’S LIABILITY IN ALL EVENTS
IS LIMITED TO, AND SHALL NOT EXCEED, THE PURCHASE PRICE PAID.
Warranty Disclaimer. Powerex has made a diligent effort to illustrate and
describe the Products in its literature, including its Price Book, accurately;
however, such illustrations and descriptions are for the sole purpose of
identification and do not express or imply a warranty that the Products are
merchantable, or fit for a particular purpose, or that the Products will
necessarily conform to the illustrations or descriptions.
Product Suitability. Many jurisdictions have codes and regulations governing
the sales, construction, installation, and/or use of Products for certain
purposes, which may vary from those in neighboring areas. While Powerex
attempts to assure that its Products comply with such codes, it cannot
guarantee compliance, and cannot be responsible for how the product is
installed or used. Before purchasing and use of a Product, please review the
Product applications, and national and local codes and regulations, and be
sure that the Product, installation, and use will comply with them.
Claims. Any non-warranty claims pertaining to the Products must be filed
with Powerex within 6 months of the invoice date, or they will not be honored.
Prices, discounts, and terms are subject to change without notice or as
stipulated in specific Product quotations. Powerex shall not be liable for any
delay or failure arising out of acts of the public enemy, fire, flood, or any
disaster, labor trouble, riot or disorder, delay in the supply of materials,
or any other cause, whether similar or dissimilar, beyond the control of
Company. All shipments are carefully inspected and counted before leaving the
factory. Please inspect carefully any receipt of Products noting any
discrepancy or damage on the carrier’s freight bill at the time of delivery.
Discrepancies or damage which obviously occurred in transit are the carrier’s
responsibility and related claims should be made promptly and directed to the
carrier. Returned Products will not be accepted without prior written
authorization by Powerex and deductions from invoices for shortage or damage
claims will not be allowed. UNLESS OTHERWISE AGREED TO IN WRITING, THE TERMS
AND CONDITIONS CONTAINED IN THIS LIMITED WARRANTY WILL CONTROL IN ANY
TRANSACTION WITH POWEREX. Any different or conflicting terms as may appear
on any order form now or later submitted by the buyer will not control. All
orders are subject to acceptance by Powerex.
Powerex
150 Production Drive
Harrison, OH 45030
USA
1-888-769-797
www.powerexinc.com
Documents / Resources
|
POWEREX SES0508 2 HP or 5 HP Scroll Enclosure Air
Compressors
[pdf] Instruction Manual
SES0508, 2 HP or 5 HP Scroll Enclosure Air Compressors, SES0508 2 HP or 5 HP
Scroll Enclosure Air Compressors
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>