MERAWEX ZUP-230V-BM-400S Power Supplies for Fire Gates User Manual
- June 13, 2024
- MERAWEX
Table of Contents
USER MANUAL
Power supplies for fire gates and fire automation systems
ZUP-230V-BM-400S, ZUP-230V-BM-700S, ZUP-230V-BM-1000S, ZUP-230V-BM-700M, ZUP-
230V-BM-1000M, ZUP-230V-BM-1500L According to EN 54-4:1997 + AC:1999 + A1:2002
- A2:2006 and EN 12101-10:2005 + AC:2007
CNBOP-PIB Certificate of Constancy of Performance No. 1438-CPR-0761 Declaration of Performance DWU-MX-19 CNBOP-PIB Approval Certificate No. 4300/2021 18.07.2022
Warnings
- Please read this User Manual carefully before operating the device.
- Do not touch the internal parts of the operating device – it may cause electric shock or burns.
- Prevent any objects or liquids from entering the device – this may cause electric shocks and damage to the device.
- Do not cover the ventilation holes – it may damage the device.
- Provide a clear space of at least 10cm on the sides of the device to enable proper ventilation.
- It is forbidden to carry or transport the device with batteries installed and connected.
- The device must be powered from the mains with a protective earthing terminal.
- This device may interfere with sensitive radio and television equipment in the vicinity.
- The device may only be operated by authorised and trained personnel.
- The device may only be serviced by the manufacturer’s service staff or by specialised units authorised by the manufacturer.
Technical description.
1.1. Intended use.
Power supply with battery backup type ZUP-230V-BM supplies uninterruptible
230V power from the mains or, in the event of a power failure, 230Vac from a
DC/AC inverter powered by an internal 24V battery.
The inverter used offers a high-quality stabilised sinusoidal output voltage
of 230V 50Hz. The inverter can be loaded with any type of receiver (inductive,
capacitive, resistive). The ZUP-230V-BM power supply is designed for operation
in two modes: CSP and UPS. The CSP mode, working with the Control and
Indicating Equipment, is intended to control the opening of gates which, in
the event of a fire, in addition to their communication function, are used to
help remove smoke from the building by acting as air gates. UPS mode can be
used wherever an uninterruptible 230Vac power supply is required. The power
supply additionally features an input for connecting an EPO (Emergency Power
OFF) circuit breaker, allowing it to be switched off completely.
The basic versions of the power supplies with 400W, 700W and 1000W are mounted
in the small cabinet (S). The power supplies in the M and L cabinets can
additionally be equipped with an uninterruptible 24Vdc power supply output.
Power supply housings have hole plugs for cable glands prepared for mechanical removal during mounting:
-
for S type cabinets:
o in the upper part for 3 M16x1.5 glands and 2 M20x1.5 glands -
for M and L type cabinets:
o in the upper part for 5 M16×1.5 glands and 7 M20×1.5 glands
o in the bottom part for 3 M16×1.5 glands and 5 M20×1.5 glands
Overall dimensions of housings and weight of power supplies
Housing| Dimensions in mm| Applied to power supplies| Maximum weight with
battery
---|---|---|---
A| B| C| D| E| F| G
S| 272| 457| 205| | 165| 385| | ZUP-230V-BM -400S -700S
-1000S| 21kg 22Ah
M| 455| 406| 205| 445| 410| 360| 420| ZUP-230V-BM -700M
-1000M| 31kg 33Ah 38kg 45Ah
L| 555| 456| 205| 495| 510| 410| 470| ZUP-230V-BM -1500L| 41kg
45Ah 54kg 75Ah
In the L cabinet of the ZUP-230V-BM-1500 power supply it is also possible to
mount batteries with larger capacities; from 50Ah to 75Ah. However, when using
batteries with these capacities, the power supply will not meet the
requirements of EN 54-4 regarding the required battery charging time.
The following signs may be used interchangeably on the cabinet doors:
MAINS or FAULT or
Completion of the power supply
Equipment | Quantit | Notes |
---|---|---|
ZUP-230V-BM power supply | 1 | Fixed equipment depending on power supply type |
75W or 150W rectifier | 1 | 150W rectifier only in ZUP-230V-BM-1500L |
Temperature probe | 1 | Power supply equipment |
Battery wire (connector) | 1 | Equipped with 2 ends depending on battery type |
Battery connection wires | 2 | Equipped with ends depending on battery type |
M16×1.5 glands | 2 | Quantities can be changed in the order |
M20×1.5 glands | 2 | Quantities can be changed in the order |
Notes :
– the above general overview does not include optional modules (see 1.3.);
– 2x12V batteries must be ordered separately.
1.2. Available power supply types.
An overview of the available power supply types is given below:
Power supply type| Inverter ower| Housing type| Available battery capacity
*4)| Optional equipment
---|---|---|---|---
12 Ah| 18 Ah| 22 Ah| 26 Ah| 33 Ah| 45 Ah| 50 ÷ 75 Ah| 24Vdc output
*1)
| Relay module
*2)
ZUP-230V-BM-400S| 400| S| +| +| +| | | | | | +
ZUP-230V-BM-700S| 700| +| +| +| | | | | | +
ZUP-230V-BM-1000S| 1000| | +| +| | | | | | +
ZUP-230V-BM-700M| 700| M| | | | +| +| | | +| +
ZUP-230V-BM-1000M| 1000| | | | +| +| +| | +| +
ZUP-230V-BM-1500L| 1500| L| | | | +| +| +| *3)| +| +
1) Module used: ZUP-230V-BM-24V
2) Programmable relay module used: ZUP-TR
3) Batteries above 45Ah can be placed in L type housing, but such a power supply will not comply with EN 54-4.
4) Other capacities may be used, ranging between those indicated in the table. In this case, the power supply manufacturer should be asked to indicate the limitations.
1.3. Technical data.
The table below is provided as a basis for meeting the requirements of the
standards indicated:
− EN 54-4, which imposes a time limit of 24 hours for charging the battery to
80% of its capacity with the possibility of drawing Imax_a current for the
needs of the supplied devices
(Imax_b is the maximum, momentary current whose drawing does not allow such
charging) and the maximum additional resistance Ri max in the battery circuit;
− EN 12101-10, which defines the conditions for battery operation (when fully
charged): waiting for the load (so-called supervision) during which the
indicated current Imax_a may be drawn for 72h and the maximum short-duration
current Imax_b for 180s.
In the columns of the table that are assigned to the currents described by the
standards, for the 230Vac output, the power that can be drawn from this
output, under the same conditions as the current, is entered.
The tables present only such combinations that result from possible
configurations of the ZUP-230V-BM power supply (see 1.2.)
Permitted output loads according to EN 54-4
Power supply type| Imax_b| Imax_a| Imax_a for 24Vdc output in A for batteries
with capacities
---|---|---|---
230Vac| 24Vdc| 230Vac
W| A| W| 12Ah| 18Ah| 22Ah| 26Ah| 33Ah| 45Ah
ZUP-230V-BM-700M| 700| 2.27| 700| | | | 1.21| 0.92|
ZUP-230V-BM-1000M| 1000| 2.16| 1000| | | | 1.11| 0.82| 0.33
ZUP-230V-BM-1500L| 1500| 3.0| 1500| | | | 3.0| 3.0| 3.0
Permitted output loads according to EN 12101-10
Power supply type| Imax_b| Imax_a| Imax_a for 24Vdc output in A for batteries
with capacities
---|---|---|---
230Vac| 24Vdc| 230Vac
W| A| W| 12Ah| 18Ah| 22Ah| 26Ah| 33Ah| 45Ah
ZUP-230V-BM-700M| 525| 3.0| 0| | | | 0.21| 0.29|
ZUP-230V-BM-1000M| 750| 3.0| 0| | | | 0.18| 0.26| 0.40
ZUP-230V-BM-1500L| 1125| 3.0| 0| | | | 0.11| 0.21| 0.36
Note 1.
The power supplies in the S type housing cannot be equipped with 24Vdc output
Note 2.
The specified power values for 230V are the determined continuous load power
for the table of EN 54-4 (with present mains supply) and for 180s operation
for the table of EN 12101-10 for battery energy balance (battery operation,
without mains supply).
Note 3.
The Imax_b current shown in the tables is limited by the fuse used (see table
Basic electrical and environmental parameters).
Note 4.
It is possible to use batteries with other capacities between those indicated
in the table. In this case, ask the manufacturer of the power supply to
determine the Imax_a and Imax_b currents suitable for the battery used. The
described conditions are met for operation in the so-called CSP mode, in which
the PSU works with the control and indicating equipment. This mode of
operation is described in more detail in
3.1. For operation in the so-called UPS mode (for a detailed description see
3.2) the conditions of the EN 54-4 standard are met, while the conditions of
battery operation can be selected according to the needs of the facility where
the power supply is installed.
An example load table for the following battery operating conditions is shown
below:
− waiting time (ready to work) 8h;
− operating time at full power 180s;
− current drawn from the 24Vdc output 0.1A;
− 24Vdc output activation time 24h
Based on these assumptions and the required power from the 230V output, the
minimum battery capacity can be determined. The conditions imposed by EN 54-4
define the possible load of the power supply at the actual mains supply (see
table below).
Power supply type | Battery capacity | according to EN 54-4 |
---|---|---|
Imax_b | Imax_a | |
230Vac | 24Vdc | 230Vac |
ZUP-230V-BM-700M | 26 Ah | 700 W |
ZUP-230V-BM-1000M | 33 Ah | 1000 W |
ZUP-230V-BM-1500L | 45 Ah | 1500 W |
The Imax_b current shown in the table is limited by the fuse used (see table
Basic electrical and environmental parameters).
Basic electrical and environmental parameters.
Power supply
Mains power supply voltage| 230V – 15% +10% 50Hz
Mains current / type of power supply| 3.4A/400, 5.2A/700
6.9A/1000, 10.9A/1500
230Vac outputs *1)
230Vac output voltage
– with actual mains supply
– in case of no mains power supply *2)| equal to the supply voltage 230V ±10%
50Hz
Short-circuit protection – fuse| 10AT 5×20mm
Nominal power / power supply type| 400W/400, 700W/700
1000W/1000, 1500W/1500
24Vdc output (option)
Nominal 24Vdc output voltage 3)| 27.1V
24Vdc voltage change range 4):
– for ZUP-230V-BM-400 only
– the other ZUP-230V-BM types| 20.2…28.8V
19.0…28.8V
Maximum ripple value| 100mVRMS
Short-circuit protection – fuse| 3.15AF 5×20mm
Battery
Nominal battery voltage| 24V
Floating operation voltage at 25°C| 27.1 V (2.26 V/cell)
---|---
Temperature coefficient of the floating operation voltage| -48mV/°C
(-4mV/°C/cell)
Low battery indication| 22V
Disconnecting voltage of discharged battery
– during active inverter operation (TA time)
– out of the time of active inverter operation| 18.9…19.9V
20.4V
Maximum battery charging current
– battery capacity 12Ah
– battery capacity from 18Ah to 45Ah
– battery capacity from 50Ah to 75Ah 5)| 1.0A
2.0A
2.0A
Current draw from batteries for own use
– with the inverter operating
– with the inverter switched off
– when disconnected from discharged battery| /power supply type 0.59A/400,
0.93A/700,
1.04A/1000, 1.44A/1500 39mA 0.34mA
Maximum additional resistance in the battery circuit Ri max6)| See table of
executions in 1.2 and the settings in 5.8.
Environment
Operating temperature| -5…+40°C
EN 60529:1991 protection degree| IP 30
1) The circuits of the mains supply and the 230Vac outputs have a common neutral N wire.
2) This voltage is not synchronised with the mains supply voltage.
3) With charged battery at 25C.
4) The range shown includes the voltages between the voltage of the discharged battery ( at the end of the battery operating cycle) and the accelerated charging voltage.
5) When using batteries with the indicated capacities, the power supply will not meet the requirements of the EN 54-4 standard regarding battery charging
6) Designations according to EN 54-4+A1+A2
Compliance with standards
Electrical safety | EN 62368-1:2014 + A11:2017 class I |
---|---|
Functionality | EN 54-4:1997 + AC:1999 + A1:2002 + A2:2006; |
EN 12101-10:2005 + AC:2007
Functional class| EN 12101-10:2005 + AC:2007 class A
Environmental class| EN 12101-10:2005 + AC:2007 class 1
EMC immunity| EN 50130-4:2011 + A1:2014
EMC emission| EN IEC 61000-3-2:2019
EN 61000-3-3:2013
EN IEC 61000-6-3:2019
The power supply meets the requirement of the regulation of the Minister of
the Interior and Administration of 20 June 207 (Journal of Laws, No. 143, item
1002), with the amendment of 27 April 2010 (Journal of Laws, No. 85, item
553).
In addition, the power supply meets the requirements of the Regulation (EU)
305/2011 of the European Parliament and of the Council of 9 March 2011. (CPR –
Construction Products Regulation).
Construction and principle of operation of the power supply.
The ZUP-230V-BM power supply includes: the ZUP-BM module, a 24Vdc/230Vac
inverter, a 24V battery and a rectifier. The power supply can operate in one
of two modes: CSP and UPS. The selected operating mode defines the specific
characteristics and behavior of the power supply. This is explained in more
detail later in this manual. The ZUP-BM module is responsible for charging the
battery and supervising its status, receiving control signals, making
decisions on switching the power supply sources and performing functions
related to gate control.
With the actual mains supply, the inverter operates all the time, but with no
load on its output. This makes it possible to monitor its condition and
indicate any damage. In CSP mode, after a mains power failure, the inverter
acquires the output power supply and after a set time is switched off to save
battery power. When a control signal (fire alarm) occurs, the inverter is
switched on and supplies the receivers for a set period, after which it is
switched off again.
In UPS mode, after a mains failure, the receivers are switched to inverter
power and operate until the battery reaches end-of-discharge voltage, after
which the inverter is switched off. In this mode it is also possible to
remotely control the switching on and off of the inverter using the DO input.
The battery backs up the PSU in case of mains power failure. Its capacity
depends on the power of the inverter and the number of operated gates.
The 230Vac/24Vdc rectifier charges the battery, keeps the inverter operating
with the actual 230V mains supply and allows the power supply of additional
receivers connected to the optional 24Vdc output.A simplified diagram of the
power supply is shown below.
For the user, there is a fused 230Vac power supply output of the gate OUT and
relay indicating outputs GEN FLT and CSO. Via the GEN FLT output (collective
fault signal) the power supply indicates:
– 230V mains power failure,
– inverter damage,
– high resistance of the battery circuit,
– low battery voltage,
– configuration error of a control input from CSP,
– rectifier damage,
– temperature probe damage,
– tripping of the EPO input.
Depending on the selected operation mode, the CSO output triggers gate opening
or acts as an additional PSU status indication. The power supply has two
control signal inputs CIE and DO. Their function depends on the selected
operating mode.
The main feature that distinguishes CSP mode from UPS mode is the way the
voltage is supplied to the OUT output and the control of the CSO output, as
well as the way the signals from the CIE and DO inputs are received. However,
in both cases, 230Vac mains voltage is supplied to the OUT output when mains
power is present.
Accessory equipment of the ZUP-230V-BM power supply: ZUP-230V-BM-24V – a
module enabling to supply external devices which require uninterruptible 24Vdc
voltage.
The module includes a connector for mounting on a TS-35 bus together with a
fuse. Voltage is supplied from the rectifier and, in the event of a mains
power failure, from the battery. Maximum load of this output depends on the
particular type of the ZUP-230V-BM power supply and its operation mode (see
table of technical data in 1.2 ).
ZUP-TR – programmable relay module enabling additional time functions. The
ZUP-TR module contains a relay, designed for mounting on a TS-35 rail,
equipped with a potential-free output with a load capacity of 10A/230Vac and
10A/24Vdc, which can be controlled from both 24Vdc and 230Vac. In addition to
the relay, additional elements are supplied: connecting cables, connectors,
single-circuit connectors, etc.
The relay can be used, for example, to extend the time of switching the power
supply from the mains to the battery or vice versa (in this manual it is the
T_DLY time) when the power supply unit cooperates with controllers requiring a
long break between the power failure and return.
If it is necessary to use this relay, it is required to contact the
manufacturer of the power supply in order to agree on detailed electrical and
assembly requirements.
2.1. Operation in CSP mode for air gates.
The CSP mode is designed to work with the output of the CIE (Control and
Indicating Equipment) or the output of its wire module. Receiving a fire alarm
signal through the CIE input causes control of the relay at the CSO output,
which, through the gate controller, causes opening of the gate. In the event
of a mains power failure, the voltage is switched off at the OUT output after
a set TS time of the inverter. Only when the control signal appears, it
restarts the inverter, which supplies the OUT output and then, with some
delay, the relay at the CSO output is controlled The delay enables the
operating conditions of the controller to settle down so that the controller
can accept this signal. The DO control input functionally works in the same
way as the CIE input. The differences concern their purpose and the way they
are connected. The CIE input is designed to work with CIE and the way it is
connected can be configured. The DO input only enables to connect an
additional manual push button to open the gate by closing its terminals.
The DO input should not be used for normal daily gate operation. In the
absence of mains power, this can lead to discharging of the batteries and
incorrect operation of the PSU in the event of a real emergency. The manual
gate opener button connected to this output should be treated in the same way
as the fire alarm buttons, i.e. it should be protected against accidental or
unauthorised use. Restoration to normal operation requires it to be reset and
re-secured. If the DO input is left in the ON (closed) state, in any situation
where the CSO signal has already been switched off, the appearance of a fire
alarm at the CIE input switches it on again
Note.
For the factory settings, voltage is always present at the OUT output when
mains power is present.
In the absence of mains power, battery operation lasts only a specified time.
For more information on the electrical parameters for the CSP mode, please
refer to the technical data table in 1.2. The time dependencies for this mode
are presented in 3.1
DO – Manual opening of the gate. Digital input active by closing the
terminals.
CIE – signal input from CIE or wire module output. It can be configured as a
digital input with wire resistance monitoring. For digital inputs it will be
respectively closing and opening of the terminals and for operation with wire
control, low and high resistance (see Power supply configuration). CSO – relay
output. In CSP mode, the CSO output is responsible for triggering the gate
opening by closing the corresponding input in the gate controller. Continuous
or cyclic operation can be set, with repeated pulses triggering the gate
opening. The function of this output can also be changed to indication of 230V
mains power failure.
EXT MOD – connector for connection of expansion modules.
2.2. Operation in UPS mode.
The UPS mode only provides voltage backup to the OUT output after a mains
power failure (see 3.2). The backup time is limited only by the capacity of
the batteries used and the actual load. In this mode, the inverter operation
is controlled by the DO input. Through this input, the inverter can be
remotely switched off and on again. The CIE input is inactive in this mode of
operation. For more information on the time dependencies for UPS mode, see 3.2
and 5.8.
DO – Signal of resuming or shortening the operation time. Digital input active
by closing the terminals.
CSO – relay output. In UPS mode, the CSO output is responsible for indication
of low battery voltage. This function can be changed to indication of 230V
mains power failure.
2.3. EPO circuit breaker
An EPO (Emergency Power OFF) circuit breaker can be connected to the power
supply.
Note.
The EPO circuit breaker may only be used when operating in UPS mode. Operation
of the power supply in the CSP mode, i.e. as a fire protection device,
excludes such a possibility.
Its use causes a complete shutdown of the power supply: disconnection of the
230V output and the 230V mains supply as well as disconnection of the internal
inverter from the battery. The disconnection concerns only the L wire of the
230V supply system. The N wire between the mains input and the PSU output
remains connected. In this state only the power supply controller and its
status indication remain active.
The purpose of the mains disconnection relay is to protect against backfeed -.
voltage appearing in the mains circuit as a result of the operation of the
inverter in the power supply.
The power supply enables selection of the operation mode of the EPO signal
input: by opening or closing the terminals – see pos. 9 in the table
describing the setting of the slide switch in 5.8. Restoring the power supply
to operation, apart from switching off the EPO signal, requires a reset of the
power supply with the RUN button. If this input is not used, the terminals of
this input must be necessarily closed and the slider no. 9 of the SETTINGS
switch set to the ON position.
Detailed description of the power supply operation
A table of detailed setting ranges for CSP and UPS mode is provided in 5.8.
A description of the time designations used in Figures 5 to 13, together with
their values, is presented in the table below.
TA | 9 min | inverter operating time triggered by a fire alarm |
---|---|---|
TS | 9 min | inverter operating time triggered by mains power failure |
T DLY | 25ms/2s | mains to battery and battery to mains supply switching time |
T MR | 5s | delay in switching to mains (required time of stable mains) |
T INV | max 10s | inverter start-up time |
T CIE | 2s | time of recognition of the control signal at the inputs (minimum |
duration)
T CSO| 2s/12s| gate opening delay
Each switching of the power source is associated with a loss of the output
voltage for the T_DLY time. There is a choice of two values for this time: 2s
or 25ms.
Switching from battery to mains supply can only take place when the 230V mains
voltage has been present and stable for the T_MR time (5s). This function
protects the power supply against the connection of unstable mains voltage.
The presence of a control signal at the CIE or DO inputs for a minimum of 2s
(T_CIE time) is required to eliminate false alarms and disturbances. A too
short or unstable signal will be ignored.
There are two values of gate opening delay time to choose from: 2s or 12s.
3.1. CSP mode
The voltage at the OUT output when the mains supply is present is always
present. The inverter operates during this time for control purposes only. In
the event of a mains power failure, the voltage is switched off at the OUT
output after a set TS time of the inverter. Giving a control signal to the CIE
or DO input (they have the same function) activates the power supply for TA
time (9min), during which the inverter supplies the OUT output. The CIE input
is dedicated to operate the fire automation signal, hence it can be
supervised, the DO input is dedicated to connect a manual gate opener button.
The figures below present basic situations of the power supply operation in
the CSP mode, in which the voltage backup at the OUT output has been set to
continue with the present mains supply, in spite of the termination of a fire
alarm (the H sliding switch in the ON position, see the table in 4.).
Setting the switch to OFF position will switch off the voltage at OUT output
after TA time (simultaneously with CSO signal disappearance) both in case of
the present mains supply and battery operation. This is intended to improve
safety during firefighting operations. Thus, the occurrence of a fire alarm
will trigger a certain action of the power supply only once. A second or
subsequent alarm signal will have no effect. Return to normal operation after
the abovementioned action and restoration of the voltage at the OUT output
requires a reset of the power supply by pressing the RUN button (see the table
in 4.0.). The CSO output can operate in two ways (see table in 4.0.): − give
a continuous gate-opening signal; − cyclically repeat the pulses that trigger
the opening of the gate. The second way can be used by some gate controllers
to automatically resume its movement if the gate is temporarily mechanically
blocked, or stopped by a button on the control panel.
Fig.5 (below) Return of mains power and appearance of fire alarm with 230V
mains power present.
In the stand-by state ( without fire alarm) the appearance and then the
persistence of a stable MAINS supply for a T_MR time causes the power supply
to switch to the OUT output. If a signal appears on the CIE input at the
present mains supply and is aintained for the T_CIE time, a countdown of the
TA and T_CSO times will be started. After the countdown of T_CSO time, the CSO
relay is excited, triggering the opening of the gate. With the end of the TA
time countdown, the CSO relays switched off.
Fig.6 (below) 230V mains power failure and appearance of a fire alarm in the
absence of mains power.
In the event of a mains power failure, a switchover to battery power takes
place after T_DLY time for a set TS time. If there is a signal on the CIE or
DO input present for a T_CIE time, the inverter is activated. After T_INV time
(time required for inverter start-up), the voltage at the inverter output
appears and the countdown of TA and T_CSO times starts. After the countdown of
T_CSO time, the CSO relay is excited, triggering the opening of the gate.
Then, after the TA time has passed, the inverter and the CSO relay are
switched off.
Fig.7 (below) Appearance of a fire alarm during battery operation caused by
230V mains power failure.
The detection of a fire
alarm at the CIE input during battery operation (triggered as in the
description to Fig.6.) causes the interruption of the TS time countdown and
the start of the TA and T_CSO time countdown. Then, as before, after the
countdown of theT_CSO time, the CSO relay is excited, triggering the opening
of the gate. Then, after the TA time has passed, the inverter and the CSO
relay are switched off.
Fig.8 (below) 230V mains power failure during theTA operation triggered by a
fire alarm.
230V mains power failure during TA time countdown forces switching to battery
supply with momentary power failure at theT_DLY time. The behaviour of the CSO
relay, previously switched on after recognition of the CIE signal, depends on
the setting of the T_DLY time (switching time of the power source). For a set
long break time (2s), the CSO relay is switched off together with the mains
power failure and switched on again, after switching to battery operation,
with the T_CSO delay. This behaviour is compatible
with the gate controllers, which do not tolerate even short power outages,
after which they need to be reset and restarted – to continue opening the
gate.
Gate controllers that are able to ignore the short break time (25ms) do not
require a reset and restart operation. In this case switching on of the CSO
relay is maintained despite a change of the power source.Fig.9 (below) Return
of 230V mains supply during battery operation caused by mains power failure.
Detection of MAINS stable mains supply at T_MR time interrupts the TS time
countdown (see description to Fig.6.), ends battery operation and with a delay
of T_DLY restores mains supply to the OUT output.
Fig. 10a. (below) Return of 230V mains supply during battery operation
triggered by a fire alarm, with interruption of battery operation.
If battery operation is allowed to be interrupted when the mains supply
returns (see 4. Description of ZUP_BM board, switch B), switching to mains
supply takes place as soon as the stable mains is detected at the T_MR time.
In this case, after the TA time is counted down, only the CSO relay is
switched off. The detailed way of switching to the mains power supply
including the operation of the CSO relay is included in the description to
Fig.8.
Fig. 10b (below) Return of 230V mains supply during battery operation
triggered by a fire alarm, without interruption of battery operation.
If the possibility of interruption of battery operation on return of the mains
voltage is disabled (see 4. Description of ZUP_BM board, switch B), in spite
of its return in TA time, the switching to the mains voltage takes place as
soon as this time has passed, provided that the mains voltage was sustained
before that time longer than the T_MR time and additionally only after the
T_DLY break time. The CSO relay is switched off at the end of the TA time
countdown.
If, however, the battery is discharged during battery operation, the
switchover to mains operation will take place immediately, as indicated in the
description to Fig.10.a above.
3.2. UPS mode
In this state, the voltage on the OUT output is always present when the
230V network is present. The CIE input is inactive.
The way the device operates depends on the setting of the switch no. 4 in the
CI section defining the operation of the DO input (see 5.8 Power supply
configuration). For battery triggered operation (switch in OFF position) it is
recommended to use a monostable switch (e.g. a button). A bistable switch
should be used for battery static operation (switch in ON position).
For slider switch no. 4 set to OFF (triggered switchable battery operation), a
switchover to battery operation takes place as soon as a mains power failure
is detected. At the OUT output after the
T_DLY time a voltage of 230V from the inverter appears. In this state,
appearance of a low state at the DO input causes switching off of the inverter
(230V voltage failure at the OUT output). Each reappearance of the low state
on the control input changes the operating status of the inverter – it turns
it on if it was previously off, or turns it off if it was previously on. With
the mains supply present, the DO input is inactive.
In case of the slide switch no. 4 set in the ON position (static battery operation, switched on) at the moment of detecting the mains power failure, the battery operation is switched (switching of the OUT output to 230V voltage from the inverter after the T_DLY time) provided that the DO signal is active. This voltage is maintained as long as the signal at the DO input is active. When no active signal is detected at the control input, the inverter operation is switched off. The inverter can be switched on again when an active state is given to the DO input.
The return of a stable voltage from the mains (for the T_MR time) causes the OUT output to switch to the mains regardless of the state of the DO input. If an active state was maintained on the DO input before the mains power returned and the OUT output was connected to the inverter voltage, the output from the inverter will be switched to the mains.
Start-up of the inverter in the absence of mains power and its continued operation depend on the state of charge of the batteries.
Description of ZUP-BM board
Description of elements of ZUP-BM board.
In the Designation column, the full English words from which the acronyms were
derived are entered.
Designation | Function descriptio n |
---|
Connectors on ZUP-BM board
MAINS 230V MAINS 230V| 230Vac mains power input.
INVERTER Inverter 1)| Power input from 230Vac inverter.
OUT Output| Power output 230Vac.
PS MAINS Mains Power Supply 1)| 24Vdc rectifier mains supply connector.
CSO Control Signal Output| Relay output of the control signal. NO and NC
contacts are available.
The excitation status of the relay is indicated by a yellow LED mounted at the
edge of its base.
SERVICE Service| Service connector (do not connect!).
COM Communication| Digital communication connector (do not connect!). Only for
the manufacturer’s use.
TEMP Temperature probe 1)| Temperature probe connector.
GEN FLT General Fault| Fault relay indication (see description of FAULT LED).
The output is a collective fault signal. NO and NC contacts are available. It
operates with a delay of 5s in case of mains power failure.
The excitation status of the relay is indicated by a yellow LED mounted at the
edge of its base.
CIE| Control signal input from Control and Indicating Equipment
Control and Indicating Equipment| – the alarm state must last longer than 2s;
the method of operation is described in 5.8
---|---
DO Open Doors| Non-parameterised signal input for manual gate opening in CSP
mode and inverter on/off in UPS mode.
EPO Emergency Power Off| Control signal input from safety switch.
DC INPUT DC Input 1)| 24Vdc power input.
24V OUT 24V OUT| | Connector for connection of 24Vdc output module of ZUP-
230V-BM-24V
+INV Inverter| 1)| Positive bus of the inverter power supply.
+BATT Battery| 1)| Positive terminal of the battery.
– BATT Battery| *1)| Negative terminal of the battery.
| RUN button
RUN Run| | A short press on the button provides:
– resetting the power supply after its switching off by the signal from the
EPO input;
A button pressed for more than 2s resets the EPO function and additionally
enables:
– reduction of the TA time ( time of operation triggered by a fire alarm); –
starting the power supply from a battery;
– checking the functionality associated with the selected mode;
– in the CSP mode, resetting the power supply after an action triggered by a
fire alarm (see 3.1) only with H slider of the SETTINGS switch in the OFF
position
LED indication on ZUP-BM board
ON On| Green| Board power indication
INVERTER POWER Inverter Power| Red| Indication of connection of the inverter
directly to the battery.
INVERTER ST-BY Inverter Stand By| Yellow| Inverter back-up indication.
Inverter powered by 230Vac/24Vdc rectifier
INVERTER INV-OUT Inverter Out| Green| Inverter operation indication.
CIE Control and Indicating Equipment| Red| Fire alarm indication
– off: no alarm or UPS mode operation
– lit: a fire alarm has occurred (also when using the RUN or DO button);
– flashing: a fault has been detected on the fire alarm input wire from the
CIE;
– short flashes – correct CIE wire status
DO Open Door| Yellow| Indication of active state on DO input.
OUT Output| Green| OUT output connected to mains
Yellow| OUT output connected to inverter
Turned off| No voltage at the OUT output
RI Battery Circuit Resistance| Yellow| Battery fault indication
EPO Emergency Power Off| Red| Indication of the tripping of the EPO circuit
breaker
LED indication on the door of the ZUP-230V-BM power supply cabinet
MAINS| Green| Power status:
Mains| | – lit: mains supply present;
– flashing: battery operation (no mains supply) – off: no power supply,
battery disconnected
---|---|---
FAULT Fault| Yellow| Fault indication:
– 230V mains power failure,
– inverter damage,
– high resistance of the battery circuit,
– low voltage of 22V battery (only during battery charging)
– configuration error of a control input from CIE,
– rectifier damage,
– temperature probe damage,
– tripping of the EPO input.
SETTINGS slide switch (detailed description in 5.8.)
CI Control and Indicating| Setting the mode and method of operation for the
power unit
Ah Ampere Hours| Choice of battery capacity
CSO Control Signal Output| Setting the method of operation for the CSO output
EPO Emergency Power Off| Setting the method of operation (active state) for
the EPO input
Hu Hold Up| Maintaining voltage on the OUT output after a fire alarm from the
CIE input
P Pulse| Method of gate opening activation by CSO output
E130 End of Battery Operation| Method of terminating battery operation when
the mains power returns (for CSP mode only).
*1) Connections made by the power supply manufacturer.
Installation
5.1. General notes
The place of installation of the power supply should be selected in such a
way as not to expose it to mechanical damage and not to exceed the acceptable
parameters of temperature and air humidity. If possible, the power supplies
should be installed in fire-separated rooms (e.g. electrical switchboards,
technical rooms, cable shafts, etc.). A small cabinet (S type) should be fixed
directly to the wall through 3 holes in its back wall, whereas a medium and a
large power supply cabinet (types M and L) can be fixed directly to the wall
through 4 holes in its back wall or using four distance brackets. The location
of the fixing holes is shown in Fig.1. Metal screw anchors should be used for
installation. Screw anchors made of PVC must not be used. When assembling a
medium or large cabinet with direct use of the rear panel openings, it is
advisable to first remove the inverter by unscrewing the two nuts at its
bottom, tilting it slightly and sliding it downwards. Due to its weight and
dimensions, the battery should be placed in the abinet last, after all cable
connections have been made.
Note.
The selection of cables in power supply and control systems for fire
protection devices should take into account Art. 187 of the Regulation of the
Minister of Infrastructure of 12 March 2009 Dz. U. /Journal Of Laws/ No. 56
item 461 on technical conditions to be met by buildings and their location, as
amended. Consolidated text of the Ordinance of the Minister of Infrastructure
of 7 June 2019 item 1065.
5.2. Connection of mains supply
The mains supply cable with a minimum cross-section of 3×1.5mm 2, after
being fixed in the gland, should be led through a large arc before it is fixed
by the cable holder and connected to the corresponding terminals of the ZUP
power supply. The outer insulation of the cable (tyre) should be removed
directly behind the cable clamp.
Note: It is absolutely necessary to identify the L wire of the mains
supply and to connect it properly to the L terminal of the ZUP-230V-BM feeder
(MAINS 230V connector, L terminal).
The connection of the mains supply must be made as a permanent installation
with continuity of the neutral wire (N). The installation switch described
below must be in the live wire (L). The power supply is not equipped with its
own mains circuit breaker, so a special installation breaker is required
outside the power supply. Such a circuit breaker should also perform the role
of an overload and short-circuit protection and allow to power devices with a
high starting current. It is recommended to use the S301 C16A installation
circuit breaker. Such a circuit breaker should be clearly marked as being used
in the fire protection system and must not be used in other circuits at the
same time.
Warning.
Connecting the mains using the switch located outside the power supply can
be done only with fully assembled internal wiring of the power supply,
including the inverter correctly connected and mounted. It is forbidden to
leave the 230Vac power plug disconnected from the inverter output.
5.3. Connection of 230Vac circuits
The wires for external connections should be routed through the selected
openings in the cabinet body (after removing the blanking plugs) and fixed by
twisting the appropriate cable glands. The wires which are to be led to the
output (and outputs of optional expansion modules) after fixing them in the
glands should be led through a large arc before they are fixed by cable
holders and connected to respective terminals of the ZUP power supply. The
outer insulation of the cable (tyre) should be removed directly behind the
cable clamp. A 3-core HDGs 1.5mm 2 cable is recommended for making connections
of 230Vac power supply systems in fire protection systems. For devices of
insulation class II, it is possible to use 2-core cables without connection to
PE bus. Only one consumer device can be connected to the OUT output on the
ZUP-BM board of the power supply. It is necessary to pay attention to the
nature of load carried by some receivers. For example, induction motors can
consume considerable current at start-up that can lead to blowing of the fuse
placed at the given output or prevent correct start-up of the inverter.
5.4. Connecting the battery
The battery, placed with its terminals on the door side of the housing,
must be connected using the two wires already brought out from the power
supply, paying particular attention to the correct polarity: red wire to the
positive terminal of one battery, black wire to the negative of the other
battery. Finally, connect the two batteries to each other using the cable
(connector) supplied by the manufacturer.
NOTE: The power supply is not protected against reverse connection of the
battery. Incorrect connection may lead to destruction of the power supply.
The battery should be connected with the battery disconnector switched off and
its fuse link removed. All connections should be made carefully, bearing in
mind that during battery operation (when the mains supply is off) the current
drawn by the inverter may reach 90A. For correct temperature compensation of
the battery floating operation voltage, the temperature probe should be placed
between the sides of both batteries.
5.5. Emergency operation with one power source.
The power supply should work with both power sources connected:
– primary, mains;
– backup, battery.
However, it is possible to run the power supply in an emergency when only one
power source is present, which will, for example, allow the gate to be
operated, but will not ensure that the primary function -of providing a
guaranteed power supply is fulfilled.
Below, there is an indication of the operational status of the ZUP-230V-BM
power supply in case of connection of both power sources (mains and batteries)
or only one of them. Start-up of the power supply from the mains is automatic.
In case of lack of the mains power supply, the RUN button should be pressed
(see 4).
The table shows the operation of the power supply in the CSP mode. Notes under
the table indicate differences specific to UPS mode.
Operation indications in case different power sources are connected|
battery and mains| only battery| only mains
---|---|---|---
LED indication – cabinet door
MAINS| green| Mains supply status.| turned on| flashes| turned on
FAULT| yellow| Fault indication.| turned off| turned on| turned on
LED indication – ZUP-BM board.
ON| green| Board supply status.| turned on| turned on| turned on
INV-OUT| green| Inverter operation indication.| turned on| turned on| turned
off
POWER| red| Inverter connected directly to the battery.| turned off| turned
off| turned on
ST-BY| yellow| Inverter in stand-by mode (supplied by rectifier)| turned on|
turned off| turned off
CIE )| red| Indication of the confirmation of a fire alarm.| short flashes|
short flashes| short flashes
DO )| yellow| DO input active state| turned off| turned off| turned off
OUT| green| Mains voltage present at OUT output| turned on| turned off| turned
on
yellow| Voltage from the inverter present at the OUT output| turned off|
turned off )| turned off
RI| yellow| Battery fault indication.| turned off| turned off| turned on
EPO )| red| Indication of the tripping of the EPO circuit breaker| turned
off| turned off| turned off
Relay indication
GEN FLT| Fault indication The excited state indicates no damage.| excited| not
excited| not excited
CSO| Control signal output.| not excited| not excited| not excited
*) The indicated LED state corresponds to the absence of an active state at the CIE input. Its short flashes additionally indicate the correct state of the CIE wire (see table in 4.). In UPS mode, the CIE input activity indication is off.
) In UPS mode with switch operation, the DO input activity indication lights
up. In this mode, with battery power only, the OUT output is supplied with
voltage from the inverter, so the OUT LED lights up yellow.
Yellow LEDs are mounted near the bottom edge of the housing of both indicating
relays. Their lighting indicates the state of excitation of the respective
relay.
5.6. Connection of control inputs.
** The CIE input (confirming the fire alarm signal from the CIE) can operate
with parameterisation or as a binary input. However, in both cases it is
required that the parameters of the control circuit are within certain defined
limits: − for input with parameterisation, resistance values including
connection resistance and leakage resistance (between wires) must not differ
by more than 10% from the required value of 1kΩ and 10kΩ
− for binary input the short circuit resistance must not be higher than 1kΩ
and the leakage resistance (between wires) must not be lower than 100kΩ.
If these values are exceeded, the power supply sets the GEN FLT error
indication.
The DO and EPO inputs, unlike the CIE input, are not supervised. They are
binary inputs responding to short-circuit and open terminals.
5.7. First start-up.
5.7.1. Starting the power supply in the CSP mode.
The power supply start-up process described below refers to start-up using
the factory settings described in 5.8. It is recommended that the first start-
up be performed by service personnel trained by the manufacturer. In case of a
different PSU configuration than the one resulting from the factory settings,
some items will look different. The presented process assumes correct
operation of all elements. In case of any discrepancies, please refer to the
appropriate descriptions included in the operational manual or contact the
manufacturer’s service to clarify any doubts.
Initial state:
− mains power disconnected by the installation switch (outside the power
supply);
− terminals of the batteries are not connected and, additionally, the
batteries are disconnected by the circuit breaker inside the power supply
(marking on the diagram: W-BAT)
− if no gate controller is connected to the OUT output, any receiving device
(voltage indicator, bulb, motor, etc.) should be connected in its place;
− if no gate controller is connected to the CSO output, e.g. an ohmmeter or
other tester will be needed to check the relay status on this output;
− if no receiver for this signal is connected to the GEN FLT output (e.g. fire
panel), e.g. an ohmmeter or other tester will be needed to check the relay
status on this output;
− check the configuration of the SETTINGS switch, which should be in
accordance with the factory settings (see figure below);
The setting of the Ah section (sliders 5 and 6) should correspond to the
specific type of power supply being activated, and the battery used (see
tables in 5.8.)
− resistors parameterising this wire should be connected to the CIE input as
shown in Fig. 15. with the 1kΩ resistor circuit being open (no fire alarm);
− the DO input should be left unconnected and, if it is to be used, the switch
connected to it should be opened (no forced opening of the gate);
− a jumper should be placed on the EPO input (this input is not used in CSP
mode).
Preparation for start-up:
− connect the battery terminals paying special attention to the correct
polarity (reversed polarity can lead to permanent damage to the power supply;
− Switch on the W-BAT battery switch.
Start-up
-
Switching on the mains supply
• the green ON diode lights up permanently (power supply operation indication);
• a test of 5 LEDs is carried out, the LEDs light up one after the other and then go out, leaving the current operating status indication:• short flashes of the CIE diode indicate correct operation of the CIE fire alarm wire parameterisation system;
• green colour of the OUT LED indicates presence of the mains power at the OUT output of the power supply.Relay outputs: GEN FLT excited (no damage) CSO not excited (no signal to open the gate)
-
Switching off mains power (switching to battery operation)
• the power supply switches to backup source (battery), which is indicated by the OUT diode turning yellow as soon as voltage from the inverter appears at the OUT output;
• after a short power failure, for the T_DLY time of 2s, the voltage from the inverter appears at the OUT output which is independently maintained in this state for the maximum TS time of 9min.Relay outputs:
GEN FLT not excited (fault indication – no power supply) CSO not excited (no signal to open the gate) -
Transmission of a fire alarm signal to the CIE input.
• at TS time, when battery operation is in progress, connect a 1kΩ resistor to the CIE input for longer than T_CIE 2s;
• from this moment on, at the OUT output supplied by the inverter, the voltage is maintained independently for a maximum TA time of 9min.Relay outputs:
GEN FLT not excited (fault indication – no power supply)
CSO excited after T_CSO time of 12s, which triggers opening of thegate (if the gate controller is connected) -
Return of mains power during gate opening
• at TA time, during operation triggered by a fire alarm, this alarm must be disabled (disconnect the 1kΩ resistor from the CIE input) and then restore the mains supply; If a gate controller is connected to the power supply, it is advisable to perform this operation before the gate is fully open.
• the power supply switches to main power source (mains), which is indicated by the OUT diode turning green as soon as voltage from the mains appears at the OUT output;
• the inverter enters standby mode which is indicated by its ST-BY LED;• after a short voltage decay, for the T_DLY time of 2s, the mains voltage appears on the OUT output;
• the relay at the CSO output temporarily, at T_DLY + T_CSO time of 14s stops being excited and after TA time of 9min switches off permanently,
If a gate controller is connected to the power supply, the return of the CSO signal should resume the gate movement if it has stopped during a temporary mains power failure.
• after the TA time of 9min has elapsed, the power supply returns to the state described in step 1 of start-up.
The TA time countdown can be interrupted (shortened) by pressing the RUN button.The time course shows the entire start-up process with an indication of its successive steps.
5.8. Power supply configuration
On the ZUP-BM board there is a slide switch allowing to set the function of
the power supply. Some of the settings require restarting the power supply,
restarting by temporarily disconnecting the 230V mains and the battery until
the ON diode goes out. In the table below, these particular slide switch
positions are enclosed in rectangular brackets [ ]. Description of the
SETTINGS switch sliders.
Item| Slide control in the OFF position – off| Slide control in
the ON position – on
---|---|---
[ 1. ]| UPS mode operation (see 2.2.)| CSP mode operation TA =
9min (see 2.1.)
2.| T_DLY delay in mains-battery-mains switching off (min. value
of ~25 ms remains)| T_DLY delay in mains-battery-mains switching on
(2s)
3.| CIE signal- active low state: shorted terminals or low
resistance (1kΩ)| CIE signal – active high state: terminal open or high
resistance (10kΩ)
4.| For CSP mode CIE input parameterisation off. (shorted – open).|
For USP mode DO signal
– switch operation (see 3.2.)| For CSP mode CIE input
parameterisation on (1kΩ/10kΩ).| For USP mode
DO signal
– static operation (see 3.2.)
[ 5. ]| See the following table of Ah section settings.
[ 6. ]
7.| T_CSO delay Gate opening: 2s| T_CSO delay Gate opening: 12s
[ 8. ]| CSO output for CSP mode – triggers the opening of thegate|
CSO output for UPS – mode indicates low battery| The CSO output for
both modes, CSP and UPS, – signals the loss of the 230V mains supply.
9.| EPO signal – active low state (terminals shorted)| EPO
signal – active high state (terminals open)
Only for CSP mode
10.| With the mains supply present, after the alarm on the CIE wire
is terminated, the voltage on the OUT output disappears after a TA
time| When the mains supply is present, despite the disappearance of an alarm
on the CIE wire, the voltage at the OUT output remains even after
TA time.
11.| CSO output switched on continuously (only when gate opening
activation is selected: slider 8 in OFF position.| CSO output switched
cyclically: pulse 5s and pause 5s
(only when gate opening activation is selected: slider 8 in OFF position).
[12.]| Switching to the mains supply during the TA time countdown (will temporarily interrupt the power supply at the OUT output).| Switching to mains supply will only take place after the set TA time has elapsed.
Slide switch settings in the Ah section. Slide positions 5 and 6
Power supply type | Selected battery capacity and charging current |
---|
|
|
|
ZUP-230V-BM-400| –| –| 12Ah / 1A| 18 and 22Ah / 2A
ZUP-230V-BM-700| 12Ah / 1A| 18 and 22Ah / 2A| 26Ah / 2A| 33Ah / 2A
ZUP-230V-BM-1000| 18 and 22Ah / 2A| 26Ah /2A| 33Ah / 2A| 45Ah / 2A
ZUP-230V-BM-1500| 26Ah / 2A| 33Ah / 2A| 45Ah / 2A| 50…75Ah / 2A
Maximum additional resistance Ri max in the battery circuit in mΩ.
Power supply type | Battery capacity |
---|---|
12Ah | 18Ah |
ZUP-230V-BM-400 | 99 |
ZUP-230V-BM-700 | 46 |
ZUP-230V-BM-1000 | |
ZUP-230V-BM-1500 |
The following shows the status of the SETTINGS switches for the factory settings and a table describing the functions selected with them.
Slider No.| Slider position|
Description
---|---|---
1.| ON| Operation in CSP mode
2.| ON| Output voltage dtop time T_DLY : 2s.
3.| OFF| Fire alarm triggered by a low state.
4.| ON| CIE input parameterisation enabled (1kΩ/10kΩ).
5.| x| Position of sliders according to power supply type
6.| x
7.| ON| T_CSO delay for gate opening: 12s
8.| OFF| CSO output triggers gate opening
9.| ON| EPO input active with high state (terminal open)
10.| ON| The voltage at the OUT output is maintained even though the alarm
has been cancelled
11.| OFF| The CSO output is switched on continuously.
12.| OFF| Switching to mains supply can take place during the TA time
countdown.
The setting of sliders 1, 10 and 12 indicated above are required to ensure that the power supply complies with the EN54-4 standard.
Maintenance and service
- Service personnel may only replace the indicated fuse with a fuse of the same parameters and type as that used in the device.
- All warranty and post-warranty repairs are carried out by the manufacturer’s service department or by a specialised unit authorised by the manufacturer.
Maintenance
The device does not require any special maintenance. During normal
operation, the only action required is to keep the surroundings of the power
supply reasonably clean.
Service
The following is a list of fuses available to service personnel that can be
replaced in the event of damage.
Description of an element in the power supply| Manufacturer|
Type| Size| Value
---|---|---|---|---
Fuses in all ZUP-230V-BM power supplies
CHARGER| SIBA| 179020| 5 x 20mm| 10AF
OUTPUT| SIBA| 179120| 5 x 20mm| 10AT
Fuse in battery circuit for ZUP-230V-BM-400, -700, -1000
W-BAT| | gG| D02 (15 x 36mm)| 63A
---|---|---|---|---
Fuse in battery circuit for ZUP-230V-BM-1500
W-BAT| DF ELECTRIC| gG| CH22 (22 x58mm)| 100A
Fuse in additional module ZUP-230V-BM-24V
| SIBA| 179020| 5 x 20mm| 3.15AF
Additional information
7.1. Manufacturer’s remarks
The manufacturer reserves the right to introduce design and process
modifications not affecting the parameters of the product.
7.2. Compulsory technical inspection
The ZUP-230V-BM power supply should be subjected to periodical technical
inspection by the manufacturer’s service or an entity authorised by the
manufacturer at least once a year during its entire life.
Any work carried out by unauthorised persons, or failure to carry out periodic
inspection, may result in the loss of the manufacturer’s warranty and will
transfer the responsibility for the correct operation of the power supply to
the user. The execution of the inspection should be confirmed by an
appropriate protocol according to a model established by the manufacturer.
The user is obliged to ensure access to the devices to be inspected and to
present documentation showing how the power supply is connected to the
cooperating devices. It is recommended that such documentation, operational
manuals for the power supply and associated equipment and inspection records
are kept together and made available upon request by the manufacturer and
during periodic inspection. It is also recommended that between inspections,
during normal operation of the equipment, attention be paid to any electrical
or mechanical damage, both to the power supply itself and to the associated
equipment, which could affect the operation of the entire assembly. Any
observations or concerns arising from this should be reported to the
manufacturer for assessment of their potential impact on further operation.
Technical and service issues, as well as those related to periodic
inspections, please contact directly the MERAWEX Service Department or a unit
authorised by the manufacturer.
Note
The obligation to carry out regular technical inspections of fire protection
equipment results from the ordinance of the Ministry of Internal Affairs and
Administration of 7.06.2010 on the fire protection of buildings, other civil
structures and areas (Dz. U. /Journal of Laws/ No. 109, item 719, Art. 3, sec.
3).
7.3. CE marking
** 1438
MERAWEX Sp. z o.o. ul. Toruńska 8, 44-122 Gliwice, Poland 21
1438-CPR-0761
EN 54-4:1997 + AC:1999 + A1:2002 + A2:2006,
EN 12101-10:2005 + AC:2007
Power supplies for fire gates and fire automation systems.
ZUP-230V-BM-400S, ZUP-230V-BM-700S, ZUP-230V-BM-1000S, ZUP-230V-BM-700M, ZUP-
230V-BM-1000M, ZUP-230V-BM-1500L DWU / DoP : DWU-MX-19 Other technical data:
see operational manual
7.4. Handling of packaging, worn-out products and batteries
** The product packaging is made of recyclable materials (wood, paper,
cardboard, plastic).
Unnecessary packaging should be sorted and handed over to a waste collector.
This marking on the product indicates that the product should not be disposed
of with household waste at the end of its service life, but should be taken to
a collection point for electronic waste. Used batteries are hazardous waste
and must be disposed of. This will help to avoid damaging human health and the
environment through uncontrolled waste disposal.
MERAWEX Sp. z o.o.
44-122 Gliwice
ul. Toruńska 8
Phone: +48 32 23 99 400
fax +48 32 23 99 409
e-mail:merawex@merawex.com.pl
www:http://www.merawex.com.pl
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>