HITACHI RAM-8MQ Inverter-Driven Multi-Split System Air Conditioners Instruction Manual
- June 13, 2024
- Hitachi
Table of Contents
RAM-8MQ Inverter-Driven Multi-Split System Air Conditioners
Product Information:
Product Name: Inverter-Driven Multi-Split System Air
Conditioners
Models: 8HP, 10HP, 12HP, 14HP, 16HP, 18HP
Manual: Installation and Maintenance Manual
Product Usage Instructions:
1. Before installation, carefully read and understand the manual
provided. Keep the manual for future reference. 2. Ensure to hand
over this manual to the constructor of the next step and finally
let the customer keep it. 3. Important Notice: – This air
conditioner is designed for common air conditioning for people. Do
not use it for other purposes such as for food, animals, plants,
high precision machines, or work of art. – Do not install the unit
in places filled with mineral oil mist or oil spray (including
machinery oil) or where vapor is produced. Also, avoid installation
in places filled with sulfurous gas such as hot spring areas. –
Avoid installation in places where strong salty wind blows such as
coast regions or in an acid or alkaline environment. – When
installing the unit in a hospital or other facilities where
electromagnetic waves are radiated from medical equipment, ensure
that the electromagnetic wave does not directly radiate to the
electrical box, remote control cable, or remote control switch.
Keep wave generating machines such as radio and medical equipment
at least 3 meters away from the air conditioner to avoid the
influence of electromagnetic waves. – Do not install the unit where
wind directly blows on animals or plants as it could adversely
affect them. – Keep the receiver of the wireless remote controller
away from lighting equipment by at least 1 meter to avoid signal
reception failure. 4. Safety Summary: – Before installation, read
the safety section carefully to install correctly. – The manual
contains a Danger symbol indicating hazardous situations that may
result in death or serious injury if installed incorrectly. Observe
important safety messages. – During the test run after
installation, if any abnormalities are found, explain the correct
methods of usage and maintenance to the customer according to the
user’s manual. Hand over both the installation manual and user’s
manual to customers. 5. Meaning of symbols: – DANGER: Indicates a
hazardous situation that may result in death or serious injury if
not avoided. – Mandatory Symbol: Indicates instructing behavior of
general users. – Mandatory Symbol: Indicates grounding must be
performed for machines with grounding terminal. Indicates
prohibited items. 6. Electrical Works: – Assign an authorized
dealer to perform the electrical work. Improper installation may
result in electric shock. Please follow these instructions
carefully for safe and proper usage of the Inverter-Driven
Multi-Split System Air Conditioners.
Before installation, please read this manual carefully and keep it properly.
INVERTER-DRIVEN MULTI-SPLIT SYSTEM AIR CONDITIONERS
Outdoor Units
IMPORTANT:
READ AND UND ERSTAN D THIS MANUAL BEFORE USIN G THIS HEAT-PUMP AIR CONDITIONER
. KE EP THIS M A NUA L FOR FUTURE REFERENCE.
InstallationMaintenance Manual
Models
8HP
10HP
12HP
14HP
16HP
18HP
RAM-8MQ(D)
RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D)
Be sure to hand over this manual to constructor of next step and finally let the customer keep it. (Transportation and Handling) (Refrigerant Piping) (Electrical Wiring) (Test Run) (Customer)
Important Notice
z This air conditioner has been designed for common air conditioning for
people. Do not apply to other purposes such as for food, animals, plants, high
precision machines or work of art.
z Do not install the unit in the following places. It may cause fire,
deformation, corrosion or failure. Places where is filled with mineral oil
mist or oil spray (including machinery oil) or vapor is produced. Places where
is filled with sulfurous gas such as hot spring area.
z Do not install the unit in the following places, it may cause corrosion.
Places where strong salty wind blows such as coast regions. An acid or
alkaline environment.
z Pay attention to the following situations when the unit is installed in a
hospital or other facilities where electromagnetic wave is radiated from
medical equipment. Do not install the unit where the electromagnetic wave is
directly radiated to the electrical box, remote control cable or remote
control switch. To avoid the influence of electromagnetic waves via air, wave
generating machines such as radio, medical equipment must be kept at least 3
meters from air conditioner.
z Do not install the unit in the place where wind directly blows on animals or
plants. It could adversely affect the animals or plants. z Using wireless
remote controller, the receiver may fail to receive signals due to effect of
the lighting equipment. Therefore keep the receiver
away from the lighting equipment more than 1 meter as possible.
Safety Summary
z Before installation, read this section carefully in order to install
correctly.
z This manual contains ” Danger” symbol. This symbol indicates a hazardous
situation which, if installed incorrectly, it may result in death or serious
injury. Therefore, make sure to observe important messages of safety.
z While checking any abnormality during the test run after installation,
explain to customer the correct methods of usage and maintenance according to
the instructions of user’s manual. Then hand over the installation manual and
user’s manual to customers.
Meaning of symbols
DANGERIndicates a hazardous situation which, If not avoided, may result in
death or serious injury.
Mandatory Symbol: indicate instructing behavior of general users.
Mandatory Symbol: indicate grounding must be performed for
machine with grounding terminal. Indicate prohibited item.
About Electrical Works
z
z
z z
z DANGER z
z
z
Assign an authorized dealer to perform the electrical work. Please note that
if improperly performed by yourself, it may result in electric shock.
Perform electrical work according to relevant national regulations and the
installation manual. Make sure to use the exclusive circuit to avoid electric
shock or fire due to insufficient capacity of power or improper work.
Use only specified wires for wirings between units. Incorrect selection of
wires also causes fire or electric shock.
Properly fasten the terminals of wirings. Improper fastening the joint of
terminals may result in fire, electric shock or the overheated terminals.
Fix the cables securely. External forces on the terminals could lead to a
fire.
Installation of an earth leakage breaker (ELB) is necessary. If an ELB is not
installed, current leakage may occur.
When opening the service cover due to need of wiring work or inspection, make
sure to completely cut off power before work to avoid electric shock.
Perform grounding according to the grounding work instructions. Incident of
electric shock may occur if indoor and outdoor units are not grounded. The
ground wire must not be connected to gas pipe, water pipe, lighting rod and
ground wire of telephone line. If the ground wire is not properly connected,
it may result in electric shock.
About installation
z Installation must be done in accordance with this installation manual.
Improper installation may result in water leakage, electric shock or fire.
z Install the air conditioner on a foundation strong enough that it can
withstand the weight of the unit. A foundation of insufficient strength may
result in the unit falling and injury.
DANGER z Do not perform installation at locations subject to existence or
entry of flammable gas. z Do not climb or put any object on the air
conditioner to prevent injury caused by the unit falling. z In the event of
refrigerant leakage, immediately turn off the fire source (e.g. stoves), wipe
the refrigerant off the floor, open the door and windows for ventilation and
then contact the service personnel or the dealer.
66MP1373
1
z Use the adequate non-flammable refrigerant (R410A) and refrigerant oil
(Idemitsu Kosan Co.,Ltd.)(FVC68D) to the outdoor unit in refrigerant cycle.
Charging other refrigerant or refrigerant oil, oxygen, acetylene into the
refrigerant cycle may result in explosion or fire.
DANGER z This air conditioner contains high pressure gas, in any case, the
unit or any part of the unit is prohibited to be heated. It may result in
machine malfunction, even explosion or fire.
1. Common Items
(1) Confirmation of unit model
- Base unit
HP
8
Model RAM-8MQ(D)
10
12
14
16
18
RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D)
- Combination of Base Units
HP
20
22
24
26
Model HP
RAM-12MQ(D) RAM-8MQ(D)
30
RAM-10MQ(D) RAM-10MQ(D)
32
RAM-14MQ(D) RAM-8MQ(D)
34
RAM-14MQ(D) RAM-10MQ(D)
36
RAM-14MQ(D) RAM-12MQ(D)
38
Model HP
Model HP
Model
RAM-16MQ(D) RAM-14MQ(D)
— 42 RAM-16MQ(D) RAM-14MQ(D) RAM-12MQ(D) 54 RAM-18MQ(D) RAM-18MQ(D) RAM-
18MQ(D)
RAM-16MQ(D) RAM-16MQ(D)
— 44 RAM-18MQ(D) RAM-14MQ(D) RAM-12MQ(D)
RAM-12MQ(D) RAM-12MQ(D) RAM-10MQ(D)
46 RAM-18MQ(D) RAM-14MQ(D) RAM-14MQ(D)
RAM-12MQ(D) RAM-12MQ(D) RAM-12MQ(D)
48 RAM-18MQ(D) RAM-16MQ(D) RAM-14MQ(D)
RAM-16MQ(D) RAM-12MQ(D) RAM-10MQ(D)
50 RAM-18MQ(D) RAM-18MQ(D) RAM-14MQ(D)
For 20~54HP, please refer to the table above to select the combination of base units.
28 RAM-14MQ(D) RAM-14MQ(D)
40 RAM-16MQ(D) RAM-12MQ(D) RAM-12MQ(D)
52 RAM-18MQ(D) RAM-18MQ(D) RAM-16MQ(D)
(2) Combination of Indoor Unit and Outdoor Unit Please refer to the table, select outdoor unit and indoor unit number and capacity. (When the indoor unit does not fit ” Minimum Individual Operation Capacity ” in the table as shown below, It must not be connect to the outdoor unit. Please pay particular attention!)
HP
Indoor Unit
Range of
Maximum Connectable
Combination Capacity Indoor Unit Number
8
13
10
16
12
19
14
23
16 26
18
20
33
22
36
Max. 130%
24
40
26
43
28
47
30
50
32
53
34
56
36
59
38~54
64
Please refer to piping connection limit on P.9.
The Suggestion of Maximum Connectable Indoor Unit Number
8 10
16 18 20 26
32
38
2
2. Transportation and Handling
(1) Operation temperature range
Item Cooling
Air Inlet Temperature of Outdoor Unit Air Inlet Temperature of Indoor Unit (Non-room Temperature)
-5 DB 43 DB
21 DB/15 WB 32 DB/23 WB
DBDry Bulb WBWet Bulb
(2) When transporting the outdoor unit, observe the following items. Please transport the unit to the installation location under packed condition.
(3) When hanging the outdoor unit, please follow the description of the label
attached to the outdoor unit. After removing the
package, in order to avoid body damage, the unit needs protecting by
corrugated board or cloth if moving again.
When hanging outdoor unit, please do not tie the ropes on wooden base or the inside of hanging square holes.
ExampleRAM-8MQ(D)
INCORRECT
Rope Wooden Base
CORRECT
Rope SHqouleare
INCORRECT
Rope
Square
Hole
Corrugated Paper Frame Do not remove corrugated paper and plastic bands. Do
not apply any force to this place.(Both Sides)
Corrugated Paper Frame
Do not remove corrugated paper and plastic bands.
Do not apply any force to this place.(Both Sides)
Angle of ropes is more than 60°.
Rope
Plywood or splint thickness should be more than 15mm.
Wooden Base
Apply rope through the square holes.
Angle of ropes is more than 60°.
Rope
Plywood or splint thickness should be more than 15mm.
Apply rope through the square holes.
3
3. Before Installation
(1) The pressure of refrigerant R410A is 1.4 times higher than conventional
refrigerant; it is contaminated easily by moisture, oxide, oil and other
impurities. New refrigerant is adopted; therefore refrigerant oil also needs
to be changed. When installing, make sure to prevent moisture, oxide, oil,
conventional refrigerant or refrigerant oil, or other impurities from getting
into the refrigerant cycle.
The air-tight test pressure of the product is 4.15Mpa.
(2) To avoid accidental mixing of different refrigerant or different refrigerant oil, the size of the charging connectors must be changed. It is necessary to prepare the following special R410A tools before performing the installation work.
Measuring instrument or tool which is directly contact to refrigerant must be used only for refrigerant R410A.
Symbol DescriptionFor new and old type refrigerant
Only for R410A(not for R22)
Only for R407C(not for R22)
For both R410A and R407C
Interchangeability
Reason of Non-Interchangeability and Attention
Measuring Instrument and Tool
with R22
(only for new refrigerant)
Use
R407C R410A
(Strictly Required)
Pipe Cutter
Refrigerant
Pipe
Flaring Tool
Extrusion Adjustment Gauge
(not use)
Pipe Bender
Expanding Tool
Cutting Pipe Removing Burrs
To ensure the high pressure of R410A, tube, make dimension of tube larger
if using flaring for R410A. If
Flaring
for
Tubes
you continue to use existent products, shall be used
with the flaring tube adjustment gasket (1mm).
(R410A special flaring tool can be used directly in the Dimensional Control
R407C)
for Extruded Portion
if Tube after Flaring
If using the 1/2H pipe, it can not be processed. Please use the elbow welding to connect.
Bending
If using the 1/2H pipe, it can not be processed. Please use the elbow welding to connect.
Expanding Tubes
Torque Wrench Refrigerant
Pipe
R410A for12.715.88; spanner size is up 2mm; existent products can not be used.
Connection of Flare Nut
For 6.359.5319.05; spanner size is the same.
Brazing Tool Nitrogen Gas
Lubrication Oil (for Flare Surface)
Refrigerant Cylinder
Perform correct brazing work.
Brazing for Tubes
Strict control against contamination. (Blow nitrogen during brazing)
Prevention from Oxidation during Brazing
Use a synthetic oil(FVC68D) which is equivalent
to the oil used in the refrigerant cycle.
Do not use R22 with mineral oil, and products must Applying Oil to the Flared
be used the same synthetic oil.
Surface
Synthetic oil absorbs moisture quickly. Do not place
it in the humid environment.
Check refrigerant cylinder color.
(R410A:Pink)(R407C:Brown)
(Brown) (Pink) Refrigerant must be charged in a state of liquid.
(Charging in a state of gas is strictly prohibited.)
Refrigerant Charging
Vacuum Pump
Adapter for
Vacuum Drying
Vacuum Pump (prevent from reverse)
Refrigerant Manifold Valve
Change
Charging Hose
Charging Cylinder
Prohibited
The conventional ones are applicable. However, it is required to mount a
vacuum pump adapter which can prevent from reverse flow when a vacuum pump
stops.
No interchangeability is available due to higher pressure when compared with
R22. R410A connection diameter1/2 UNF R407C connection diameter7/16 UNF
Do not use conventional ones (R22) to the different refrigerant ; If used,
mineral oil will flow into the cycle and cause sludge, resulting in clogging
or compressor failure.
Please use the weight scale.
4
Vacuum Pumping
Vacuum Pumping; Vacuum Holding; Refrigerant Charging and Check of Pressures
Refrigerant Charging
Weight Scale
Refrigerant Gas Leakage Detector
The current gas leakage detector(R22) is not applicable due to different detecting method.
Measuring Instrument for Refrigerant Charging
Gas Leakage Check
(3) The piping and connection parts use the following R410A. Flare nut and the front of pipe flare size also changes as shown in the table below.
Pipe Flare Size
Pipe thickness selected
Diameter
¯6.35 ¯9.53 ¯12.7 ¯15.88 ¯19.05 ¯22.2 ¯25.4 ¯28.6 ¯31.75 ¯38.1 ¯41.3 ¯44.45
Thickness 0.8 0.8 0.8 1.0 1.0 1.0 1.0 1.0 1.1 1.35 1.20 1.55
R410A
Unitmm
Material O O O O
1/2H 1/2H 1/2H 1/2H 1/2H 1/2H 1/2H 1/2H
Diameter ¯d
¯6.35 ¯9.53 ¯12.7 ¯15.88 ¯19.05
Unitmm
Dimension
¯A
+0 -0.4
R410A ¯9.1 ¯13.2
¯16.6
¯19.7 Can not be processed
(1/2H material)
Selection of joints With the design pressure changes, the connection pipe
(elbow etc.) thickness are also changes. When using 1/2H material, the bending
and flaring can not be processed, so please follow the table below to choose
the minimum thickness that appropriate to the connecting pipe. Please note
that there are several changes in flare nut size.
Connection minimum thickness (mm)
Diameter ¯6.35 ¯9.53 ¯12.7
¯15.88 ¯19.05 ¯22.2
R410A 0.5 0.6 0.7 0.8 0.8 0.9
Diameter ¯25.4 ¯28.6 ¯31.75 ¯38.1 ¯41.3 ¯44.45
R410A 0.95 1.0 1.1 1.35 1.45 1.55
Flare Nut
Flare Nut dimension B (mm)
Diameter
¯6.35 ¯9.53 ¯12.7
Flare Nut dimension B(mm) R410A 17 22 26
Diameter
¯15.88 ¯19.05
Flare Nut dimension B(mm) R410A 29 36
5
4. Installation Work
(1) Selection of Installation Location
- Make sure the space for operation and maintenance service is secured around
the outdoor unit. 2) Install the outdoor unit where it is dry and well
ventilated. 3) Install the outdoor unit where it is in the shade or it will
not be exposed to direct sunshine or direct radiation from high
temperature heat source. 4) Install the outdoor unit where the operating sound does not affect neighbors. 5) The outlet air does not directly blow to plants or neighbor’s windows. 6) The foundation is strong enough to support the weight and withstand vibrations of the outdoor unit. 7) Do not install the outdoor unit where dust or other contamination could block the heat exchanger of the unit. 8) Do not install the outdoor unit where strong wind could blow to the unit from the air outlet side. 9) Do not install the unit inside the house. 10) Do not place flammable objects near the unit, it may result in fire. 11) Do not install the outdoor unit where there is a high concentration of oil spray, salty air or harmful gases such as sulfurous
gas. 12) Do not install the outdoor unit where the electromagnetic wave directly radiates to the electrical box. 13) To avoid the influence of electromagnetic waves, wave generating machines such as radio should be kept 3 meters from
electromagnetic wave radiator.
(2) Installation Space
- Ensure the maintenance space around the outdoor unit as shown below. The insufficient air inlet and outlet space may result in insufficient air intake, poor performance, and other problems. Please be sure to follow it for the convenience of maintenance.
Unit:mm
If the season winds blows directly, defrost time will increase.
Season winds
Air inlet
Season winds
WWiFinneddnbbcrreeeaakk
Air inlet Air inlet
Air inlet
If the wall of front side is higher than 1,500 mm, the required space is
500h2/2mm.
If the wall of rear side is higher than 500 mm, the required space is
300h1/2mm.
If there are no walls at the front and rear side, the required spaces for the
front and rear side are 500 mm and 300 mm.
If the unit is surrounded by walls, make a ventilation hole on the wall. Leave
space between the top side and wall.
- Leave the service space when outdoor unit is installed 1.Walls in 2 Directions
Unit:mm
2.Walls in 3 Directions Single Unit Installation
6
Multiple Unit Installation
3.Walls in 4 Directions Single Unit Installation Multiple Unit Installation
Unitmm
Keep the upper side open. The front side should be less than 1,500mm; air
inlet side should be less than 500mm; other sides are no limits. If the
heights are beyond the limits, add h1/2mm and h2/2mm on the front side and air
inlet side respectively. For the multiple installation, one group allows 6
outdoor units(max.).The required space between each set is at least
1m.
The walls should be partially open if the unit is surrounded by walls in four
directions. NoteIf the distance between unit and obstacles/ceilings is less
than 1,500mm or the space is closed, set up the duct on the air outlet side to
prevent the return air.
7
(3) Foundation Work Please perform this work properly. Ensure the unit does not lean, vibrate, make a noise or fall in the event of strong wind or earthquake.
-
The height of the base should be 150 mm higher than the ground level. 2) Perform adequate drainage around the foundation. 3) All foot of the outdoor unit need installing on the base. 4) Install the outdoor unit horizontally (Use a level gauge). Ensure the horizontal tolerance is within 10mm.
Unitmm -
Precautions The concrete base should be set along the foot direction as shown below. Incorrect installation may cause the foot of the outdoor unit deformation.
(4) Anchor Bolt Installation Dimensions RAM-8~12MQ(D)
RAM-14~18MQ(D)
4-38×15 Hole of Anchor Bolt
(5) Confirmation of drainage
Unitmm
4-38×15 Hole of Anchor Bolt
- When Defrosting operate, the condensation water will be discharged. Select the best area for drainage.
The drain hole position is shown below
RAM-8MQ(D)~12MQ(D)
RAM-14MQ(D)~18MQ(D)
Drain Hole (¯26) Drain Connector Position
Refrigerant Gas Piping Connection Hole (¯60)
Power Supply Connection Hole (¯52)
Circuit Control Connection Hole (¯26×2)
Refrigerant Liquid Piping Connection Hole (¯47)
Refrigerant Gas Piping Connection Hole (¯60)
8
Drain Hole (¯26) Drain Connector Position Power Supply Connection Hole (¯52)
Circuit Control Connection Hole (¯26×2)
Refrigerant Liquid Piping Connection Hole (¯47)
- Drain connector installation methods: 1.Set the washer on the upper part of drain connector. 2.According to the shape of base drain holes, insert the drain connector and turn it clockwise about 40°. 3.Drain connector is equivalent to VP20. 4.Drain pipe is field supplied.
NoteThe drain connector is installed for discharging condensation water
Convex Drain Connector
Washer
Base Drain Hole
Drain Connector
Drain Pipe (Field Supplied)
5. Refrigerant Piping
(1) Refrigerant Piping 1) Selection of refrigerant pipes 1.Please prepare
field supplied copper pipes. 2.Select the piping size as the table below.
Piping between Outdoor Unit and First Multi-kit
Gas/Liquid Pipe Size (mm)
HP
Equivalent Length100m
Equivalent Length100m
8
19.05 / 9.53
22.2 / 12.7
10
22.2 / 9.53
25.4 / 12.7
12~14
25.4 / 12.7
28.6 / 15.88
16
28.6 / 12.7
31.75 / 15.88
18~24
28.6 / 15.88
31.75 / 19.05
26~34
31.75 / 19.05
34.9 / 22.2
36~54
38.1 / 19.05
41.3 / 22.2
3.Select clean copper pipes. Be sure that there is no dust and moisture inside
of the pipes. Cut the copper pipes with a pipe cutter. Blow the inside of the
pipes with nitrogen or dry air to remove dust or foreign
materials before connecting pipes. (Do not use a saw, a grindstone or other
tool which may cause cutting powder.) Cautions for refrigerant piping
When installing pipe through the wall, secure a cap at the end of the pipe.
Do not pClOacReREthgCerTopuinpde.directly on the CORRECT
INCORRECT
CORRECT
INCORRECT
CORRECT
INCORRECT
Rain water can enter
Hole
Hole
Attach a cap or vinyl tape
Attach a cap or vinyl tape
Attach a cap or vinyl bag with rubber band.
- Refrigerant piping limitation and multi-kit 1.The order of piping connection kit is counted from the indoor unit side(as Branch Pipe 1). 2.When the maximum length of the equivalent refrigerant pipe(L1)from First Multi-kit to the indoor unit is over 100mm, the size of gas/liquid pipes from the Piping Connection Kit 1 to the First Multi-kit should be increased one size with the reducer(field-supplied). 3.The size of multi-kit between the indoor units should be the same as the size of the indoor unit pipes. 4.When the liquid piping length is longer than 15m, please use9.53 pipe(field-supplied). 5.Keep the straight line distance longer than 500mm or more after the piping connection kit. 6.The condition of refrigerant piping installation varies depending on the quantity of indoor units. 7.Due to the maximum charging of refrigerant, the total piping length should be less than 1,000m.
9
Piping Size and Multi-Kit Selection
Example of System :
The figure is an example which shows the combination of indoor and outdoor
units.
The refrigerant pipes which contain gas/ liquid pipes are shown in single
lines for simplification.
First Multi-Kit
Master (A) Slave (B) Slave (C)
PCiopninngection1Kit 1
Piping 2 Connection Kit 2
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Item
Allowable length
The number of indoor unit is The number of indoor unit
less than the recommended exceeds the recommended
maximum combined number maximum combined number
of units.
of units.
Maximum Piping Length
Actual length Equivalent length
Total length
Maximum Piping Length
Length between First Multi-kit and the furthest indoor unit
Length between each Multi-kit and Each indoor unit
Length between Piping Connection Kit 1 and the furthest outdoor unit
Maximum Height Difference
between Outdoor and Indoor Unit
If the outdoor unit is higher than indoor unit. If the indoor unit is higher than outdoor unit. Height difference between Each indoor unit Height difference between Each outdoor unit
Multi-kit and Piping
First Multi-kit
L t1000m L 290m
L 1165m L 1190m
L t300m L 240m
L 340m
L 330m
Outdoor Unit (HP)
8 10 12~14 16 18~24 26~34 36~54
L 510m
H 150m
H 140m
H 215m
H 50.1m
Gas/Liquid Piping
Diameter (¯mm)
(L 1 100m)
Gas/Liquid Piping
Diameter (¯mm)
(L 1 100m)
19.05 / 9.53 22.2 / 12.7
22.2 / 9.53 25.4 / 12.7
25.4 / 12.7 28.6 / 15.88
28.6 / 12.7 31.75 / 15.88
28.6 / 15.88 31.75 / 19.05
31.75 / 19.05 34.9 / 22.2
38.1 / 19.05 41.3 / 22.2
Multi-Kit Type
E-NP282S E-NP452S E-NP692S E-NP902S
Indoor Unit Total Capacity (kW)
Gas/Liquid Piping Diameter (¯mm)
Multi-Kit Type
Other Multi-kits
101.0 73.0~100.9 50.0~72.9 45.0~49.9 33.5~44.9 25.0~33.4 16.0~24.9
15.9
Equivalent length= Actual length+ Additional length(Elbow, Bend and Multi-Kit)
One 90°Elbow is 0.5m. One 180°Bend is 1.5m.
One Multi-Kit is 0.5m.
38.1 / 19.05 31.75 / 19.05 28.6 / 15.88
28.6 / 12.7 25.4 / 12.7 22.2 / 9.53 19.05 / 9.53
15.88 / 9.53
E-NP902S E-NP692S E-NP452S
E-NP282S
10
Piping diameter restriction between Multi-Kit and indoor units:
Indoor Unit Capacity (kW)
Piping Diameter
Gas/Liquid Piping Diameter (¯mm)
2.2~4.5
12.7 / 6.35
5.0~5.6
15.88 / 6.35
6.3~16.0
15.88 / 9.53
When piping length exceeds 15m, liquid piping diameter must change to 9.53.
Piping diameter restriction on indoor units:
Outdoor Unit
Model
RAM-8MQ(D) RAM-10MQ(D)
Gas Piping
a100m
Piping
Liquid Piping
Size
Gas Piping
a100m Liquid Piping
22.2
25.4
12.7
19.05
22.2
9.53
RAM-12MQ(D) RAM-14MQ(D) 28.6 15.88 25.4 12.7
RAM-16MQ(D) RAM-18MQ(D) 31.75 19.05 28.6 15.88
Master (A)
Slave (B)
Slave (B)
Master (A)
HP
Combination Model
Master (A) Slave (B)
Piping Connection Kit
a100m
Gas Piping
Liquid Piping
a100m
Piping Size
b
Gas Piping
Liquid Piping
Gas Piping
Liquid Piping
Gas Piping c Liquid Piping
20 10MQ(D) 10MQ(D)
22.2 9.53 22.2
20
22
12MQ(D) 14MQ(D)
8MQ(D) 8MQ(D)
E-NP692S
24 14MQ(D) 10MQ(D)
31.75
19.05
28.6
15.88
25.4
19.05
22.2
9.53
26 14MQ(D) 12MQ(D)
12.7
28
30
14MQ(D) 16MQ(D)
14MQ(D) 14MQ(D)
E-NP902S
32 16MQ(D) 16MQ(D)
34.9
22.2
31.75
19.05
28.6
25.4
28.6
12.7
11
Master (A)
Slave (B)
Slave (C)
Slave (C)
Slave (B)
Master (A)
HP
34
36
38
40
42
44
46
48
50
52
54
Combination Model
Master (A) 12MQ(D) 12MQ(D) 16MQ(D) 16MQ(D) 16MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) Slave (B) 12MQ(D) 12MQ(D) 12MQ(D) 12MQ(D) 14MQ(D) 14MQ(D) 14MQ(D) 16MQ(D) 18MQ(D) 18MQ(D) 18MQ(D) Slave (C) 10MQ(D) 12MQ(D) 10MQ(D) 12MQ(D) 12MQ(D) 12MQ(D) 14MQ(D) 14MQ(D) 14MQ(D) 16MQ(D) 18MQ(D)
Piping Connection Kit
a100m a100m
b
Gas Piping
Liquid Piping
Gas Piping
Liquid Piping
Gas Piping
Liquid Piping
Piping Size
c
Gas Piping
Liquid Piping
Gas Piping d Liquid Piping
34.9 31.75
25.4
28.6 15.88
12.7
25.4 12.7
E-NP902S×2 41.3
22.2 38.1
19.05
28.6
31.75 19.05
15.88 28.5
15.88
Gas
22.2
Piping
25.4
22.2
e
Liquid
9.53
Piping
12.7
9.53
25.4 12.7
28.6 15.88
Please follow the requirement when performing multi-kit piping. Remove the spare parts of pipes can ensure operational capacity and prevent noise.
Type
E-NP282S
E-NP452S
Gas Piping
Q’ty
1
1
12
Liquid Piping
Q’ty
Type
Gas Piping
1 E-NP692S
1 E-NP902S
Q’ty
1
1
Liquid Piping
Q’ty
1
1
(2) Caution about Outdoor Unit Installation
1.Align the outdoor units and locate large capacity Master (A) on the indoor unit side. Piping length between Piping Connection Kit 1 and each outdoor unit should be less than 10m.
HPMaster (A) Slave (B) Slave (C)
Piping LengthLA LB LC 10m
Keep the pipes straight at least 0.5m after piping connection kits.
Master (A)
Slave (B)
Slave (C)
PCiopninngection Kit
L
L
L
Mbeatxw.eLeifntODiufftedroeonrce U0n.1itm= 0.1m
Indoor UnitSide
2.Place the piping connection kit lower than the outdoor unit piping
connection. In case that the piping connection kit is placed higher than the
outdoor unit piping connection, keep 300mm (max.)
between the piping connection kit and the bottom of the outdoor unit. Also,
provide an oil trap (min.200mm) between the
piping connection kit and the outdoor unit.
Base
Bottomof Outdoor Unit IndoorUnitSide
Master (A)
Slave (B)
Slave (C)
M3a0x0.m3m00mm M30a0x.m3m00mm
M30a0x.m3m00mm
Indoor Unit Side
OilTrap OilTrap OilTrap M20in0.m2m00mm M20in0.m2m00mm M20in0.m2m00mm
13
3.Piping length between piping connection kit (at outdoor unit side) and
outdoor unit should be less than 2m. In case that the piping length between
outdoor units exceeds 2m, an oil trap (min.200mm) should be provided
for the gas pipe so that accumulation of refrigerant oil may not occur.
IndoorUnitSide
Master (A)
Slave (B)
Slave (C)
IndoorUnitSide
Master
(A) Oil Trap 2M00inm.m200mm
Slave (B)
Oil Trap 2M0i0nm. m200mm
Slave (C)
Less2mthan2m
Les2smthan2m
Les2smthan2m
Les2smthan 2m
2m o2rmmore
2m2mor more
4.Ensure the direction of outdoor unit pipes is horizontal or with downward gradient towards the indoor unit side to avoid accumulating refrigerant oil in the pipe.
IndoorUnit Side
Master (A)
Slave (B)
Slave (C)
Indoor Unit Side
Master (A)
Slave (B)
Slave (C)
Refrigerantoil accumulates in the pipe.
5.For maintenance, if the pipe is placed in front of the outdoor unit, secure
at least 500mm between the outdoor units and the piping connection kits.
Master Slave Slave ((A) ) ((B) ) ((C) )
550000mmmm
IndoorUnitSide
6.Place the piping connection kits horizontally (within ±15°).
15Within±15°
7.Piping connection of outdoor unit, please refer to the following figure.
Front or Rear SOiudtdeooPr11i/p/33ing Connection
Outdoor Unit
Outdoor 1/3 Piping Connection
Kit 1 (Gas)
Gas Piping (Field Supplied)
Gas Line Refrigerant Piping
Connection ()
Piping Connector (L-Shape)
Outdoor 22//33
Piping Connection Kit 2 (Gas)
Liquid Piping ((Field Supplied)
Piping Connector (L-Shape)
Piping Connection Kit 1 (Liquid)
Outdoor 33//33
Liquid Line Refrigerant
PipingConnection
Piping Connector (L-Shape)
Liquid Piping (Field Supplied)
Gas Piping (Field Supplied)
14
Piping Connector (L-Shape)
Piping Connection Kit 2 (Liquid)
Liquid Piping (Field Supplied)
Gas Piping (Field Supplied)
Downward Piping Connection
Outdoor 1/3
Piping Connection Kit 1 (Gas)
Outdoor 2/3
Gas Piping (Field Supplied)
Liquid Piping (Field Supplied)
Piping Connection Kit 1 (Liquid)
Piping Connector (Z-Shape)
Outdoor33//33
Piping Connector (Z-Shape)
Piping Connector (L-Shape)
Piping C2o(nnection) Kit 2 (Gas)
Piping Connector (L-Shape)
PKiitpi2ng(LCiq2ou(nidn)ection)
Gas Piping (Field Supplied)
(3) Pipe Connection Position
Liquid Piping (Field Supplied)
GCoansnLeincteioRnefrigerantPip(ing)
D C 100
D C 100
Model
RAM-8MQ(D) RAM-10MQ(D) RAM-12MQ(D) RAM-14MQ(D) RAM-16MQ(D) RAM-18MQ(D)
Liquid Line Refrigerant
PipingConnection 145 245
A A B B
Unit:mm
A
B
C
D
Gas Line Refrigerant Liquid Line Refrigerant Gas Line Refrigerant Liquid Line Refrigerant
Piping Connection Piping Connection
Piping Connection
Piping Connection
320
150
155
335 315
170
175
15
(4) Setting of the multi-kit pipe
It is necessary to use optional multi-kit to prevent unit’s insufficient
capacity due to the uneven distribution of
the refrigerant. Do not use connectors to connect. 1) The installation of the
main branch as shown below
Main Pipe (The pipe between each multi-kit or the pipe between the outdoor units and the first multi-kit)
Main BranchOne multi-kit is connected with other multi-kits connected with more than one indoor unit.
Setting ConditionThe branches extending to third are allowed, but main branches can only extend to second.
Piping length within 40 m between the first branch and the indoor units :
Best installationsituation
Third3Branch
Outdoor First B1ranch
Second B2ranch Seco2nd Main Branch
FirstMa1inBranch
Allowing installation situation
Outdoor
Second2Branch Third3Branch
First 1Branch
First M1ain Branch
Second Main Branch 2
Third 3Branch
Outdoor First1Branch
Second2 Branch
Incorrect
First Mai1n Branch Secon2dMainBranch
Outdoor
SecondB2ranch ThirdBr3anch Fourt4h Branch
First1Branch
FirstM1ainBranch
Second 2MainBranch Incorrect
Piping length in excess of 40 m between the first branch and the indoor units
Only one main branch is allowed, and total indoor unit capacity should be in
the range of 40% to 60% for each route after the first main branch.
Allowing installation situation
Pipe Length 40m~90m
Outdoor
First Main Branch
71Type
71Type
Allowing installation situation
Allowing installation situation
71Type
y
71Type
Indoor Unit Total Capacity 50%
Outdoor
First Branch
71Type 71Type
Indoor Unit Total Capacity 50%
First Main Branch
71Type 140Type
71Type
71Type 140Type
140Type
Indoor Unit Total Capacity 33%
Indoor Unit Total Capacity 67%
Pipe Length 40m~90m Outdoor Second M2ain Branch Third3Branch
First Main Branch
16
- Fixed the multi-kit piping 1.Horizontal The branch pipe must be set in the same plane.
Keep the outdoor unit pipes straight at least 0.5m after piping connection kits.
Up
Up
Straight Pipe
0.5m Above Up
In the same Horizon Plane
Down
Down
2.Vertical
Upward BranchKeep the outdoor unit pipes straight at least 0.5m after piping connection kits.
Downward BranchKeep the outdoor unit pipes straight at least 0.5m after piping connection kits.
Up
Up
Straight Pipe 0.50m.5Ambove
Down
Upward Branch
Straight Pipe 00.5.5mmAbove
Down
Downward Branch
TiltAngle W15ithin 15°
15
Tilt Angle (A Direction)
(5) Refrigerant piping fixation methods:
Connect the indoor unit and the outdoor unit with field-supplied refrigerant
piping. Fix the refrigerant piping at certain points and prevent the
refrigerant piping from touching the weak part of the building such as wall,
ceiling, etc.( If touched, abnormal sound may occur due to the vibration of
the piping, especially in the case of short length piping.)
(Fixation[Methods Ex]ample) Outdoor Unit
Piping Fixation Interval
Pipe Size 22.2 25.4
Max. Interval 1.0m
1.5m
Indoor Unit
(6) Piping Direction
- The pipes are available to connect in five directions (front, rear, left,
right or bottom side) from bottom base. 2) Please weld the flange combination
and connection pipe in advance, and then lock with the gas stop valve. 3) In
order to prevent rainwater and insects from entering into the unit, please
fill the gap between piping hole and pipes with
insulator.
Right Piping (Rig(ht Side) )
Front Piping (F(rontSide))
Left Piping ((LeftSide))
Base
Bottom Piping (Bo(ttomSide))
Rear Piping (R(earSide))
Gas Stop Valve Set
Discard
Original Washer
Closed Flange
Bolt 2 Piece Spring Washer 2 Piece Flat Washer 2 Piece
Attached Washer
Flange Combination
Flat Washer 2 Piece Spring Washer 2 Piece Flare Nut
17
(7) Refrigerant Piping Work
- Confirm that the stop valves of outdoor unit are closed. 2) Connect the
indoor unit and the outdoor unit with field-supplied refrigerant piping. Fix
the refrigerant piping at certain points
and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc.( If touched, abnormal sound may occur due to the vibration of the piping, especially short length piping.) 3) Please connect the piping between indoor and outdoor unit. When tightening the joints of piping, coat inside and outside of flare piping with a layer of refrigerant oil [Field-supplied (Idemitsu Kosan Co., Ltd. Synthetic oil”FVC68D”)], and use double spanner to tighten with specific tightening torque. After tightened, please confirm the gas leakage once more. During brazing, please blow nitrogen into the piping. 4) Before air-tight test, please re-tighten the gas line stop valve spindle. (a) After flange connection, open the gas line stop valve cap and tighten the spindle with 20 ~ 25 N · m of torque. (b) Removing the valve cap will cause voice due to slight gas leakage, but the condition is normal. - Please perform the air-tight test. Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the liquid line and the gas line stop valves. Perform the air-tight test. Apply gas pressure of 4.15MPa. 6) Insulate the unions and flare-nuts at the piping connections completely. Insulate the liquid piping and gas piping completely to avoid decreasing performance and dewing on the surface of the pipe.
Required Torque
Piping Size (mm) ¯6.35(1/4″)
Tightening Torque 20Nm
Do not apply the double spanner work here. (Refrigerant leakage will occur)
¯9.53(3/8″)
40Nm
¯12.7(1/2″)
60Nm
¯15.88(5/8″) ¯19.05(3/4″)
80Nm 100Nm
Double spanner work Stop valve tightening work
Flange With Bolt
53~75 Nm
(8) Vacuum Work
About the details of stop valve operation, please refer to the nameplate inside service cover.
- Connect a manifold gauge to the check joints at the both sides. Continue vacuum pumping work until the pressure
reaches-0.1MPa or lower for one to two hours. After vacuum pumping work, shut the manifold valve, stop the vacuum
pump and leave it for one hour. Check to ensure that the pressure in the manifold gauge does not increase.
- Because check joints and flare nut cannot be connected, please use the charging hoses. After the work, please tighten the
flare nut with 15~16N · m torque.
Use special tools and measuring instruments only for the new refrigerant R410A. If vacuum degree -0.1MPa is not available, it is considered that leakage and moisture exist.
- Vacuum drying determination example
Vacuum Degree Vacuum Degree Vacuum Degree
Outside air temperature 23°C
After the vacuum pump stop, the vacuum degree rebound phenomenon Vacuum pump
stop
Outside air temperature 20°C
System without moisture
System with moisture
System with
System with
moisture, outside air
moisture, outside air
(
temperature 20°C
temperature 10°C
Vacuum Time (min) Figure1Vacuum Time and Vacuum Degree
Vacuum Time (min)
The system without moisture is not affected by outside air temperature.
Vacuum Time (min)
Figure2 Vacuum time and degree with moisture in system
Figure3Outside air temperature vacuum time and degree
Please implement vacuum drying determination, to confirm whether moisture exists within the system. If moisture is present, please extend the vacuum time or install the drying filter until no moisture is present within the system. Be sure to do this work, otherwise the unit may be damage easily and difficult to handle.
18
(9) The Additional Refrigerant
Outdoor unit has been filled with refrigerant, but still need to add an
appropriate amount of refrigerant based on the length of the pipe. Please
follow the steps below to calculate the additional amount of refrigerant, and
fill the outdoor unit with it.
1. Calculation of Additional Refrigerant W (kg)
No. Refrigerant
1
W1
Content
Additional Amount of Refrigerant for Liquid Pipe W1(kg)
Pipe Size
Pipe Length (m)
The Amount of Refrigerant Per Meter
22.2
m
x0.39=
19.05 15.88
m
x0.28=
m
x0.19=
12.7
m
x0.12=
9.53
m
x0.06=
6.35
m
x0.03=
Total Amount of Additional Refrigerant for Liquid Pipe
Additional Amount of Refrigerant W1(kg)
Additional Refrigerant (kg) kg
Additional Amount of Refrigerant for Indoor Unit W2(kg)
8HP, 10HP each indoor unit needs addition 1 kg of refrigerant.
There is no addition of refrigerant for the unit less than 8HP.
2
W2
kg
The Total Number of 8HP, 10HP Indoor Unit
Additional Amount of Refrigerant W2(kg)
x1.0kg/unit =
Calculation of Indoor Unit Connection Capacity Ratio
(Indoor Unit Total Capacity / Outdoor Unit Capacity)
3
W3
Condition Connection Capacity Ratio 100%
Additional Amount of Refrigerant W3(kg) 0.0kg
kg
Connection Capacity Ratio 100 ~ 115%
0.5kg
Connection Capacity Ratio 116 ~ 130%
1.0kg
4
W
Additional Amount of Refrigerant W(kg)(W1W2W3)
kg
2. Additional Refrigerant Filling Amount Records
Please refer to the following formula to calculate the total charges of system
Total charges of system W W0
W Wo = 100 kg
Note: W0 : Factory refrigerant charging weight.
Additional Refrigerant: W
kg
System Refrigerant:
kg
Additional Refrigerant Date:
/
/
Outdoor Unit
RAM-8,10MQ(D) RAM-12MQ(D)
Max. Additional Ref. Charge Quantity
28.0
36.0
Ref. Charge Amount of O.U Before Shipment (W0) kg
Model
W0 Outdoor Unit Ref. Charge(Kg)
RAM-8~10MQ(D)
6.5
RAM-12MQ(D)
7.5
RAM-14MQ(D) 9.0
RAM-16MQ(D)
RAM-18MQ(D)
10.5
Note: W0 is outdoor unit ref. charge before shipment. In case of the
combination of the base unit, calculate
the total ref. charge before shipment of the outdoor units to be combined.
RAM-14,16MQ(D)
40.0
RAM-18MQ(D), 20~24HP
51.0
26~54HP
63.0
19
- Fully open the gas line stop valve.
Outdoor Unit
- After cooling operation starts, connect the gauge manifold
using charging hoses with a refrigerant charging cylinder
Liquid Line Stop Valve
to the check joints of the liquid line stop valve to charge
refrigerant. (Refrigerant charging quantity error tolerance: Gas Line Stop Valve
±0.5kg around.) In the meantime, the liquid line stop valve
is slightly open.
- Fully open the liquid line stop valve after completing
refrigerant charge.
- Please be sure to perform the air-tight test.
Excess or insufficient additional refrigerant will result in compressor failure or other abnormal conditions, be sure to charge refrigerant according to the calculated values.
Gas Piping Liquid Piping
Manifold Gauge
Nitrogen Bottle (Use for Brazing and Air-Tight Test)
Vacuum Pump
Refrigerant Cylinder (R410A)
Weight Scale
Pipe connection part union and flare nut, be sure to do insulation process.
Indoor Unit
Indoor Unit
Liquid piping must be insulated. (To prevent poor performance and low pressure pipe surfaces condensation.)
Be sure to check the refrigerant leakage. If a large amount of
refrigerant leaks, it will cause the following phenomena 1. Lack of oxygen. 2.
Harmful gases would occur if a fire was being used in the
room.
5) The check joints on the accumulator is used to fill refrigeration oil, do
not use for other purposes.
Branch Pipe Thermal Insulation Material Wrapping
Refrigerant Piping Work Diagram
(10) Caution of The Refrigerant Leakage
When an air conditioner is installed in a room, in case of refrigerant
leakage, refrigerant concentration must not exceed the maximum permissible
concentration. The products use non-flammable, non-toxic safe refrigerant
R410A. If leakage occurs and gas fills a room, it may cause
suffocation. Especially for multiple indoor units and outdoor units with long-
distance piping connection, the amount of refrigerant is more than individual
air-conditioner. So make sure the indoor unit installed in the room, even in
case of refrigerant leakage, the refrigerant concentration should never exceed
the maximum permissible concentration.
Please calculate the refrigerant concentration by the following formula
R410A( (0.3k / )
The total amount of charged refrigerant (kg)
Room space for each indoor unit (m3)
Maximum permissible concentration (kg / m3)
If a room’s refrigerant concentration is more than the maximum permissible
concentration and the air conditioner still need
to be installed, please choose a treatment method according to the following
1.Set refrigerant leakage detector alarm and link it to mechanical ventilation
devices. (See below) (Cooling capacity per ton should be more than 0.4 m3/min
ventilation capacity. Cooling capacity is shown in following table according
to the outdoor unit capacity.)
2.Set the effective ventilation outlet between adjacent rooms (The outlet area
need to be more than 0.15% floor area on the upper and lower of the door), so
that the leakage of refrigerant concentration can drop less than the maximum
permissible concentration.
Example
The total amount of refrigerant within the system: 30kg
Refrigerant Pipe
Ventilation Outlet
Outdoor Indoor
Small Room Medium Room
Large Room
mechanical ventilation devicesrefrigerant leakage detector alarms devices
(Note1) Whether it is a large room, medium room, small room or tiny small
room, ( 1)theamountofrefrigerant leakage is all 30kg. 20kg
(Note2) The concentration must not exceed the maximum permissible
concentration 0.3kg / m3.
New refrigerant R410A product notes: Since R410A is a non-azeotropic
refrigerant, when leakage occurs, the proportion of mixture will change. Do
not charge new refrigerant directly; the whole system must be re-processed.
CCoooolilningg Capacity OOutudtodooroUr nit Capacit(yton) CapaUcnitiyt (HP) R410RA410A
8~12
4.11
14~16
6.48
18
6.54
20
8.22
22~26
10.59
28~32
12.96
24
13.02
26
13.08
28~40
14.70
42
14.76
44~46
17.13
48
17.19
50~52
19.56
54
19.62
20
6. Electrical Wiring
CAUTION: All field wiring and electrical components must comply with local
codes.
(1) Wiring Capacity 1) The indoor and outdoor unit transmission cable is non-
polar. 2) Please note that the type of earth leakage breaker required is
“high-speed type” (active time less than 0.1 sec.). 3) The current breaker and
manual switch around the unit installed must be set up together with
individual earth leakage breaker. 4) Outdoor unit power supply specification
is 3230V / 380V 60Hz. 5) For 3380V 4 wire type models, it is prohibited to
switch on if N phase is not connected 6) Wiring capacity, please refer to the
following table.
Transmission Cable (non-polar)
Outdoor
Indoor
Indoor
Item
Model
RAM-8MQ RAM-10MQ RAM-12MQ RAM-14MQ RAM-16MQ RAM-18MQ RAM-8MQD RAM-10MQD RAM-
12MQD RAM-14MQD RAM-16MQD RAM-18MQD
Power Supply
3 60Hz
ELB(Earth Leakage Breaker)
Power Switch Power
Maximum
Current Number of
(A)
Poles
Rating Sensitivity Current (mA)
Rating Switch Fuse Supply
Current (A)
Capacity Capacity
(A)
(A)
Size (mm2)
24
40
30
60
35
8
29
50
Earth Wire Size (mm2)
3.5
Transmission Cable Size
40
230V
3
49
55
59
15
17
23
380V
4
28
31
75
50
14
2-Core
100
100
5.5
Shielded
100
60
22
Twist Pair
Cable 0.75(mm2)
30
30
20
5.5 2.0 Total Length
30
40
30
8
Below 1000m
50
60
3.5
45
14
34
100
60
Note: (1) Please refer to the table above to select earth leakage breaker. (2) When installing earth leakage breaker, if power supply is 380V, 34 wire must be used.
AC 34W 380V 60Hz
AC 3
230V 60Hz
Earth Leakage Breaker Fuse Main Switch Outdoor Unit Power source Cord Outdoor
Unit Earth Wire Transmission Cable (O.U~I.U) Transmission Cable (O.U~O.U)
Indoor Unit Power source Cord Indoor Unit Earth Wire
Indoor Side
Slave (C)
Slave (B)
Master (A)
Indoor AC 1 220V 60Hz
Indoor
21
(2) Wiring Instruction
The power source cord and transmission cable wiring, please follow the
following instruction to implement.
- The outdoor unit’s power source cord must be wired separately, and each outdoor unit must have individual high-speed type earth leakage breaker (ELB) and the power switch.
- Connect the power supply wiring to each indoor unit group which is connected to the same outdoor unit. And install individual earth leakage breaker (ELB) and the power switch to each indoor unit group.
- The transmission cable must be connected to the unit of the same refrigerant cycle. If refrigerant piping and the transmission cable connected with a different refrigeration cycle, abnormality will occur.
- The transmission cable between indoor and outdoor units and the transmission cable between indoor units (DC5V), use twist-pair cable with shield over 0.75mm2. Additionally, the total length must be less than 1000m.
- The 2-core wire should be used for the transmission cable of the connection. (Do not use 3-core wire or over.)
Wiring Example < 338800VV6600HHzz>
Ma1st/e3r (A() )
TB1 LLL N 1 234
Slav2e/3(B)()
TB1
LLL N 1 234
MainSwitch
Fuse
Earth LeakageBreaker 3 4W 380V
ELB MainSwitch
Fuse
Earth LeakageBreaker ELB
3 4W 380V
MainSwitch
Fuse Earth LeakageBreaker ELB
1 230V
Earth Wire
Electric Box
LL N
NO.00Indoor Unit
Electric Box
LL N
NO.11Indoor Unit
Controller Wire
Remote Controller
Controller Wire Remote Controller
Earth Wire
TB Terminal Board PCB PCBoard
Field Wiring Transmission cable of thDeCco5nVnection DC 5V Field Supply Option
Mas1te/r3(A())
TB1
RST
1 234
Slav2e/(3B)()
TB1
RST
1 234
MainSwitch
Fuse
Earth LeakageBreaker 3 230V
ELB MainSwitch
Fuse
Earth LeakageBreaker ELB
3 230V
MainSwitch
Fuse
Earth LeakageBreaker ELB 1 230V
Earth Wire
Electric Box
LL N
NO.00Indoor Unit
Electric Box
LL N
NO.11IndoorUnit
Controller Wire Remote Controller
Controller Wire Remote Controller
Earth Wire
TB Terminal Board PCB PCBoard
Field Wiring Transmission cable of thDe Cco5nVnection DC 5V Field Supply
Option
22
- Check the capacity of the electrical wires. If the power source capacity is too low, the system cannot be started due to the voltage drop.
- If the indoor and outdoor unit is not grounded it may cause electric shock and other accidents, be sure to implement grounding. The earth wiring work under the condition of 100(max.) ground resistance should be performed by qualified person.
- To prevent electric shock accidents, in the electrical wiring, maintenance and other operations before opening the services cover, please turn off power source before implementation.
Gas Piping
Liquid Piping
Power SupplyWire
Transmission Wire
tPeimpipnegrtahteurrme aglaisnspuiplaintigonofmthaetehrieaal,tPrleesaissetaunst espceacnifwiciathtisotnanpdrohdiugchts.
- The wiring connection method of indoor and outdoor units
No.0 Ref. Cycle System
Master (A)
TB1
TB2
LLL
1234
Slave (B)
TB1
TB2
LLL
1234
No.1 Ref. Cycle System
Master (A)
TB1
TB2
LLL
1234
Slave (B)
TB1
LLL
1234
Master Master H-LINK II Transmission Cable
Master Slave Transmission Master Indoor H-LINK II Cable Transmission Cable
LL N No.0
Indoor
LL N No.1
Indoor
LL N No.2
Indoor
LL N No.0
Indoor
LL N No.1
Indoor
- Treatment that 230V (or 380V) power source cord and outdoor unit terminal board are wrong connected When the outdoor unit terminal board and 230V (or 380V) power source cord are wrong connected, transmission circuit fuse on the PC board will be cut off. Therefore, make the terminal board wiring correct and set the DSW10 Pin.2 switch on the PC board to “ON”. It can restore the circuit that has been cut off. ( If the 230V (or 380V) in the terminal board are wrong connected again , the PC board will break.)
Outdoor Unit PC Board
Transmission Cable (DC 5V) AC 230V / 380V
AC 230V / 380V Transmission Cable (DC 5V)
23
- Wire connection port
When the power supply is 380V, connect the power supply to TB1 of L1, L2, L3 and N; When the power supply is 230V, connect the power supply to TB1 of R, S, T, and the earth wire should be fastened on the power supply box. Please connect transmission cable between outdoor and indoor unit to the terminal 1 and 2 of TB2. If there is other connection wiring between the outdoor units in the same refrigerant system, please connect them to terminal 3 and 4.
For terminal board tightening torque, please refer the following table:
Size
Tightening Torque (N-m)
M4
1.0-1.3
M5
2.0-2.4
M6
4.0-5.0
M8
9.0-11.0
M10
18.0-23.0
Completely seal the conduit tube after wiring to avoid entering water.
Example:
Transmission Cable Terminal Board
PPCCB1 1 TTBB2 2
TTBB1 1
Clamp
Transmission Cable of the Connection between Outdoor and Indoor Unit
Earth Wire
Transmission Cable of the Connection between Outdoor Units
Electric Box
Power Supply Terminal Board
Earth Wire Terminal
Earth Wire
Insulation Sleeve
Clamp
Power Supply Transmission Cable of the Connection
Power Supply Connection Port 52
Power Supply Connection Port 52
Transmission Cable Connection Port 26
Power Supply Connection Port 52
Transmission Cable Connection Port 26
24
7. Dip Switch (DSW) Setting of Outdoor Unit
TURN OFF all power sources before setting. Without turning OFF, the switches
do not work and the contents of the setting are invalid. ( The mark of
indicates the position of dip switches.)
Dip Switch Location
Button Switch For Checking
Refrigerant Cycle System Setting
Setting is required
Factory Setting
Setting Position
Manual Defrost
Enter For Checking
For Checking
Capacity Setting
No setting is Each model has been set in accordance required with the
following table.
8MQ(D)
10MQ(D)
12MQ(D)
Tens Digit
Units Digit
For each refrigerant cycle’s outdoor unit, the machine set serial number No. 0, No. 1, No. 2 , etc. (Factory set serial number No. 0)
Test Operation, maintenance Setting is Setting of the outdoor unit test operation required
Factory Setting
Cooling Test Operation
14MQ(D)
16MQ(D)
18MQ(D)
Emergency, test Operation, maintenance
No setting is When setting the following items, please required set the
following PIN to “ON”.
Factory Setting
Compressor Is Forced To Stop
Setting IteSmetsting No.1 Compressor No Operation No.2 Compressor No Operation The Amount of Refrigerant Determination
Pin No. 1 2 4
Outdoor Unit No. Setting
Setting is required
Combination Unit
Master (A1) /3
Slave (B)2/3
Slave (C3)/3
Field Setting
Caution When the outdoor unit is a combination unit, please be sure to do this
setting.
No setting is required
Power Supply Voltage
No setting is required
230V Factory set voltage 230V 380V Factory set voltage 380V
230V
380V
25
Transmission Using
Setting is required
End Terminal Resistance Release Setting
Factory Setting
End Terminal Resistance Is Released
If the transmission circuit fuse is short circuited, please set No.2 Pin to “ON”.
(1) Implementation the H-LINKII connection, need to setting refrigerant cycle
number (only outdoor unit(master)) and end terminal resistance.(outdoor
unit(slave) no need setting)
Setting of refrigerant cycle number
The same refrigerant system outdoor unit and indoor unit must be set to the
same refrigerant system number for the outdoor unit and the indoor unit as
shown below.
Dip Switch
Tens Digit
Units Digit Setting Position
Example: No. 25 of the refrigerant system setting example
Tens Digit
Units Digit
Use flat-blade screwdriver to set.
Outdoor Unit
Indoor Unit
Note(1) DSW and RSW switch the factory setting are “0”.
(2) The maximum setting number is “63”.(0 ~ 63,
Total 64 Sets)
(2) Setting of end terminal resistance (PCB of outdoor unit)
The unit before leaving the factory, No. 1 pin of DSW 10 is set at the “ON” side. In the case that the outdoor units quantity in
the same H-link or H-link ll is 2 or more, set No. 1 pin of DSW 10 at the “OFF” side from the 2’nd unit. Mean that the number
of end terminal resistance required only one. If only one outdoor unit is used, no setting is required.
End Terminal Resistance Setting Method (DSW 10)
Factory Setting
DSW10 End Terminal Resistance Is Released
Outdoor
Outdoor
Outdoor
Outdoor
Master (A) Slave (B) Slave (C)
Transmission Cable (H -LINK II )
Transmission Cable (H-LINK II )
Master (A) Slave (B)
Transmission Cable (H-LINK II )
Indoor
Indoor
Indoor
Indoor
26
8. Test Run
Before Test Run
Before test run, please re-confirm the installation whether there are problems, also confirm the following points. In addition, please confirm it with the installation manual attached to the outdoor unit.
- Refrigerant piping and the transmission cable if connected with a different
refrigerant cycle, abnormalities will occur. 2) Please use the 500V electrical
resistance tester to confirm the electrical parts between terminals and earth
electrical
resistance must be more than 1M. If not, the electrical part is not well insulated, please do not operate the unit. (Do not supply power to the transmission wiring of terminal No.) 3) If the power supply wiring phase is in error, the unit will not be able to run, and the remote control will display abnormal
code 05 . At this time, according to the electrical box attention nameplates, check the primary side of the phase and
Implement the phase replacement work. Ensure the power supply is cut off when performing the work above. 4) Has the oil heater of the outdoor unit been powered. (Before using, please turn on the power for more than 12 hours.)
Test Run
When installation is completed, perform test run according to the following
procedure, and make sure that no abnormality
exists, then hand over the system to the customer.
- Outdoor unit the gas stop valve and the liquid stop valve, make sure full open state.
- Perform the test run of the indoor units one by one in order. Make sure that electrical wiring and the refrigerant piping are correctly connected. (When operating more than one indoor unit, the consistency could not be checked.)
- Please follow the following procedure to perform test run, and make sure that no abnormality exists.
1.Press the “MODE” and the “CHECK” buttons together for more than 3 seconds.
The “TEST RUN” and the counting
number of the connected units are indicated on the remote control switch.
When cooling operation test run, it should be at room temperature DB 21°C, WB
15.5°C, outside air temperature DB
-5°C or more. (Outside air temperature below DB -5°C, air conditioner can not be operated.)
Using a remote controller to operate more than one indoor unit, check the
connected number of indoor unit is indicated
on LCD. If no indication appears or the number of the units indicated is
smaller than the actual number of the units, some abnormalities exist, please
confirm it again.
Press the “MODE” button again to set the desired mode of operation.
2.Press “RUN/STOP” switch.
The “TEST RUN” operation will be started. (The 2 hours OFF-TIMER will be set
automatically, “OFF-TIMER” and “2HR”
will indicated on LCD.)
3.To end the test run, wait for 2 hours or push “RUN/STOP” button again.
Number of the Unit 0
1
2
3
4
…
10
11
…
63
Setting Timer
Display Left Two Digit
01 02
03
04
05
…
11
12
…
64
Ref. Cycle NO. 0
1
2
3
4
…
10
11
…
63
Setting Timer
01 02 Display Right Two
Digit
03
04
05
…
11
12
…
64
NoteAfter the product stops operation, in order to recover the piping refrigerant to the outdoor unit, the compressor
continues to operate a period of time (most about 10 minutes). The same as in
the test run, it is not the product failure or abnormal.
During test run, the protection device will be activated by some abnormality,
the controller’s operation indicator will blink,
display “Alarm” (abnormality), while the setting temperature display will show
alarm code.
Setting temperature and setting timer display: Setting Timer Display
Setting Temperature Display
At this time, please refer
to page 25 of the alarm code
23
Abnormality
Occurred SettingTemperature
to confirm the leading cause and treatment. If it is unable to handle, please contact maintenance staff for assistance.
01
Abnormality IndoorUnit
F
(Display in s(equence))
01
01
Abnormality Indoor Unit
Refrigerant CycleCont(eAnltaormf ACbondoerm) ality
Total Number of IndoorUnitsin the
01 SAbanmoermRaelIfnridgoeorarnUt nictycle With the
Unit Ty(pe (Unit Code))
27
Alarm Code
Code Category
Content of Abnormality
Leading Cause
01
Indoor Unit
Activation of protection device (Float switch)
Activation of float switch (High water level in drain pan, abnormality of drain pipe, float switch or drain pan)
02
Outdoor Unit
Activation of protection device (High pressure cut)
Activation of PSH (Pipe clogging, excessive refrigerant, inert gas mixing)
03
Abnormality between indoor and outdoor units
Incorrect wiring, loose terminals, disconnected wire, blowout of fuse, outdoor unit power off
04
Transmission
Abnormality between outdoor PCB
inverter
PCB
and
Abnormality between fan controller and outdoor PCB
Inverter PCB – outdoor PCB transmission failure (Loose connector, broken wire, blowout of fuse) Fan controller – outdoor PCB transmission failure (Loose connector, broken wire, blowout of fuse)
05 Supply Phase Abnormal power source phases
Incorrect power source, connected to reversed phase, open-phase
06
Abnormal inverter voltage
Voltage
Abnormal fan controller voltage
Outdoor voltage drop, insufficient power capacity
07
Decrease in discharge gas superheat
Cycle
08
Increase in discharge gas temperature
Excessive refrigerant charge, failure of thermistor, incorrect wiring,
incorrect
piping connection, expansion valve locked in open position (loose connector)
Insufficient refrigerant charge, pipe clogging, failure of thermistor,
incorrect wiring, incorrect piping connection, expansion valve locked in
closed position (loose connector)
0A Transmission Abnormality between outdoor units
Incorrect wiring, broken wire, loose terminals
0b
Incorrect outdoor unit address setting
Outdoor Unit
0C
Incorrect outdoor main unit setting
Duplication of address setting for outdoor units (slave units) in the same refrigerant cycle Two (or more) outdoor units set as “master unit” exist in the same refrigerant cycle.
11
Abnormal inlet air thermistor
12 Indoor Unit Abnormal outlet air thermistor
13
Sensor Abnormal freeze protection thermistor
Incorrect wiring, disconnected wire, broken wire, short circuit
14
Abnormal gas piping thermistor
19 Fan Motor Activation of protection device for indoor fan Fan motor overheat, locked
21
Abnormal high pressure sensor
22
Abnormal outdoor air thermistor
23 24
Abnormal discharge gas thermistor on top of
Sensor on compressor Outdoor Unit Abnormal heat exchanger liquid pipe
Incorrect wiring, disconnected wire, broken wire, short circuit
thermistor
25
Abnormal heat exchanger gas pipe thermistor
29
Abnormal low pressure sensor
31
Incorrect capacity setting of outdoor and indoor units
Incorrect capacity setting of combination, excessive or insufficient indoor unit total capacity.
35
Incorrect setting of indoor unit no.
System
36
Incorrect indoor unit combination
Duplication of indoor unit No. in the same refrigerant cycle Indoor unit designed for R22(old models)
38
Abnormality of protective circuit in outdoor Failure of protection detecting device
unit
(incorrect wiring of outdoor PCB)
39
Compressor
Abnormality of running current at constant speed compressor
Overcurrent, blowout of fuse, current sensor failure, instantaneous power failure, voltage drop, abnormal power supply
3A
Abnormality of outdoor unit capacity
Outdoor unit capacity > 54hp
3b
Incorrect setting of outdoor unit models Outdoor Unit combination or voltage
Incorrect setting of master and slave unit(s) combination or voltage
3d
Abnormal transmission between main and sub unit(s)
Incorrect wiring, disconnected wire, broken wire, PCB failure
43
Activation of pressure ratio decrease protection device
Bad compression (compressor, inverter failure)
44
Activation device
of
low
pressure
increase
protection
Overload
at
cooling,
expansion
valve
locked
(loose
connector)
45
Protection Device
Activation of high pressure increase protection device
Activation of low pressure decrease
47
protection device (vacuum operation
protection)
Overload operation (clogging, short-pass), pipe clogging, excessive
refrigerant, inert gas mixing
Insufficient refrigerant, refrigerant piping clogging, expansion valve locked
in closed position (loose connector)
48
Activation of inverter overcurrent protection device
Overload operation, compressor failure
51
Abnormality of inverter current sensor
Current sensor failure(inverter PCB)
53
Inverter Power module protection activation.
54
Abnormality of inverter fin temperature
55
Inverter failure
57
Outdoor Unit
Activation of outdoor unit fan controller protection
Power module automatically stop (overcurrent, low voltage, short circuit)
Abnormal inverter fin thermister, abnormal outdoor fan Inverter PCB failure
Abnormality of fan controller (overcurrent, low voltage, short circuit)
5A
Abnormality of fan controller fin temperature Fin thermistor failure, heat exchanger clogging, fan motor failure
5b
Fan
Activation of overcurrent protection
Controller
5C
Abnormality of fan controller sensor
Fan motor failure
Failure of current sensor (instantaneous overcurrent, increase of fin
temperature, low voltage, earth fault, step-out)
28
EE
Compressor
Compressor protection alarm (It can not be reset from remote controller.)
This alarm code appears when the following alarm occurs three times within 6 hours. 02, 07, 08, 39, 43 to 45, 47
b1
Outdoor Unit No. Setting
Incorrect outdoor unit address number or unit number setting
The number set for address or refrigerant cycle is over 64.
b5
Indoor Unit Incorrect indoor unit connection number No. Setting setting
More than 17 indoor units are connected to single refrigerant system. (non-H-Link II system)
NoteIf there’s any transmission abnormality (connector loss, loose, incorrect wiring and disconnection) between indoor unit
and remote controller, remote control operation indicator will flash once every 2 seconds.
- Finally, please deliver the guarantee, operation manual, and installation manual, etc. to the customer to keep it.
DangerBefore the preparation of test running completes, please do not start running, be sure to confirm the electrical wiring, etc.
29
Test Run and Maintenance Record
MODEL:
SERIAL. No.
CUSTOMER’S NAME AND ADDRESS:
COMPRESSOR MFG. No. DATE:
1. Is the rotation direction of the indoor coil fan correct?
2. Is the rotation direction of the outdoor coil fan correct?
3. Are there any abnormal compressor sounds?
4. Has the unit been operated at least twenty (20) minutes?
5. Check Room Temperature
Inlet: No. 1 DB /WB , No. 2 DB /WB , No. 3 DB /WB
Outlet:
DB /WB ,
DB /WB ,
DB /WB
Inlet: No. 5 DB /WB , No. 6 DB /WB , No. 7 DB /WB
Outlet:
DB /WB ,
DB /WB ,
DB /WB
6. Check Outdoor Ambient Temperature
Inlet: DB
, WB
Outlet: DB
, WB
7. Check Refrigerant Temperature: Operating Mode (Cool)
Discharge Gas Temperature:
Td=
Liquid Pipe Temperature:
Te=
8. Check Pressure
Discharge Pressure:
Pd=
Suction Pressure:
Ps=
9. Check Voltage
Rated Voltage:
V
Operating Voltage:
L1-L2
V
Starting Voltage:
V
MPa MPa
L1-L3
YES/NO YES/NO YES/NO YES/NO
, No. 4 DB /WB ,
,
DB /WB ,
, No. 8 DB /WB ,
,
DB /WB ,
V L2-L3
V
Phase Imbalance:
10. Check Compressor Input Running Current
Input:
kW
Running Current:
A
11. Is the refrigerant charge adequate?
12. Do the operation control devices operate correctly?
13. Do the safety devices operate correctly?
14. Has the unit been checked for refrigerant leakage?
15. Is the unit clean inside and outside?
16. Are all cabinet panels fixed?
17. Are all cabinet panels free from rattles?
18. Is the filter clean?
19. Is the heat exchanger clean?
20. Are the stop valves open?
21. Does the drain water flow smoothly from the drain pipe?
YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO
30
MEMO
31
66MP1373 Printed in Philippines 32
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>