OVERVIEW

The nLight ECLYPSE™ system controller connects an nLight® lighting network to support connectivityand management over an IP network, control and device setting adjustment, integration with building management, integration with demand response, and more.

FEATURES

  • Communicates over IP, allowing the system controller and connected lighting controls devices to be accessed and configured across a local area network
  • Each system controller supports up to 750 nLight and nLight AIR devices. Additional controllers can connect and scale a system of lighting controls to a maximum of 20,000 devices
  • BACnet Testing Laboratories (BTL) listed as a BACnet Building Controller (B-BC)
  • Can be discovered and managed through free SensorView software and through an onboard web GUI
  • Provides time-of-day and astronomical time clock capabilities for scheduled lighting control events
  • Manages forwarding of global control channels and system profiles to affect devices on multiple controllers at the same time
  • Enhanced security through toggleable HTTP or HTTPS connections, a FIPS 140-2, Level 1 compliant security interface, SSO or Radius Server capabilities, and more
  • Optional demand response client allows activation of configurable load shed dimming levels by utility DRAS through OpenADR 2.0a

ORDERING INFORMATION

NECY Example: NECY MVOLT BAC ENC
Series Voltage BACnet

Software
nECYnLight ECLYPSE| MVOLT120-277VAC347120-277VAC, 347VAC| [blank]BACNot EnabledBACnet/IP & MS/TP Enabled| [blank]Not EnabledADROpen ADR VEN| [blank]Not EnabledSVS 1Envysion
| | |
---|---|---|---
Cellular Modem| Enclosure| Wi-Fi Adapter| Options**
[blank] No Cellular ModemREM 5         Prewired CLAIRITY™ Link router with cellular SIMREMR 2,5 Prewired CLAIRITY™ Link router with cellular SIM and cloud-toggleable relay| ENC NEMA Type 1metal enclosure| [blank]   Includes Wi- Fi Adapter NW        No Wi-FI Adapter Included| [blank] NoneSEP       Single Ethernet PortGFXK 3    Touchscreen interface (model nGWY2 GFX, mounted separately), PS 150 power supply, CAT5 cableAIR 4            Includes NECYD NLTAIR G2

ACCESSORIES
nECY ENC: NEMA 1 Enclosure and pre-mounted 120-277VAC input, 24VDC output (Max 50W) power supply
nECYD NLTAIR G2 :  nLight AIR wireless adapter
nECYREPL INTF: nLight Interface module (introduces 750 device limit if added to an ECLYPSE with AIR option)

Notes

  1. Requires BACnet option.
  2. Cloud-toggleable relay is prewired and intended to powercycle the nLight ECLYPSE remotely.
  3. If 347 voltage option is selected, includes PS150 347.
  4. AIR option supports 150 devices. RJ45 ports for connecting nLight wired devices are not available with the AIR option. GFXK option is not available with AIR option.
  5. 347 option is required for cellular connectivity in Canada. MVOLT versions will support connectivity in\ the United States and Mexico only. Active connectivity plan required for cellular connectivity. All routers ship with 12-months Ethernet connectivity enabled. See CLAIRITY Link router specification sheet for more information.
  6. Cellular connectivity performance may be affected by carrier coverage and antenna placement. Coverage by supported carriers should be verified prior to purchase.
  7. See the Specifications section for a list of all supported carriers per country.
  8. Use of default SIM included with hardware is required for REMCONN CELL connectivity plan. REMCONN ETH does not require use of a cellular SIM but is required for connectivity with the portal using a non-standard, third-party SIM, provided by, paid for, and maintained by others. Compatibility with non-default, third party SIMs is not guaranteed or warranted.

CONNECTIVITY PLANS

Remote support via the CLAIRITY Link solution is enabled through a connectivity plan (REMCONN). Purchase of a CLAIRITY Link router includes an initial 12-month Ethernet connectivity plan that begins upon shipment of hardware from the factory. For extended periods of connectivity, or for cellular connectivity, supplementary plans can be purchased. Flexible plans are offered in 3-month to 24-month durations and can be purchased at any time.

FEATURES

  • Flexible connectivity periods offer affordable, connected assistance from nLight technical experts
  • With no hidden fees and no continuous costs, CLAIRITY Link connectivity is an on-demand service that can be purchased at any time
  • On-premise systems continue to operate when a connectivity plan is inactive
  • Optional service plans affordably supplement the ability to remotely connect, adding comprehensive programming, sustainment, and preventative maintenance options

Example: REMCONN ETH 24MO CAR1

| | |
Series| Connection Type| Service Length| Supported Countries
REMCONN Connectivity plan toenable remote access by factory representatives| ETH: Uses Ethernet connection to a customer-provided network with Internet access for communication with the CL AIR ITY Link portal
CELL 6,7,8: Includes a cellular plan to supplement or replace Ethernet connectivity for communication with the CL AIR ITY Link portal| 3MO: 3-month length
6MO: 6-month length
9MO: 9-month length
12MO: 12-month length
18MO: 18-month length
24MO: 24-month length

| CAR1  US, Mexico, and Canada

SPECIFICATIONS’ Control Module

Microprocessor : Single core 1.0 GHz Sitara ARM processor
Size: 4.74″ H x 3.57″ W x 2.31″ D (12.03 cm x 9.07 cm x 5.86 cm)
Mounting: DIN rail mounted nLight ECLYPSE Assembly Size: 4.74″ H x 14.76″ W x 2.43″ D (12.03 cm x 37.5 cm x 6.16 cm)
Ports: Ethernet: (2) switched RJ-45 Ethernet ports
USB Connections: 2 x USB 2.0 ports
RS-485 Serial Communications: Screw terminals (Used for either BACnet MS/TP
Subnet : RJ-45
Real Time Clock (RTC): Real Time Clock RTC Battery: 20 hours charge time, 20 days discharge time. Up to 500 charge / discharge cycles
Enclosure: FR/ABS UL94-V0 flammability rating
Environmental: Operating Temperature: 32°F to 122°F (0 to 50°C)
Storage Temperature: -22°F to 158°F (-30 to 70°C)
Relative Humidity: 0 to 90% non-condensing
Ingress Protection Rating: IP20
Security: FIPS Publication 140-2, Level 1 Compliant Complies with California Civil Code Title 1.81.26, Security of Connected Devices, approved under Senate Bill No. 327 (2018)

nLight Network Interface Module Size: 4.74″ H x 3.20″ W x 2.31″ D (12.03 cm x 8.12 cm x 5.86 cm)
Mounting: DIN rail mounted
Ports: 3 nLight bus ports (RJ-45) nLight Bus Power Output: 0mA per port

Power Supply Module (24V)

Size: 24V: 4.74″ H x 2.85″ W x 2.31″ D (12.03 cm x 7.24 cm x 5.86 cm)
Operating Voltage : 24V: 24VAC/DC; ±15%; Class 2 Output Voltage,
Rated Current & Power: 24V: 18VDC regulated, 0-1.6A, 30W max

Enclosure
Type: NEMA 1 rated surface mount screw cover
Size: 14.25″H x 14.25″W x 4.00″D (36.20cm x 36.20cm x 10.16cm)
Rating: UL 2043 (Plenum) Rated

CLAIRITY Link Router
Size:
2.92″H x 3.27″W x 0.99″D (74mm x 83mm x
25mm)
Power Consumption: < 6.5W
Input Voltage Range: 9-30VDC
Mobile: 4G LTE – up to 150Mbps
3G – up to 42Mbps
2G – up to 236.8kbps
United States – ATT, T-Mobile/Sprint, US
Cellular, Alaska Wireless
Mexico – Telefonica
Canada – Tellus, Bell, SaskTel6
Ethernet: WAN – 10/100Mbps; connects to an ownerprovided, Internet- connected network. May be
used for nLight ECLYPSE controller discovery on
the same network.
LAN-10/100Mbps; used for discovery of nLight
ECLYPSE controllers that are connected to a
network without Internet connectivity
Wireless Mode – IEEE 802.11b/g/n
Security – WPA2-Enterprise
Wi-Fi Hotspot – used for modem and SIM diagnostics
Wi-Fi Client – not supported
Environmental: Operating temperature – -40C to 75C
Operating humidity – 10% to 90% noncondensing
Storage temperature – -45C to 75C
Security: Firewall – pre-configured firewall
Attack Prevention – DDOS prevention, port scan prevention
WEB filter – whitelist for specifying allowed sites only
Access control – control of TCP, UDP, ICMP
packets, MAC address filter
Complies with California Civil Code Title
1.81.26, Security of Connected Devices,
approved under Senate Bill No. 327 (2018)

ingress Protection: IP30
Regulatory: FCC, IC/ISED, EAC, RCM, PTCRB, RoHS, CE/RED,
WEEE, Wi-Fi Certified, CCC, Anatel, GCF, REACH,
Thailand NBTC, Ukraine UCRF, SDPPI (POSTEL)
Antennas: Mobile – 698-960/1710-2690 MHz, SMA male connector
Wi-Fi – 2400-2483.5 MHz, SMA male connector
Input/Output Input: – 1x digital, non-isolated input (on 4 pin power connector)
Output – 1 x digital, open collector output (30 V,
300 mA, on 4 pin power connector)
SIM 1 x SIM slot (Mini SIM – 2FF), 1.8V/3V, external
SIM holder
Dimensions 83 x 25 x 74 mm

COMMUNICATION

Ethernet Connection Speed: 10/100 Mbps
Internet Protocol: IPv4
BACnet Profile: BACnet Building Controller (B-BC)
BACnet Listing: BTL, B-BC
BACnet Interconnectivity: BBMD forwarding capabilities
BACnet/IP to BACnet MS/TP routing
BACnet Transport Layer: MS/TP & IP (optional)
Web Server Protocol: HTML5
Web Server Application Interface: REST API

Supported BACnet MS/TP Connectivity:

  • 1 x RS-485 serial communications port for BACnet MS/TP
  • RS-485 EOL Resistor – Built-in
  • RS-485 Baud Rates – 9600, 19200, 38400, or 76800 bps

Supported Wireless Connectivity:

  • Wireless Adapter – USB Port Connection
  • Wi-Fi Communication Protocol – IEEE 802.11b/g/n
  • Wi-Fi Network Types – Client, Access Point, Hotspot

SYSTEM ARCHITECTURE

The nLight ECLYPSE serves as the backbone for nLight and nLight AIR digital lighting networks. The nLight ECLYPSE provides networked devices with schedule management and remote software programming via SensorView web-based software. The backbone also provides support for system-wide controls such as master override switches, automated demand response, and BACnet integration. One nLight ECLYPSE is capable of handling up to 750 total devices and up to 128 global channels for the entire network. The nLight ECLYPSE is also compatible with other Distech ECLYPSE products, offering a full suite of BAS capabilities.

ENVYSION Lighting Control and Visualization
Computer
Space Utilization Edge Application
Computer
SensorView Lighting Configuration
ComputerConnection
Lightnetwork connects to nECY via onboard light port alight AIR network connects to NECY wa NECYD NLTAIR G2 adapter connected to ECY USB port).

nLight’ AIR Wireless Controls
Wireless Controls

EXAMPLE NLIGHT ECLYPSE NOMENCLATURE AND OPTIONS

 Example Nomenclature|  Connection to Wired Devices| Maximum of 150 Wireless Devices| Maximum of 750 Wireless Devices| All License Options Available (BAC, SVS, SVEA)
---|---|---|---|---
NECY MVOLT ENC| | No AIR Adapter| No AIR Adapter|
NECY MVOLT ENC+NECYD NLTAIR G2| |  Not Limited at 150| |
NECY MVOLT ENC AIR| No Wired Interface Module|  | Reduced Capability|
NECY MVOLT ENC AIR + NECYREPLY INTF|  |  Not Limited at 150|  | ****

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nlight
© 2014-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 05/30/23

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals