OVERVIEW

nLight AIR rPP power packs are designed to offer flexible control for commercial and industrial lighting applications. The rPP consists of a relay, 0-10V dimming control, and a low voltage power supply output to power and wireless sensors. The rPP is capable of switching loads up to 20 A via a latching relay designed with robust inrush protection. Select power packs provide +24VDC low voltage output to power up to 4 nLight AIR mounted occupancy sensors and photocells. The nLight AIR rPP is designed for use as part of an nLight AIR group of devices or with the nLight ECLYPSE™.

POWER PACK FEATURES

  • On/Off and dimming control of a luminaire or group of luminaires
  • 24VDC output to power up to 4 nLight AIR rCMS low voltage sensors or other low voltage devices
  • Suitable for plug load control
  • UL 924 listed options for simplified lighting control on emergency lighting circuits
  • Power Monitoring with Current Measurement +/- 3% accuracy

INSTALLATION FEATURES

  • Wireless communication enables simple retrofits – no communication wires to pull between devices
  • Chase nipple or side output dimming options
  • UL 2043 listed for plenum applications
  • An optional external antenna (CP option) for meeting code specific requirements or IP-rated applications
  • Simple app-based configuration of space behaviors

ADVANCED WIRELESS FEATURES

  • Devices intercommunicate to provide grouped-response to motion and on/off and dimming response to daylight conditions when wirelessly connected to a motion or daylight sensor, or on/off/dimming when connected to a wireless switch
  • Fully compatible with other nLight AIR devices on the site
  • Easy to integrate with the nLight ECLYPSE, which provides site-wide lighting control through nLight’s SensorView software and provides optional BMS integration
  • Comprehensive wireless security

Warranty

Five-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and- conditions
Note: Actual performance may differ as a result of end-user environment and application.
Specifications subject to change without notice.

Items marked by a shaded background qualify for the Design Select program and ship in 15 days or less. To learn more about Design Select, visit www.acuitybrands.com/designselect. *See ordering tree for details
nLight, nLight AIR and the Acuity Controls and Acuity Brands logos are trademarks of Acuity Brands. Bluetooth is a trademark of Bluetooth SIG, Inc. used by Acuity Brands under license. Apple and the Apple logo are trademarks of Apple Inc. Android and Google Play are trademarks of Google, Inc. Other trademarks are property of their respective owners.
DesignLights Consortium® (DLC) qualified product. Not all versions of this product may be DLC qualified. Please check the DLC Qualified Products List at www.designlights.org/QPL to confirm which versions are qualified.

ORDERING INFORMATION

rPP20
Example: rPP20 D 24V EFP G2

| | | |
---|---|---|---|---
Series| Dimming and Low Voltage Output| Emergency| Fault Protection
RPP20 nLight AIR
Power/Relay Pack| [blank] None 24V
No dimming, 24V Output
Terminals D 0-10VDC Dimming output (via chase nipple), no 24V Output Terminals D 24V 0-10VDC dimming output (via chase nipple), 24V output terminals| DS 0-10VDC dimming output (via side leads), no 24V output terminals
DS 24V 0-10VDC Dimming output (via side leads), 24V Output Terminals| [blank] 1 None ER UL924 Emergency Operation, via power sense leads EM
2 UL924 Emergency Operation, via separate normal power sensing device| EFP External Fault
Protection
| | |
---|---|---|---
Territory Compliance| Voltage| Power Monitoring| Generation
[blank] None CP  3 Chicago Plenum| [blank]  4 120-277V
UVOLT  4 120-480V| [blank] None IM
Current Monitoring| G2 Generation 2 compatibility

ACCESSORIES
NPP FUSE J10 Replacement Fuse
Notes

  1. Can provide normal power sensing information to nLight AIR devices with EM option. See the UL 924 Response section for more information.

  2. EM option requires an nLight AIR device connected to normal power for wireless normal power detection.
    See the UL 924 Response section for more information.

  3. Not available with UVOLT model.

  4. All phase-to-phase applications, including 208VAC and 480VAC, require factory installation.

SPECIFICATIONS

Size:| 3.50″ x 3.52″ x 1.82″ (120-277V model)
4.725″ x 4.80″ x 1.865″ (UVOLT model)
---|---
Weight:| 6 oz
Mounting:| 1/2″ Knockout
Color:| White (standard), Red (ER & EM)
Humidity:| 5 to 95% non-condensing
Location:| Damp Location Rating
Wires:| Line and load 12 AWG stranded
Neutral, ground, and power sense (ER version) 18 AWG stranded
0-10V, 20 AWG stranded
Operating Voltage:| 120-277VAC, 120-480VAC (UVOLT)
Relay type:| Latching
Frequency:| 50/60Hz
Current Monitoring:| MVOLT versions include automatic voltage detection for power calculation. HVOLT versions require user input of voltage via SensorView to calculate power
Minimum Current required to ensure +/- 3% Accuracy MVOLT – 425mA UVOLT – 625mA
DC Output Terminals:| Push-in Terminals, solid or tinned 16-20AWG
DC Output Voltage/Current:| 24 VDC, 100 mA max output
0-10V Dimming:| Sinks 150mA; 0-10VDC dimmable ballasts or LED drivers;
Radio Frequencies:| 900 MHz up to +20dBM, 2.4 GHz up to +10 dBM
Wireless Standard:| 900 MHz: IEEE 802.15.4-based; 2.4 GHz: Version 4.0+ of the Bluetooth specification
Security:| Application Data Encryption AES-128 bit, Mutual
Entity Authentication, Message Confidentiality,
Message Authentication and Replay Prevention, Limited Anonymity
Complies with California Civil Code Title 1.81.26,
Security of Connected Devices, approved under Senate Bill No. 327 (2018)
Regulatory Compliance:| FCC ID: 2ADCB-RMODIT3
IC: 6715C-RMODIT3
IFETEL: RCPNLNL20-2057
cULus
RoHS

Temperature and Load Ratings

Model| rPP20 (-10 to 50 C)| rPP20 (-10 to 60 C)| rPP20 UVOLT (-10 to 70C)
---|---|---|---
Voltage| 120 VAC| 277 VAC| 120 VAC| 277 VAC| 120 VAC| 277 VAC| 347 VAC| 480 VAC
General Purpose| 20A| 20A| 5A| 5A| 20A| 20A| 20A| 5A
Tungsten| 20A| 20A| 5A| 5A| 20A| 20A| 20A| 5A
Standard Ballast| 20A| 20A| 5A| 5A| 20A| 20A| 20A| 5A
Electronic Ballast| 16A| 16A| 5A| 5A| 16A| 16A| 16A| 5A
Motor| 1.5 HP| 1.5 HP| 1.5 HP| 1.5 HP| 1.5 HP| 1.5 HP| 3/4 HP| 1/2 HP

WIRING (Do not wire hot)

Legend
BLK – Unswitched Hot 120-277, 347VAC*
WHT – Neutral
BLU – Switched Output
VIO – 0-10V Dim
PNK
– 0-10V Common
RED (Terminal) – +24VDC
BLK (Terminal) – DC Common
GRN – Ground

  • 0-10V Dimming Common from luminaire may be pink or as otherwise indicated per section 410.69 of the 2020 NEC.
    **347 only supported by UVOLT option.

WIRING FOR EMERGENCY (-ER) UNITS

Legend
RED – 120-277, 347VAC* Emergency Hot
WHT/RED – Emergency Neutral
BLK – Unswitched Norm. Hot
WHT – Norm. Neutral
BLU – Switched Output
VIO – 0-10V Dim (+)
PNK
– 0-10V Com (-)
RED (Terminal) – +24VDC
BLK (Terminal) – DC Com
GRN – Ground
– Optional Test Switch (by others)

  • 0-10V Dimming Common from luminaire may be pink or as otherwise indicated per section 410.69 of the 2020 NEC
    347 only supported by UVOLT option.
    UL924 Sequence of Operation:**
    When normal power sense leads have absence of voltage

    • Relay is closed and 0-10V dimming is at high end trim level
    • Device ignores wireless lighting control commands

UL 924 Response – nLight AIR Devices with EM Option
The below information applies to all nLight AIR devices with an EM option.

  • EM devices will remain at their high-end trim and ignore wireless lighting control commands, unless a normal-power-sensed (NPS) broadcast is received at least every 8 seconds.
  • Using the CLAIRITY™+ mobile app, EM devices must be associated with a group that includes a normal power sensing device to receive NPS broadcasts.
  • Only non-emergency rPP20, rLSXR, rSBOR, rSDGR, and nLight AIR luminaires with version 3.4 or later firmware can provide normal power sensing for EM devices. See specification sheets for control devices and luminaires for more information on options that support normal power sensing.

DIMENSIONS

Acuity Brands | One Lithonia Way Conyers, GA 30012
Phone: 800.535.2465
www.acuitycontrols.com
© 2014-2023 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/26/23

Documents / Resources

| nLiGHT rPP20 Air Power or Relay Pack [pdf] User Guide
rPP20 Air Power or Relay Pack, rPP20, Air Power or Relay Pack, Power or Relay Pack, Relay Pack, Pack
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals