JUMO TN-60-6003164 Surface Mounting Thermostat Room Instruction Manual

June 13, 2024
JUMO

JUMO TN-60-6003164 Surface Mounting Thermostat Room

JUMO TN-60-6003164 Surface Mounting Thermostat Room

Please read these Operating Instructions before commissioning the instrument.

Please assist us to improve these operating instructions, where necessary. Your comments will be appreciated.

Phone +49 661 6003-0
Fax +49 661 6003-607

If any difficulties should arise during commissioning, you are asked not to undertake any unauthorized manipulations on the instrument. This will endanger your rights under the instrument warranty! Please contact your supplier or the main factory.

Introduction

Use
  • JUMO heat THERM-AT surface-mounting thermostats monitor and control temperatures in heat-generating plant and HVAC applications.
  • JUMO heat THERM-AT room thermostats control heating and cooling installations (climate control, ventilation) in commercial premises, nurseries, stables and HVAC applications.
Marking
  • Version in accordance with
    EN 14597 as:
    TR = Temperature controller
    TW = Temperature monitor
    STW = Safety temperature monitor
    STB = Safety temperature limiter

  • Type examination to:

    • EN 14597
    • Pressure Equipment Directive (only STW and STB)
    • UL 873 (in progress)
  • JUMO heat THERM-AT surface-mounting and room thermostats meet EN 60730 (VDE 0631).

Safety notes
  • Cutting through or kinking the capillary will lead to permanent instrument failure.
  • Liquid may escape in the event of a measuring system fracture.

Physical and toxicological properties of the expansion medium that may escape in the event of a measuring system fracture:

Control range
with
end of scale
°C| Dangerous
reaction| Ignition temp. °C| Water
contamination|

Toxicological data

---|---|---|---|---
irritant| danger to health| toxic
< +200| no| +375| Class 1, mildly contaminant| no| no| no
≥ 200 ≤+350| No| +490| yes| yes| 1| no

  1. At present, there is no restrictive statement from the health authorities concerning any danger to health over short periods and at low concentrations, e.g. after a fracture of the measuring system.

Identifying the instrument

  1. Type code / Order code

  2. Contact rating: break contact (SPST-NC) /
    Contact rating: make contact (SPST-NO)

  3. Control / limit temperature at which this thermostat has been calibrated (option) / maximum instrument temperature / enclosure rating

  4. Sales number

  5. Serial number

  6. Year of production

  7. Week of production

  8. Approval mark
    Identifying the instrument

Mounting

General

Mounting position to DIN 16257,
NL 0 — NL 90

Mounting
Opening the housing

Opening the housing

Mounting the protection tube
  • The instruments must only be operated with the appropriate protection tubes.
  • For operation in air, without protection tube.
    Mounting the protection tube
    Mounting the protection tube
    The temperature probe must be completely immersed in the medium being measured.
Probe-Ø Prot. tube-Ø Material
6 mm 8 x 0,75 mm Brass / stainless steel
Wall mounting
  1. Drilling jig, single thermostat
  2. Drilling jig, dual thermostat
  3. Bending radius ≥ 5 mm.
  4. Shaped spring secures probe against sliding outWall mounting
    Wall mounting

Pipe mounting

  1. Shorten according to requirements.
    Pipe mounting

Settings / functions

  • Setpoint adjustment TR
  • Control range limiting
    Settings / functions

Setpoint / limit setting TW/STW/STB

STB reset

The STB can be reset when the temperature has fallen about 10% below the preset limit.

STB reset 

Response to measuring system fracture

If the measuring system is destroyed (i.e. the expansion liquid leaks) then the membrane pressure falls and the circuit will be permanently opened in the case of an STW or STB. On an STB, resetting is no longer possible.

Response to low temperature

If the probe temperature on an STB or STW falls below about -20°C, the circuit will open, but will automatically close again when the temperature rises.

IP54 protection

To achieve the enclosure protection rating IP54, the sealing elements must be inserted as shown in the  diagram.

IP54 protection

Lead sealing

(not included in delivery)

Lead sealing

(1) Drill only in the cross-hatched area on both sides

Installation

Electrical connection

Regulations and notes

  • The electrical connection must only be made by qualified personnel.
  • The choice of cable, the installation and the electrical connection must conform to the requirements of VDE 0100 “Regulations for the installation of power circuits with nominal voltages below 1000 V”, or to the appropriate local regulations.
  • If contact with live parts is possible while working on the unit, it must be completely disconnected from the supply.
  • Earth the instrument at the PE terminal to the protective conductor. This cable must have a cross-section that is at least as large as the supply cables.
Electrical connection
  • contact (plug-in terminal) * suitable for conductor cross-section 0.75 — 2.5 mm2. Use core-end ferrule with stranded conductor.
  • Connection suitable for fixed cabling. Cable entry with strain relief. Attachment type X or M.
  • Implement the connection according to the wiring diagram.

Prepare the cables

(1) Use a suitable crimping tool

Make the connection

Make the connection

*“Push-In®“ terminal technology is patented by Weidmüller GmbH & Co. KG, Detmold

Technical data

Permissible ambien t temperature in operation| at capillary and switch head +50′ C max.| at temperature probe max. setpoint: +15%
---|---|---
Permissible storage temperatu r e| maximum +50″C, minimum -30′  C
M a x .

contact rating

| for break contact (SPST-NC) (contacts 1-2)| 230 V AC +10%, 16 (2.5)A,

p.f. = 1 (0.6)

230 voe +10%, o.25 A

for make contact (SPST-NO) (contacts1-4)

TR, TW , STW : 230 VAC+10%,6.3 (2.5)A,
STB: 2    V AC +10%, 2 (0.4) A,
p.f. = 1(0.6)
230 VDC +10%, 0.25 A

M in. con t act rating| In order to ensure the maximum switching reliability, were commend a minimum contact loading of: AC/ DC= 24 V, 100 mA
rated surge voltage: 2500V
Requ i red fusing| see max. contact rating
Switching point accuracy| referred to the setpoint at T,,_ + 22 ‘ C see nameplate data on the instrument
M ean ambient temperature effect, referred to setpoint| A deviation of the ambient temperature around the switching head or the capillary from the calibration temperature of +22′ C will cause a shift of the switching point.

Higher ambient temperature = lower switching point Lower ambient temperature= higher switching point

This effect can be minimized by using a temperature compensation depending on the instrument configuration.

Weight| approx. 0.2 kg
Enclosur e   protection| EN 60 529 – IP40(IP54.)Pollution level 2
Operating medium| water, oil, air, super heated steam
Time constant to.632| in water s 45 sec in oil S 60 sec

in air/super htd. steam S120 sec

Mode of operation| asp erEN60730-1, EN 60 730-2-9 and EN14597 TR, TW : Type 2BL

STW       : Type 2BKLNP

STB        : Type 2BFHKLNPV

Customer Support

JUMO GmbH & Co. KG
Moritz-Juchheim-Straße 1 36039 Fulda, Germany
Tel.: +49 661 6003-0 Fax: +49 661 6003-500
mail@jumo.net | www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway
Harlow, Essex CM20 2TT, UK
Phone: +44 1279 635533 Fax: +44 1279 635262
sales@jumo.co.uk | www.jumo.co.uk

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals