Basler Electric BE1-11 Feeder Protection System User Guide
- June 12, 2024
- Basler Electric
Table of Contents
BE1-11
Protection Systems
Quick Start Guide
BE1-11 Feeder Protection System
WARNING: California’s Proposition 65 requires special warnings for products that may contain chemicals known to the state of California to cause cancer, birth defects, or other reproductive harm. Please note that by posting this Proposition 65 warning, we are notifying you that one or more of the Proposition 65 listed chemicals may be present in products we sell to you. For more information about the specific chemicals found in this product, please visit https://www.basler.com/Prop65.
Preface
This instruction manual provides basic installation and setup information for
BE1-11 Protection Systems.
To accomplish this, the following information is provided:
- BESTCOMSPlus® software installation and operation
- Power supply connections
- Settings configuration
- Programming BESTlogic™Plus programmable logic
For complete information on a specific BE1-11 Protection System, refer to one of the following instruction manuals:
- BE1-11d, DC Power Protection System, Publication 9424200761
- BE1-11f, Feeder Protection System, Publication 9424200990
- BE1-11g, Generator Protection System, Publication 9424200994
- BE1-11i, Intertie Protection System, Publication 9424200993
- BE1-11m, Motor Protection System, Publication 9424200996
- BE1-11t, Transformer Protection System, Publication 9424200995
Conventions Used in this Manual
Important safety and procedural information is emphasized and presented in
this manual through warning, caution, and note boxes. Each type is illustrated
and defined as follows.
Warning!
Warning boxes call attention to conditions or actions that may cause personal
injury or death.
Caution
Caution boxes call attention to operating conditions that may lead to
equipment or property damage.
Note
Note boxes emphasize important information pertaining to installation or
operation.
Warning!
READ THIS MANUAL. Read this manual before installing, operating, or
maintaining the BE1-11. Note all warnings, cautions, and notes in this manual
as well as on the product. Keep this manual with the product for reference.
Only qualified personnel should install, operate, or service this system.
Failure to follow warning and cautionary labels may result in personal injury
or property damage. Exercise caution at all times.
Basler Electric does not assume any responsibility to compliance or
noncompliance with national code, local code, or any other applicable code.
This manual serves as reference material that must be well understood prior to
installation, operation, or maintenance.
For terms of service relating to this product and software, see the Commercial
Terms of Products and Services document available at
www.basler.com/terms.
This publication contains confidential information of Basler Electric Company,
an Illinois corporation. It is loaned for confidential use, subject to return
on request, and with the mutual understanding that it will not be used in any
manner detrimental to the interests of Basler Electric Company and used
strictly for the purpose intended.
It is not the intention of this manual to cover all details and variations in
equipment, nor does this manual provide data for every possible contingency
regarding installation or operation. The availability and design of all
features and options are subject to modification without notice. Over time,
improvements and revisions may be made to this publication. Before performing
any of the following procedures, contact Basler Electric for the latest
revision of this manual.
The English-language version of this manual serves as the only approved manual
version.
Revision History
A historical summary of the changes made to this instruction manual is
provided below. Revisions are listed in reverse chronological order.
Visit www.basler.com to download the latest
hardware, firmware, and BESTCOMSPlus® revision histories.
Instruction Manual Revision History
Manual Revision and Date | Change |
---|---|
F, Mar-23 | ■ Updated to latest style |
■ Removed mention of CD-ROM and updated BESTCOMS Plus Installation
E, Feb-19| ■ Added information for BE1-11d
■ Minor edits throughout manual
D1, Nov-18| ■ Added Prop 65 warning on back of cover page
D, May-17| ■ Minor text edits throughout manual
C, Jul-16| ■ Added Windows 10 compatibility for BESTCOMS Plus software
■ Replaced Figures 4 and 6 to keep consistent with BESTCOMS Plus version
3.14.00
■ Added a note about standard I/O option in the paragraph above Figure 2
B, Dec-15| ■ Updated Figure 12 to show Primary A pickup setting
A, Apr-14| ■ Initial release
Quick Start Guide
This guide provides basic installation and setup information about BE1-11
Protection Systems. Upon receipt of the BE1-11, check the model and style
number against the requisition and packing list for agreement. If there is
evidence of shipping damage, file a claim with the carrier, and notify the
Basler Electric Regional Sales Office, your sales representative, or a sales
representative at Basler Electric, Highland, Illinois.
If the BE1-11 is not installed immediately, store it in the original shipping
carton in a moisture- and dustfree environment.
Note
Do not connect a USB cable between the PC and the BE1-FLEX until
BESTCOMSPlus® is installed. Connecting a USB cable before setup is complete
may result in errors.
Maintenance
Preventive maintenance consists of periodic replacement of the backup battery
and periodically checking that the connections between the BE1-11 and the
system are clean and tight. The front cover should be removed only when
replacing the backup battery for the real-time clock. Ensure that the BE1-11
is powered off and taken out of service before removing the front cover.
BE1-11 units are manufactured using state-of-the-art, surface-mount
technology. As such, Basler Electric recommends that no repair procedures be
attempted by anyone other than Basler Electric personnel.
Storage
This device contains long-life aluminum electrolytic capacitors. For devices
that are not in service (spares in storage), the life of these capacitors can
be maximized by energizing the device for 30 minutes once per year.
Install BESTCOMSPlus® Software
BESTCOMSPlus software is built on the Microsoft® .NET Framework. The setup
utility that installs BESTCOMSPlus on your PC also installs the BE1-11 plugin
and the required version of .NET Framework (if not already installed).
BESTCOMSPlus operates with systems using Windows® 7 SP1, Windows 8.1, and
Windows 10 version 1607 (Anniversary Edition) or later. System recommendations
for the .NET Framework and BESTCOMSPlus are listed in Table 1.
Table 1. System Recommendations for BESTCOMSPlus and the .NET Framework
System Type | Component | Recommendation |
---|---|---|
32/64 bit | Processor | 2.0 GHz |
32/64 bit | RAM | 1 GB (minimum), 2 GB (recommended) |
32 bit | Hard Drive | 200 MB (if .NET Framework is already installed on PC) |
4.5 GB (if .NET Framework is not already installed on PC)
64 bit| Hard Drive| 200 MB (if .NET Framework is already installed on PC)
4.5 GB (if .NET Framework is not already installed on PC)
To install BESTCOMSPlus, a Windows user must have Administrator rights.
- Download BESTCOMSPlus from www.basler.com.
- Click the installation button for BESTCOMSPlus. The setup utility installs BESTCOMSPlus, the .NET Framework (if not already installed), the USB driver, and the BE1-11 plugin for BESTCOMSPlus on your PC.
When BESTCOMSPlus installation is complete, a Basler Electric folder is added to the Windows programs menu. This folder is accessed by clicking the Windows Start button and then accessing the Basler Electric folder in the Programs menu. The Basler Electric folder contains an icon that starts BESTCOMSPlus when clicked.
**Power Up and Activate the BE1-11 Plug-In
**
The BE1-11 plugin is a module that runs inside the BESTCOMSPlus shell. The
BE1-11 plugin contains specific operational and logic settings for only BE1-11
protection systems. Uploading settings to the BE111 is possible only after
activating the BE1-11 plugin.
Note that if a BE1-11 is not connected, you will not be able to configure
certain Ethernet settings. Ethernet settings can be changed only when an
active USB or Ethernet connection is present. Refer to the Communication
chapter in the appropriate BE1-11 instruction manual for more information.
USB Connection
The USB driver was copied to your PC during BESTCOMSPlus installation and
is installed automatically after powering the BE1-11. USB driver installation
progress is shown in the Windows Taskbar area. Windows will notify you when
installation is complete. Connect a USB cable between the PC and your BE1-11.
A typical USB cable with a Btype connector is shown to the right.
Note
In some instances, the Found New Hardware Wizard will prompt you for the USB
driver. If this happens, direct the wizard to the following folder: C:\Program
Files\Basler Electric\USB Device Drivers\
If the USB driver does not install properly, refer to the Troubleshooting
chapter.
Apply Operating Power
The nominal power supply values are listed on the front-panel label. See
Figure 1 for an example.
Connect rear terminals A6, A7, and A8 (ground) to a power supply. Figure 2 shows the rear terminals of the BE1-11f in a J type case with standard I/O option. Figure 3 shows the rear terminals of the BE1-11f in an H or P type case. Apply operating power consistent with the nominal power supply values listed on the front-panel label. Wait until the boot sequence is complete.
Start BESTCOMSPlus® and Activate BE1-11 Plugin
To start BESTCOMSPlus, click the Start button, point to Programs, Basler
Electric, and then click the BESTCOMSPlus icon. During initial startup, the
BESTCOMSPlus Select Language screen is displayed (Figure 4). You can choose to
have this screen displayed each time BESTCOMSPlus is started, or you can
select a preferred language and this screen will be bypassed in the future.
Click OK to continue. This screen can be accessed later by selecting Tools and
Select Language from the menu bar.
The BESTCOMSPlus platform window opens. Select New Connection from the Communication pull-down menu and select BE1-11. See Figure 5. The BE1-11 plugin is activated automatically after connecting to a BE1-11.
The BE1-11 Connection screen shown in Figure 6 appears. Select USB Connection
and then click the Connect button.
The BE1-11 plugin opens indicating that activation was successful. You can now
configure the BE1-11 communication ports and other BE1-11 settings.
Programming the BE1-11
This section contains an introduction to BESTCOMSPlus, explains summary
screens, and gives an example of settings elements and programming logic for
the BE1-11f Feeder Protection System. Other applications are similar.
Introduction to BESTCOMSPlus®
BESTCOMSPlus is a Windows®-based, PC application that provides a user-
friendly, graphical user interface (GUI) for use with Basler Electric
communicating products. The name BESTCOMSPlus is an acronym that stands for
Basler Electric Software Tool for Communications, Operations, Maintenance, and
Settings.
BESTCOMSPlus provides the user with a point-and-click means to set and monitor
the BE1-11. The capabilities of BESTCOMSPlus make the configuration of one or
several BE1-11 Protection Systems fast and efficient. A primary advantage of
BESTCOMSPlus is that a settings scheme can be created, saved as a file, and
then uploaded to the BE1-11 at the user’s convenience.
The BE1-11 plugin opens inside the BESTCOMSPlus main shell. The same default
logic scheme that is shipped with the BE1-11 is brought into BESTCOMSPlus by
downloading settings and logic from the BE1-11 or by selecting application
type (D, F, I, G, T, or M) on the Style Number screen. This gives the user the
option of developing a custom setting file by modifying the default logic
scheme or by building a unique scheme from scratch.
BESTlogic™Plus Programmable Logic is used to program BE1-11 logic for
protection elements, inputs, outputs, alarms, etc. This is accomplished by the
drag-and-drop method. The user can drag elements, components, inputs, and
outputs onto the program grid and make connections between them to create the
desired logic scheme.
BESTCOMSPlus also allows for downloading industry-standard COMTRADE files for
analysis of stored oscillography data. Detailed analysis of the oscillography
files can be accomplished using BESTwave software.
Figure 7 illustrates the typical user interface components of the BE1-11
plugin with BESTCOMSPlus.
Click the View drop-down button to switch between the Settings Explorer and Metering Explorer or split the view between both. The Settings Info Panel displays settings ranges. A workspace can be opened, saved, or set as default. See Figure 8.
Summary Screens
Summary screens provide an overview of the system setup. The legend, located
in the lower right-hand corner, provides interpretation for the various
indicated colors. The current state of a protection and control function or
element is indicated by the color of the adjacent indicator. If the function
is enabled, the color is green. If the function is disabled only by a setting
(such as zero), the color is yellow. If the function is disabled only by a
mode, the color is blue. If the function is disabled by both a setting and
mode, the color is gray. The System Summary screen is available by clicking
BE1-11 in the Settings Explorer as shown in Figure 9. Summary screens are also
available for General Settings, Alarm Configuration, Protection, and Control.
Programming Example
Changing default logic is sometimes required to match the protection
requirements of the system. Additionally, elements must be enabled and
operating settings set. This example demonstrates how to configure typical
nominal settings and program the 50-3 instantaneous overcurrent element.
System nominal quantities are set to 69.3 volts and 3.6 amps. The 50-3 element
is set for a 5.62 amp pickup and a 30 second time delay. Additionally, the
element pickup output is logically wired to output 4 and a user alarm.
Step 1: Start BESTCOMSPlus and select New Connection, BE1-11 from the
Communication pull-down menu to connect to the BE1-11. See Figure 5.
Step 2: The BE1-11 Connection screen appears. See Figure 6. Select USB
Connection and click Connect.
Step 3: Select Download Settings and Logic from Device from the Communication
pull-down menu. This copies all settings and logic from the BE1-11 to
BESTCOMSPlus.
Step 4: Click on the View drop-down button and de-select Show Metering Panel
and Show Setting Information. See Figure 8. This maximizes the settings
workspace.
Step 5: In the Settings Explorer, click the “+” next to BE1-11. This expands
the sub menus in the tree.
Now expand System Parameters and select the Power System screen. See Figure
10.
Step 6: Under Nominal Settings, enter settings for (secondary) Phase Voltage
(69.3 V) and (secondary) Phase Current (3.6 A).
Step 7: In the Settings Explorer, expand Protection, Current and select the
Instantaneous Overcurrent (50-3) screen. See Figure 11.
Step 8: Select the Mode (3 Phase) and enter settings for Pickup (5.62 A) and
Time Delay (30,000 ms).
Step 9: In the Settings Explorer, click BESTlogicPlus Programmable Logic to
open the logic diagram. Click the Logic Page 1 tab. See Figure 12. Examine the
50-3 element. The Logic 0 connected to the Block input indicates that the 50-3
element is never blocked.
Off-Page Inputs/Outputs are used to make connections between logic pages and
help keep logic diagrams free from clutter. The Trip output is connected to an
Off-Page Output named 50-3 Trip. This 50-3 Trip Off-Page Output is carried
over to Logic Page 2 (Figure 13) where it becomes an Off-Page Input. The 50-3
Trip Off-Page Input and several others are OR gated to the Trip Bus Off-Page
Output which is carried over to Logic Page 3 (Figure 14) where it becomes an
OffPage Input. The Trip Bus Off-Page Input in connected to physical Output 1
on the BE1-11. Therefore, the OUT1 contacts operate when the 50-3 element is
tripped.
Step 10: In this step, the Pickup output of the 50-3 element is connected to Output 4. When the Pickup output of the 50-3 element is true, the label of Output 4 is displayed in the fault report and/or sequence of events report. The label is named in Step 12. Click the Logic Page 1 tab and then click the I/O tab at the bottom. Expand Output Objects and then Physical Outputs. Click and drag OUT4 over to the logic diagram. Click on the Pickup output of the 50-3 element and drag it to the input of OUT4 to make a connection. Refer to Figure 15.
Step 11: In this step, the Pickup output of the 50-3 element is connected to User Alarm 1. When the Pickup output of the 50-3 element is true, the label of the user alarm is displayed on the Alarms screen on the front-panel display and in the fault report and/or sequence of events report. The label is named in Step 13. Click the Logic Page 1 tab and then click the Elements tab at the bottom. Locate the User Alarm 1 element. Click and drag USERALM1 over to the logic diagram. Click on the Pickup output of the 50-3 element and drag to the input of USERALM1 to make a connection. Refer to Figure 16.
Step 12: Click the Save button to save the logic to BESTCOMSPlus memory for later inclusion in the settings file. See Figure 17.
Step 13: In the Settings Explorer, expand Programmable Outputs, Contact
Outputs, and name Output #4 (50-3 Pickup) as shown in Figure 18.
Step 14: In the Settings Explorer, expand Alarm Configuration, User
Programmable Alarms, and name User Programmable Alarm #1 (50-3 Pickup) as
shown in Figure 19.
Step 15: Figure 20 shows the user-defined labels of OUT4 and USERALM1 that
were named in Step 13 and Step 14.
Step 16: Select Save from the File pull-down menu to save your new settings
file.
Step 17: To make your new settings active in the BE1-11, select Upload
Settings and Logic to Device from the Communication pull-down menu. Enter the
username and password.
12570 State Route 143
Highland IL 62249-1074 USA
www.basler.com
info@basler.com
Tel: +1 618.654.2341
Fax: +1 618.654.2351
© 2023 by Basler Electric
All rights reserved
First printing: April 2014
Documents / Resources
|
Basler Electric BE1-11 Feeder Protection
System
[pdf] User Guide
9424200772, BE1-11, BE1-11 Feeder Protection System, Feeder Protection System,
Protection System, System
---|---
References
- Basler Electric - Providing quality electrical products and service to customers throughout the world
- basler.com/terms
- Basler Prop65
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>