Basler Electric BE1-11 Feeder Protection System User Guide

June 12, 2024
Basler Electric

BE1-11
Protection Systems
Quick Start Guide

BE1-11 Feeder Protection System

WARNING: California’s Proposition 65 requires special warnings for products that may contain chemicals known to the state of California to cause cancer, birth defects, or other reproductive harm. Please note that by posting this Proposition 65 warning, we are notifying you that one or more of the Proposition 65 listed chemicals may be present in products we sell to you. For more information about the specific chemicals found in this product, please visit https://www.basler.com/Prop65.

Preface

This instruction manual provides basic installation and setup information for BE1-11 Protection Systems.
To accomplish this, the following information is provided:

  • BESTCOMSPlus® software installation and operation
  • Power supply connections
  • Settings configuration
  • Programming BESTlogic™Plus programmable logic

For complete information on a specific BE1-11 Protection System, refer to one of the following instruction manuals:

  • BE1-11d, DC Power Protection System, Publication 9424200761
  • BE1-11f, Feeder Protection System, Publication 9424200990
  • BE1-11g, Generator Protection System, Publication 9424200994
  • BE1-11i, Intertie Protection System, Publication 9424200993
  • BE1-11m, Motor Protection System, Publication 9424200996
  • BE1-11t, Transformer Protection System, Publication 9424200995

Conventions Used in this Manual
Important safety and procedural information is emphasized and presented in this manual through warning, caution, and note boxes. Each type is illustrated and defined as follows.
Warning!
Warning boxes call attention to conditions or actions that may cause personal injury or death.
Caution
Caution boxes call attention to operating conditions that may lead to equipment or property damage.
Note
Note boxes emphasize important information pertaining to installation or operation.
Warning!
READ THIS MANUAL. Read this manual before installing, operating, or maintaining the BE1-11. Note all warnings, cautions, and notes in this manual as well as on the product. Keep this manual with the product for reference. Only qualified personnel should install, operate, or service this system. Failure to follow warning and cautionary labels may result in personal injury or property damage. Exercise caution at all times.
Basler Electric does not assume any responsibility to compliance or noncompliance with national code, local code, or any other applicable code. This manual serves as reference material that must be well understood prior to installation, operation, or maintenance.
For terms of service relating to this product and software, see the Commercial Terms of Products and Services document available at www.basler.com/terms.
This publication contains confidential information of Basler Electric Company, an Illinois corporation. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interests of Basler Electric Company and used strictly for the purpose intended.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual provide data for every possible contingency regarding installation or operation. The availability and design of all features and options are subject to modification without notice. Over time, improvements and revisions may be made to this publication. Before performing any of the following procedures, contact Basler Electric for the latest revision of this manual.
The English-language version of this manual serves as the only approved manual version.
Revision History
A historical summary of the changes made to this instruction manual is provided below. Revisions are listed in reverse chronological order.
Visit www.basler.com to download the latest hardware, firmware, and BESTCOMSPlus® revision histories.
Instruction Manual Revision History

Manual Revision and Date Change
F, Mar-23 ■ Updated to latest style

■ Removed mention of CD-ROM and updated BESTCOMS Plus Installation
E, Feb-19| ■ Added information for BE1-11d

■ Minor edits throughout manual

D1, Nov-18| ■ Added Prop 65 warning on back of cover page
D, May-17| ■ Minor text edits throughout manual
C, Jul-16| ■ Added Windows 10 compatibility for BESTCOMS Plus software
■ Replaced Figures 4 and 6 to keep consistent with BESTCOMS Plus version 3.14.00
■ Added a note about standard I/O option in the paragraph above Figure 2
B, Dec-15| ■ Updated Figure 12 to show Primary A pickup setting
A, Apr-14| ■ Initial release

Quick Start Guide
This guide provides basic installation and setup information about BE1-11 Protection Systems. Upon receipt of the BE1-11, check the model and style number against the requisition and packing list for agreement. If there is evidence of shipping damage, file a claim with the carrier, and notify the Basler Electric Regional Sales Office, your sales representative, or a sales representative at Basler Electric, Highland, Illinois.
If the BE1-11 is not installed immediately, store it in the original shipping carton in a moisture- and dustfree environment.
Note
Do not connect a USB cable between the PC and the BE1-FLEX until BESTCOMSPlus® is installed. Connecting a USB cable before setup is complete may result in errors.

Maintenance

Preventive maintenance consists of periodic replacement of the backup battery and periodically checking that the connections between the BE1-11 and the system are clean and tight. The front cover should be removed only when replacing the backup battery for the real-time clock. Ensure that the BE1-11 is powered off and taken out of service before removing the front cover. BE1-11 units are manufactured using state-of-the-art, surface-mount technology. As such, Basler Electric recommends that no repair procedures be attempted by anyone other than Basler Electric personnel.
Storage
This device contains long-life aluminum electrolytic capacitors. For devices that are not in service (spares in storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once per year.
Install BESTCOMSPlus® Software
BESTCOMSPlus software is built on the Microsoft® .NET Framework. The setup utility that installs BESTCOMSPlus on your PC also installs the BE1-11 plugin and the required version of .NET Framework (if not already installed). BESTCOMSPlus operates with systems using Windows® 7 SP1, Windows 8.1, and Windows 10 version 1607 (Anniversary Edition) or later. System recommendations for the .NET Framework and BESTCOMSPlus are listed in Table 1.
Table 1. System Recommendations for BESTCOMSPlus and the .NET Framework

System Type Component Recommendation
32/64 bit Processor 2.0 GHz
32/64 bit RAM 1 GB (minimum), 2 GB (recommended)
32 bit Hard Drive 200 MB (if .NET Framework is already installed on PC)

4.5 GB (if .NET Framework is not already installed on PC)
64 bit| Hard Drive| 200 MB (if .NET Framework is already installed on PC)
4.5 GB (if .NET Framework is not already installed on PC)

To install BESTCOMSPlus, a Windows user must have Administrator rights.

  1. Download BESTCOMSPlus from www.basler.com.
  2. Click the installation button for BESTCOMSPlus. The setup utility installs BESTCOMSPlus, the .NET Framework (if not already installed), the USB driver, and the BE1-11 plugin for BESTCOMSPlus on your PC.

When BESTCOMSPlus installation is complete, a Basler Electric folder is added to the Windows programs menu. This folder is accessed by clicking the Windows Start button and then accessing the Basler Electric folder in the Programs menu. The Basler Electric folder contains an icon that starts BESTCOMSPlus when clicked.

**Power Up and Activate the BE1-11 Plug-In

**

The BE1-11 plugin is a module that runs inside the BESTCOMSPlus shell. The BE1-11 plugin contains specific operational and logic settings for only BE1-11 protection systems. Uploading settings to the BE111 is possible only after activating the BE1-11 plugin.
Note that if a BE1-11 is not connected, you will not be able to configure certain Ethernet settings. Ethernet settings can be changed only when an active USB or Ethernet connection is present. Refer to the Communication chapter in the appropriate BE1-11 instruction manual for more information.
USB Connection
The USB driver was copied to your PC during BESTCOMSPlus installation and is installed automatically after powering the BE1-11. USB driver installation progress is shown in the Windows Taskbar area. Windows will notify you when installation is complete. Connect a USB cable between the PC and your BE1-11. A typical USB cable with a Btype connector is shown to the right.

Note
In some instances, the Found New Hardware Wizard will prompt you for the USB driver. If this happens, direct the wizard to the following folder: C:\Program Files\Basler Electric\USB Device Drivers\
If the USB driver does not install properly, refer to the Troubleshooting chapter.
Apply Operating Power
The nominal power supply values are listed on the front-panel label. See Figure 1 for an example.

Connect rear terminals A6, A7, and A8 (ground) to a power supply. Figure 2 shows the rear terminals of the BE1-11f in a J type case with standard I/O option. Figure 3 shows the rear terminals of the BE1-11f in an H or P type case. Apply operating power consistent with the nominal power supply values listed on the front-panel label. Wait until the boot sequence is complete.

Start BESTCOMSPlus® and Activate BE1-11 Plugin
To start BESTCOMSPlus, click the Start button, point to Programs, Basler Electric, and then click the BESTCOMSPlus icon. During initial startup, the BESTCOMSPlus Select Language screen is displayed (Figure 4). You can choose to have this screen displayed each time BESTCOMSPlus is started, or you can select a preferred language and this screen will be bypassed in the future. Click OK to continue. This screen can be accessed later by selecting Tools and Select Language from the menu bar.

The BESTCOMSPlus platform window opens. Select New Connection from the Communication pull-down menu and select BE1-11. See Figure 5. The BE1-11 plugin is activated automatically after connecting to a BE1-11.

The BE1-11 Connection screen shown in Figure 6 appears. Select USB Connection and then click the Connect button.
The BE1-11 plugin opens indicating that activation was successful. You can now configure the BE1-11 communication ports and other BE1-11 settings.

Programming the BE1-11

This section contains an introduction to BESTCOMSPlus, explains summary screens, and gives an example of settings elements and programming logic for the BE1-11f Feeder Protection System. Other applications are similar.
Introduction to BESTCOMSPlus®
BESTCOMSPlus is a Windows®-based, PC application that provides a user- friendly, graphical user interface (GUI) for use with Basler Electric communicating products. The name BESTCOMSPlus is an acronym that stands for Basler Electric Software Tool for Communications, Operations, Maintenance, and Settings.
BESTCOMSPlus provides the user with a point-and-click means to set and monitor the BE1-11. The capabilities of BESTCOMSPlus make the configuration of one or several BE1-11 Protection Systems fast and efficient. A primary advantage of BESTCOMSPlus is that a settings scheme can be created, saved as a file, and then uploaded to the BE1-11 at the user’s convenience.
The BE1-11 plugin opens inside the BESTCOMSPlus main shell. The same default logic scheme that is shipped with the BE1-11 is brought into BESTCOMSPlus by downloading settings and logic from the BE1-11 or by selecting application type (D, F, I, G, T, or M) on the Style Number screen. This gives the user the option of developing a custom setting file by modifying the default logic scheme or by building a unique scheme from scratch.
BESTlogic™Plus Programmable Logic is used to program BE1-11 logic for protection elements, inputs, outputs, alarms, etc. This is accomplished by the drag-and-drop method. The user can drag elements, components, inputs, and outputs onto the program grid and make connections between them to create the desired logic scheme.
BESTCOMSPlus also allows for downloading industry-standard COMTRADE files for analysis of stored oscillography data. Detailed analysis of the oscillography files can be accomplished using BESTwave software.
Figure 7 illustrates the typical user interface components of the BE1-11 plugin with BESTCOMSPlus.

Click the View drop-down button to switch between the Settings Explorer and Metering Explorer or split the view between both. The Settings Info Panel displays settings ranges. A workspace can be opened, saved, or set as default. See Figure 8.

Summary Screens
Summary screens provide an overview of the system setup. The legend, located in the lower right-hand corner, provides interpretation for the various indicated colors. The current state of a protection and control function or element is indicated by the color of the adjacent indicator. If the function is enabled, the color is green. If the function is disabled only by a setting (such as zero), the color is yellow. If the function is disabled only by a mode, the color is blue. If the function is disabled by both a setting and mode, the color is gray. The System Summary screen is available by clicking BE1-11 in the Settings Explorer as shown in Figure 9. Summary screens are also available for General Settings, Alarm Configuration, Protection, and Control.

Programming Example
Changing default logic is sometimes required to match the protection requirements of the system. Additionally, elements must be enabled and operating settings set. This example demonstrates how to configure typical nominal settings and program the 50-3 instantaneous overcurrent element. System nominal quantities are set to 69.3 volts and 3.6 amps. The 50-3 element is set for a 5.62 amp pickup and a 30 second time delay. Additionally, the element pickup output is logically wired to output 4 and a user alarm.
Step 1: Start BESTCOMSPlus and select New Connection, BE1-11 from the Communication pull-down menu to connect to the BE1-11. See Figure 5.
Step 2: The BE1-11 Connection screen appears. See Figure 6. Select USB Connection and click Connect.
Step 3: Select Download Settings and Logic from Device from the Communication pull-down menu. This copies all settings and logic from the BE1-11 to BESTCOMSPlus.
Step 4: Click on the View drop-down button and de-select Show Metering Panel and Show Setting Information. See Figure 8. This maximizes the settings workspace.
Step 5: In the Settings Explorer, click the “+” next to BE1-11. This expands the sub menus in the tree.
Now expand System Parameters and select the Power System screen. See Figure 10.
Step 6: Under Nominal Settings, enter settings for (secondary) Phase Voltage (69.3 V) and (secondary) Phase Current (3.6 A).
Step 7: In the Settings Explorer, expand Protection, Current and select the Instantaneous Overcurrent (50-3) screen. See Figure 11.
Step 8: Select the Mode (3 Phase) and enter settings for Pickup (5.62 A) and Time Delay (30,000 ms).

Step 9: In the Settings Explorer, click BESTlogicPlus Programmable Logic to open the logic diagram. Click the Logic Page 1 tab. See Figure 12. Examine the 50-3 element. The Logic 0 connected to the Block input indicates that the 50-3 element is never blocked.
Off-Page Inputs/Outputs are used to make connections between logic pages and help keep logic diagrams free from clutter. The Trip output is connected to an Off-Page Output named 50-3 Trip. This 50-3 Trip Off-Page Output is carried over to Logic Page 2 (Figure 13) where it becomes an Off-Page Input. The 50-3 Trip Off-Page Input and several others are OR gated to the Trip Bus Off-Page Output which is carried over to Logic Page 3 (Figure 14) where it becomes an OffPage Input. The Trip Bus Off-Page Input in connected to physical Output 1 on the BE1-11. Therefore, the OUT1 contacts operate when the 50-3 element is tripped.

Step 10: In this step, the Pickup output of the 50-3 element is connected to Output 4. When the Pickup output of the 50-3 element is true, the label of Output 4 is displayed in the fault report and/or sequence of events report. The label is named in Step 12. Click the Logic Page 1 tab and then click the I/O tab at the bottom. Expand Output Objects and then Physical Outputs. Click and drag OUT4 over to the logic diagram. Click on the Pickup output of the 50-3 element and drag it to the input of OUT4 to make a connection. Refer to Figure 15.

Step 11: In this step, the Pickup output of the 50-3 element is connected to User Alarm 1. When the Pickup output of the 50-3 element is true, the label of the user alarm is displayed on the Alarms screen on the front-panel display and in the fault report and/or sequence of events report. The label is named in Step 13. Click the Logic Page 1 tab and then click the Elements tab at the bottom. Locate the User Alarm 1 element. Click and drag USERALM1 over to the logic diagram. Click on the Pickup output of the 50-3 element and drag to the input of USERALM1 to make a connection. Refer to Figure 16.

Step 12: Click the Save button to save the logic to BESTCOMSPlus memory for later inclusion in the settings file. See Figure 17.

Step 13: In the Settings Explorer, expand Programmable Outputs, Contact Outputs, and name Output #4 (50-3 Pickup) as shown in Figure 18.
Step 14: In the Settings Explorer, expand Alarm Configuration, User Programmable Alarms, and name User Programmable Alarm #1 (50-3 Pickup) as shown in Figure 19.

Step 15: Figure 20 shows the user-defined labels of OUT4 and USERALM1 that were named in Step 13 and Step 14.
Step 16: Select Save from the File pull-down menu to save your new settings file.
Step 17: To make your new settings active in the BE1-11, select Upload Settings and Logic to Device from the Communication pull-down menu. Enter the username and password.

12570 State Route 143
Highland IL 62249-1074 USA
www.basler.com
info@basler.com
Tel: +1 618.654.2341
Fax: +1 618.654.2351
© 2023 by Basler Electric
All rights reserved
First printing: April 2014

Documents / Resources

| Basler Electric BE1-11 Feeder Protection System [pdf] User Guide
9424200772, BE1-11, BE1-11 Feeder Protection System, Feeder Protection System, Protection System, System
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals