RedEarth ENERGY STORAGE SRS-1xx SunRise 1 Phase Home Battery System Installation Guide
- June 12, 2024
- RedEarth ENERGY STORAGE
Table of Contents
- Safety
- SunRise Overview
- Dimensions and clearance/positioning information
- Summary of connections
- Internal Components description
- Installation – 8 steps for installation and customer handover
- Services & Options available for the SunRise
- Appendix A – Single Line Diagrams
- Appendix B – Technical Specifications
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SunRise 1-phase
Home Battery System
Model: SRS-1xx & SRM-1xx
Installation Manual
SunRise 1ph NS – Installation Manual
Note: This product was not tested to AS/NZS 4777.2:2020 Section 5 for
multiple inverter combinations. The SunRise system (SRS-1xx and SRM-1xx) are
not designed to include multiple units on a single site.
Note: A previous version of the SRS-1xx and SRM-1xx has an integrated PV
isolator (yellow and red PV isolator as shown below.. The new version of the
SRS-1xx and SRM-1xx, as described in this manual, does not include this PV
isolator and an external PV isolator is required.
Note: The product was not tested to AS/NZS 4777.2:2020 Section 6 for
Generation/Export limit control”.
Safety
Symbol | Explanation |
---|---|
Refer to the operating instructions | |
**** | Indicates additional information, emphasized contents or tips that may |
be helpful.
| Caution, risk of electric shock.
| Caution, risk of danger.
| Do not touch live parts until 10 minutes after disconnection from the power
sources.
**** The wiring diagrams and installation instructions are given as a guide only and compliance to appropriate standards is the responsibility of the installer. Relevant standards are listed below:
AS/NZS 3000:2018 | Wiring rules |
---|---|
AS/NZS 5033:2021 (and 1&2) | Installation and safety requirements for |
photovoltaic (PV) arrays
AS/NZS 4509.2:2012| Stand-alone power systems-Design
AS/NZS 1170.2:2011| Structural design actions-Wind actions
AS/NZS1768:2007| Lightning protection
AS/NZS 3008.1.1:2017| Electrical installations – Selection of cables
AS4777.2:2020| Grid connection of energy systems via inverters
AS/NZS 5139:2019| Electrical installations-Safety of battery systems for use
with power conversion equipment
The SunRise must only be installed by suitably qualified personnel who
have read and are familiar with its operation and hazards.
The battery provided with this system must be charged only by the
Sungrow inverter. Do not attempt to charge the batteries with any other
charger device or connect any devices directly to the DC battery bus unless
approved by RedEarth.
** In the event of a fire evacuate the area and call emergency services. A
dry agent fire extinguisher should be readily available and used. DO NOT use
water.
Note: MSDS document is provided with the system and can be found at
www.redearth.energy
Do not use a damaged battery. Batteries should only be disposed of at an
appropriate recycling centre. Please contact RedEarth for advice.
** A battery can present a risk of electrical shock and high short-circuit
current. The following precautions should be observed when working on
batteries:
- Remove watches, rings, and other metal objects.
- Use tools with insulated handles.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
**** In our efforts towards constant product enhancement, this document is subject to change at any time. Please visit http://www.redearth.energyand download the appropriate and latest version manual.
SunRise Overview
SunRise Home Battery is an Australian-made all-in-one battery system designed
to optimise your customer’s electricity usage, reduce your electricity bill
and also reduce your carbon footprint.
The system, including solar panels, generates and stores electricity for use
day & night, and includes a backup capability so that your customers key loads
remain powered during any blackout.
You and your customer can monitor the system via RedEarth’s EMU app, available
for both Apple and Android phones.
There is also the option to use your customer to use their electricityin other
ways via RedEarth’s PPP (Private Power Plant), to generateadditional income
such as through Energy Trading. Contact RedEarthfor additional information.
RedEarth can also provide ongoing monitoring to ensure the system isoperating
correctly.
The SunRise system can operate without batteries, however much ofthe
functionality will not be available unless batteries are installed.
- With batteries, PV solar electricity generated during the day will be used by the home, excess electricity will be stored in the battery and then exported to the grid, which reduces the electricity bill. In addition the battery ensures essential household loads (fridges, lights etc) can be powered during a power outage. It is also a requirement for accessing the features of RedEarth’s PPP.
- Without batteries excess PV generated during the day can be exported to the grid, which reduces the electicity bill, however no electricity can be stored for later use. Note that the SunRise is designed so that batteries can easily be added inside it at a later date, as demand grows and budgets allow.
- The SunRise system can also easily be retrofitted to an existing PV solar system that may already be installed at the home.
All batteries added later must be of the same make and model and supplied by RedEarth to maintain the customer’s warranty. A maximum of 6 batteries can be added into the SRS-1xx (Maxi) totalling 24.6kWh nominal and a maximum of 3 batteries can be installed into the SRM-1xx (Mini) totaling 12.3kWh nominal..
A small battery will limit the amount of self consumption and energy trading possible.
A total of 6.6kW of solar panels can be connected to the SunRise 1ph systems, and be fully claimable via the government solar rebate scheme. Note that an additional PV inverter can also be added to increase the total size of the solar system. In a typical home with 1-phase wiring up to 5kW of additional PV inverters can be added, allowing a maximum of 13.2kW of solar panels to be installed. Contact RedEarth for more information if you are looking for a larger grid-connected system.
PPP Private Power Plant: RedEarth offers its PPP to generate more value for your customer from their SunRise system than is normally available from other battery systems which only offer a VPP option (Virtual Power Plant). Contact RedEarth for more details and to see if you qualify for RedEarth’s Private Power Plant. Finally, SunRise is fully certified to AS4777.2:2020 & IEC62109.1&2 & AS60950.1 and conforms to the Australian Battery Safety Guide.
Dimensions and clearance/positioning information
Model numbers:
SRS-1xx Maxi model numbers;
- SRS-100 (no batteries)
- SRS-104 (x1 battery = 4.1kWh nominal)
- SRS-108 (x2 battery = 8.2kWh nominal)
- SRS-112 (x3 battery = 12.3kWh nominal)
- SRS-116 (x4 battery = 16.4kWh nominal)
- SRS-120 (x5 battery = 20.5kWh nominal)
- SRS-124 (x6 battery = 24.6kWh nominal)
SRM-1xx Mini model numbers;
- SRM-100 (no batteries)
- SRM-104 (x1 battery = 4.1kWh nominal)
- SRM-108 (x2 battery = 8.2kWh nominal)
- SRM-112 (x3 battery = 12.3kWh nominal)
Summary of connections
A typical complete installation of the SunRise Home Battery will require the electrical connection of the following items:
-
Meter (supplied) installed in the MSB and connected to the SunRise system via Cat5/6 cable or similar. The information from this meter affects the operation of the SunRise system, make sure the wires are connected the right way around.
-
AC cables from the MSB directly to the Grid terminals inside the SunRise system.
-
AC cables from the MSB directly to the Emergency Power Supply (EPS) terminals inside the SunRise system.
o Note: the installer will also have to select which circuits are wired on the EPS side of the system (i.e., with Back-up support) inside the MSB (“splitting the board”). Putting too many loads on the EPS circuit can either empty the battery too quickly during an outage or overload the inverter. The maximum power the EPS from the battery alone is 3kW. If the PV array is providing power, then up to 5kW of backup power is available. -
Up to 2 arrays of PV solar panels are connected to the MC4 conectors pre-terminated inside the unit. Note also that in this NS version of the SunRise an external DC switch (PV Isolator) shall be fitted for connection of PV panels, the DC switch shall comply with AS60947.3 and relevant AU regulations.
-
Optional – an internet cable from the home internet router to the system to provide a second communication link if the WiFi signal or 4G signal is poor.
In addition, the installer will need to program the Sungrow inverter for the
customer’s specific requirements (e.g., level of grid-feed allowed by the
utility) Use the Sungrow iSolarCloud APP operating in local mode to access
these settings.
Once the SunRise system is up and running, the installer (or end customer) can
call RedEarth Tech Support and set-up the monitoring.
Note: The SunRise is not designed to act as the customers MSB as it does
not include space for additional main & customer circuit breakers or RCDs.
RCD’s must be installed in the MSB as required by AS4777.2:2020
Internal Components description
Opening the SunRise
RedEarth’s SunRise Home Battery System can be internally accessed by removing
the lid. To do this, remove the nine (9) screws with a Philips screwdriver
(PH2), lift and pull the cover away from the unit and place in a safe
location.
Inside layout
The SunRise is divided into three main areas. On the Lefthand side (LHS) is
the Inverter, in the middle are the batteries and on the Righthand Side (RHS)
are the electrical components and cable connection points for installation.
Prior to leaving the factory the
system is tested. It leaves the factory with the inverter cabling fully
connected and ready-to-run. The batteries are usually removed for
transportation.
Left hand Side (LHS)
Here you will find the Sungrow SH5K30 inverter. All the connections to it
arealready made. In this area you will also find the terminal blocks that
connect the comms cable that goes to the meter you will install in the switch
board.
Middle area
This is where the batteries are located. A complete set will have 6x RedEarth
Troppo-4841 Lithium Batteries in the SunRise-Maxi (SunRise Mini will have 3x
RedEarth Troppo Batteries). Note that the battery modules are usually shipped
separately. They are connected in parallel using the battery cables that are
already pre-wired in the system.
Right-hand Side (RHS)
Here you will find all the protection devices and the connection points needed
to wire in the system during installation.
There are labels to clearly identify which cables are connected where during
installation.
Note that it is recommended to complete all these electrical connections prior
to installing the Troppo batteries.
Additional items:
The SunRise is supplied with documentation and a parts kit box to complete the
installation.
-
Documentation
o User manual
o Installation manual
o SunRise Identification sheet (serial #s etc)
o SunRise production checklist
o Inverter manual – Sungrow
o Battery module manual – Troppo-4841
o MSDS – battery -
Additional hardware:
o 1x PV Isolator for external mounting next to the SunRise NS (no-switch) system -
Parts Kit box: (see image at right)
o Sungrow meter (with CT) for installation in the switch board
o Stickers and Traffolytes required for the installation
o 2x MC4 connector pairs – for terminating the PV array strings
o 1x M16 Gland for the comms antenna
o 6x M25 glands (suitable for sealing around 25mm flexible conduit)
o 1x Two-pole 32A circuit breakers
Installation – 8 steps for installation and customer handover
The SunRise system is designed to be easy to install. It includes prewired
connection points and comprehensive labelling and parts kit to simplify the
installation.
Technical support is available directly from RedEarth during installation if
required.
8 steps to complete the SunRise installation:
-
Transporting – getting the SunRise to site
-
Positioning – the SunRise in its final location on site
-
Solar Install – including bringing the PV cabling to the SunRise system
-
Electrical connections – at the SunRise system and the house switch board
4.1.1. Solar
4.1.2. Battery
4.1.3. Grid & EPS
4.1.4. Aux. Earth Fault Alarm
4.1.5. MSB & Sungrow meter -
Understanding Turn on/Shutdown procedures
-
Commissioning the system – turning on and programming and confirming system operation
-
Activating remote Monitoring and Communications – contact RedEarth to confirm remote operation
-
Customer Handover – including helping with access to RedEarth EMU app
Step 1 – Transporting
The SunRise system is usually supplied on a pallet, with the batteries in
separate cardboard boxes. It has been factory tested; however, the batteries
are usually subsequently removed for transportation. Without batteries but
with all other components in place the system weighs 87kg. The SunRise-Maxi
system weighs 339kg with x6 lithium batteries installed. The SunRiseMini
weighs 213kg when filled with 3x Troppo batteries. The image shows A SunRise-
Maxi with batteries packed separately as well as a second pallet of solar
panels in a trailer.
WARNING: Personal Injury
Use safe lifting techniques and standard safety equipment when working with
this equipment.
Step 2- Positioning
The SunRise is designed as a freestanding weatherproof system (IP43).
It is rated for the following Environmental Condition
**** – Rated maximum ambient operating temperature 50degC for outdoor
unconditioned without solar effects. According to AS4777.2:2020.
This means the SunRise system shall be installed in a shaded area. If
necessary, a solar shade will need to be installed above the system.
The SunRise system should be located at least 100mm off the wall to allow for
proper ventilation. It should be placed closer to the solar panels and the MSB
to minimise voltage drop/power loss.
Without batteries the assembled SunRise enclosure weighs 126kg. It should be
placed into position, secured to the ground and wired to the solar panels and
house switch board BEFORE installing the batteries. Note that the inverter can
be removed to further reduce the weight to 99kg if required.
- Allow space around the system (no doors or windows) to comply with current installation standards. (See image at right) if the system is within 300m of the wall.
- Note: the material that the wall is made of (flammability) can influence the allowed positioning, however, if the SunRise system is installed 300mm off the wall then the type of material is no longer relevant. This is a specific advantage of the SunRise system over some competitor’s systems.
- The SunRise has four holes in the base to allow for securing. This can be done with dynabolts or material appropriate screws.
Clearance for ventilation:
Cooling air flow passes up through vents in the base of the SunRise system and
then out through fans at the rear. The fans are controlled by an adjustable
temperature switch set to 35⁰C in the factory. Do not block any vents or
airflow access to the base as otherwise the system will overheat and shutdown.
(Once the system cools down again it should restart automatically).
NOTE: SunRise can be installed indoors. however, proper additional
ventilation must be installed according to AS/NZS 5139.
NOTE: Minimum distance between the wall and the back of the SunRise is
100mm
Step 3 – Solar Installation
PV Racking & Panels should be designed and installed in accordance wAS/NZS
5033 and the latest CEC Installation guidelines. Caution should taken in
selecting PV panels and the wiring method to ensure Open CircVoltage (VOC) and
Short Circuit Current (ISC) ratings are not exceeded.
String configuration:
The SunRise 1-phase system has x2 MPPTs. A maximum of 6.6kW of PVcan be
connected and still receive the full STCs for the government.
The Isc rating of the SH5k-30 Sungrow inverter is shown below.
| Type designation| Sh5K-30
---|---|---
DC Input Data|
Recommended max. PV input power| 6700 W
Max. PV input voltage| 600 V
Startup voltage| 125 V
Rated input voltage| 350 V
MPP voltage range| 125 V – 560 V
MPP voltage range for rated power| 240 V – 520 V
I No. of MPPTs| 2
Max. number of PV strings per MPPT| 1 /1
Max. PV input current| 22 A (11 A /11A)
Max. current for input connector| 15A
_ Short-circuit current of PV input| 30 A (15 A /15 A)
PV isolator:
Note that in this NS (no-switch) version of the SunRise there is no PV
isolator installed inside the system. Note also that in this NS version of the
SunRise an external DC switch (PV Isolator) shall be fitted for connection of
PV panels, the DC switch shall comply with AS60947.3 and relevant AU
regulations. See image at right. The two sets of PV cables are then brought
into the rear of the unit and plugged into the 2 sets of MC4 equipped PV
cables inside the unit which are already connected to the connection points in
the base of the inverter (see Step 4.1).
PV modules must have an IEC61730 Class A rating
Ensure that the array is within the inverter specification and polarity
of the array is correct.
** PV array must be floating (must not be grounded)
WARNING: The Solar DC Isolator on the SunRise must be in the off position
before any solar panels are connected
Step 4 Electrical Connections
** Before any electrical connections are made, check all internal
connections in the SunRise are secure and have not come loose during
transport.
**** Ensure that all breakers and isolators, as well as those supplying power
to the unit, are turned OFF.
All cable entry points for the AC, PV and any communication cables are made
via the 25mm gland/entry points on the rear of the system, as shown at right.
Use the 25mm glands that are supplied in the parts kit. These are designed to
accept flexible 25mm conduit. The 16mm gland is for the antenna of the RedPi
monitoring device.
The SunRise system must be hardwired to a remote switchboard, which contains a
MEN and an earth stake. To begin, open the unit as explained in “Opening the
SunRise” section and direct your attention to the RHS. Here are all the
connection points needed for installation.
4.1 Solar
The SunRise has 2x Maximum Power Point Trackers (MPPTs) and allows for two PV
strings to be installed as explained in Step 3. For ease of installation,
extension cables for the two strings are already connected to the inverter and
terminated with MC4 connectors inside the SunRise In this NS version of the
SunRise an external PV isolator (supplied) is attached to the wall next to the
SunRise system as explained in Step 3.
To connect the solar power, terminate the two PV strings in the external PV
isolator. Next run the two pairs of unterminated cables into the rear of the
SunRise, then terminate with the MC4’s supplied in the parts kit. Once this is
done, check for correct polarity and VOC, then plug the two strings into the
correct MC4s in the system.
4.2 Grid & EPS
Grid and Emergency Power Supply (EPS)
Terminal Blocks are pre-wired to simplify making all the GRID and EPS
connections during installation. They are labelled as shown at right.
The Terminal Block labelled as “Grid Active” connects the SunRise directly to
the Grid in the MSB.
(Also review wiring diagram included in Appendix A)
The Terminal Block labelled as “EPS Active” identifies the connection point
that remains live during a Black-out. In theMSB you will connect loads to this
output that are to continue operating during a black-out. Do not overload the
EPS circuit in the MSB with non-essential loads.
Earth connection must be made to the same switchboard as the power
cables
This system complies to IEC 62109-2 clause 13.9 for earth fault
monitoring.
**** There is no need for a separate neutral for EPS as the connection is
maintained internally to the SunRise system, see images below.
To connect the cables to the system, pass them through one of the outlets in the rear of the SunRise (use the glands provided which are designed to seal around 25mm flexible conduit). Secure the exposed end of the cable into the correct terminal block. Tighten with a flat-head screwdriver to 0.5N•m. The cable for Grid and EPS must be sized to support a maximum of 21.7A according to AS/NZS 3008.1.1:2017. All cables must be sized to appropriate Australian standards and not be less than 2.5mm².
MSB – Main switch board setup
After the installation of your single-phase SunRise, the Main
Switchboard of your property should look something like this. The two key
components related to your SunRise system are identified below:
- SunRise Meter: This measures the amount of power imported from, or exported to the grid
- “BATTERY SYSTEM CIRCUIT BREAKER”: Isolates the SunRise from the Switchboard, which is needed if for example work is to be done on the Switchboard. At all other times this switch remains on.
All cables must be sized to Australian standards and not be less than 2.5mm².
Earth-connection must be made to the same switch board as the power.
The SunRise system is compatible with Type A 30mA RCDs.
This system complies with IEC62109-2 clause 13.9 for earth fault monitoring.
The cable for EPS must be sized to support a maximum of 15.2A according to
AS/NZS 3008.1.1:2017
During a blackout the essential loads are supported by the SunRise system. The
non-essential loads will turn off until grid power is restored. Note that if
too many loads are on the essential circuit the battery could run flat quite
quickly or the backup circuit could become overloaded and turn off
temporarily.
4.3 Battery
The SunRise has been tested and commissioned at the RedEarth factory.
If the batteries have been removed for transportation/positioning, follow the
procedure below to correctly wire in the batteries.
This 1-phase SunRise system operates at 48Vdc nominal and batteries are
connected in parallel to increase capacity, maintaining 48Vdc nominal.
To attach the battery cable to the battery terminal, simply push it onto the
terminal until you hear a click.
To remove the battery cable, press the button on the side of the terminal and
pull it straight up with a slight wiggle.
Be careful to connect all the black cable plugs ONLY to the black
battery terminals on the Troppo batteries, and the red cable plugs ONLY to the
red battery terminals.
If the battery polarity is connected incorrectly, it will damage the SunRise
system.
Procedure to install batteries;
- Take the batteries out of the transport boxes and place them next to the SunRise system. Turn all the batteries on using the 2-pole switch on the top of each battery to confirm that they are all at a similar voltage (+/- 0.3 volts). Turn the batteries off again.
- Remove the front cross bar by undoing the 4x6mm nuts and install the Troppo batteries with the display towards the front. Put the first battery on the left side.
- Reinstall the cross bar to secure the batteries from falling over.
- Ensure the MAIN BATTERY BREAKER on the right side of the SunRise is turned OFF.
- Plug the battery cables into the batteries, being careful that red goes to red and black goes to black. Note: if the system is not full of batteries, then some of the battery cables will remain unconnected. These are available for connecting additional batteries in the future. This is what a battery-ready system really is.
- Turn the breakers on top of each battery on. You will notice some crossflow of electricity as the batteries balance with each other.
- The battery bank is now ready to be used. The MAIN BATTERY BREAKER can be turned on when you are ready to turn on the system.
4.4 Auxiliary remote Earth Fault Alarm option
The Sunrise has two small terminal blocks for the installation of an external
third-party alarm if desired. This is in addition to the audible alarm built
into the SunRise and the alerts received from the monitoring system.
The two terminals are on the same din rail as the main terminals and can be
identified by their smaller size, with the grey terminal set as the active and
the blue the neutral. This provides a dry contact which closes when active.
4.5 MSB & Meter
In the switch board, three tasks must be done for a complete Sunrise
Installation:
- Separation of the circuits into non-essential and essential circuits (EPS)
- Installation of the Sungrow meter and CT
- Installation of the double pole MCB breaker
If the property already has a PV system, when separating the circuits in
the MSB keep the pre-existing PV Inverter on the non-essential side. As
shown in the image below, when installing the Sungrow Meter, be sure to have
it on the non-essential side and have the CT clipped in between the Meter and
the Main Circuit Breaker (with the ARROW pointing towards the LOAD).
The communication between the meter and the SunRise system can be made with a
CAT5 or CAT6 cable. Using 2 of the strands from the CAT cable, connect one (A)
to the terminal 24 and the other (B) to terminal 25, as shown. Inside the
SunRise and underneath the inverter are the terminals that the other end of
this CAT cable will connect to. Strip the end of strands A and B and connect
them to the correct terminals.
For ease of comprehension, install the double pole breaker between the non-
essential and essential loads, as shown below. Then all the essential loads
can be put on the left-side of the SunRise system breaker.
Step 5 Understanding the Turn ON/SHUTDOWN Procedure
Before starting up the SunRise confirm the following items have been
completed,
- The PV cables have the correct polarity and are correctly connected to the MC4s provided.
- Grid and EPS cables are securely connected.
- Proper weatherproof seals on all cable entry glands of the SunRise
- The battery terminal connections on the Battery MCB are tight. (Check after transportation)
To Turn ON the unit for the first time, follow the steps below:
- Switch ON all battery breakers on top of each battery
- Switch ON the BATTERY SYSTEM D.C. ISOLATOR (label #2).
- witch ON the externally mounted SOLAR D.C. ISOLATOR (label #2).
- Switch the Bypass switch to Normal Operation (upwards = (I)).
- Turn ON all AC circuit breakers (label #1).
The Shutdown Procedure is the reverse of the “turn on” procedure and is shown below. This procedure can be found on the traffolyte label on the RHS of the unit.
- Turn OFF all AC circuit breakers (#1).
- Switch OFF the SOLAR D.C. ISOLATORS (#2).
- Switch OFF the BATTERY SYSTEM D.C. ISOLATOR (#3).
Step 6 Commissioning the system
The SunRise is commissioned and tested in RedEarth’s factory to confirm
correct operation of the system prior to shipment.
The RedEarth settings can be accessed via the Local-mode login on the
iSolarCloud APP. The installer will need to confirm inverter settings and
complete on-site parameter adjustments (e.g., Export limitation, connection to
the customer’s Wi-Fi or changing Australia A to B or C depending on where the
system is being installed in Australia).
This involves the following steps, which are detailed after this list.
- Power up the SunRise System. Note that the Sungrow takes up to 5 minutes to fully start-up when the system is initially powered up.
- Access the Sungrow inverter via the iSolarCloud APP, using local mode. Note that you can also use the display panel on the front of the inverter to adjust all the settings (installer login)
- Confirm the inverter initial configuration including regional settings and make any adjustments required.
- Test and confirm the operation of the whole system – including EPS mode (by turning off the main breaker of the house) and as well as PV generation and the By-pass switch.
Commissioning steps details are explained below.
-
1. Power up the SunRise system
Follow the procedure outlined in Step 5 “Understanding the Turn ON/Shutdown procedure” above.
While it is powering up, which can take 5 minutes, you can download the Sungrow APP (see step 2 below). Note: during powerup you will hear several relays clicking inside the system. -
Access the inverter via the iSolarCloud APP, using Local Mode.
Download the iSolarCloud APP and log into the Sungrow inverter Local Mode with your phone, via the onboard Wi-Fi, as explained below,
A more complete explanation is available in Chapter 8 of the Sungrow User manual available online at, https://info- support.sungrowpower.com/application/pdf/2022/07/20/SH3.6_4.6_5K-30%20UENVer18-202206.pdf
The display panel on the front of the inverter can also be used to adjust all the settings. Refer to Chapter 7 in the above manual. Note that the side panel of the SunRise needs to be removed to access the display.
a) Download the iSolarCloud APP onto your mobile (Android or iPhone)
b) Disconnect the 4G on your mobile. This is to avoid interference when accessing the Sungrow inverter’s Local mode.
c) Open the APP (iSolarCloud) and click on “Local Mode”.
d) Scan the QR code on the Sungrow Wi-Fi dongle as requested. Note that you will need to remove the side panel of the SunRise to get easy access to the base of the inverter, where the dongle is installed
e) Connect the Wi-Fi of your mobile phone to the Wi-Fi dongle of the Sungrow inverter which looks like this SG-B20*****XXXXf) The Local Access login details are shown at right. This is only for admin access by the installer.
The USER login details are shown in the User Manual.Account| admin
---|---
Password| pw8888 -
Confirm initial configuration and selection of regional settings and other settings at commissioning
** For compliance with AS/NZS 4777.2:2020 confirm that Australia Region A/B/C for the grid code is set correctly. Please contact your local grid operator for which Region to select. The default region set in the factory is Australia A unless specifically requested otherwise
Key settings to confirm are shown at right including;
o Country = Australia
o Power Company = Australia A (or B/C).
o Date & time (used for some control operations)
o Software version – confirm latest
The screen shots below from the iSolarCloud APP show the sequence to reach the System Parameters setting page where these key parameters can be confirmed or adjusted.
Make parameter adjustments as required. For additional information follow the procedure in Chapter 8 of the Sungrow User Manual, available at the link listed above, on how to make these alterations without compromising the existing configuration.After successful installation, the LCD screen on the front of the inverter will display as below. If dashes appear instead of numbers, the installation is incorrect and must be fixed. Generating a summary page of initial setting at end of commissioning:
To comply with the AS4777.2:2020 Section 7.3.8 (shown below) a summary of the final settings, as shown above, can be saved when you are in Local mode and logged in as the admin, and kept for future reference. In the future, anyone with the admin login details is also able to access this information to confirm the current settings via Local mode as well as remotely via the iSolarCloud webpage and APP.
7.3.8 Firmware
** The documentation shall provide instructions for viewing of the inverter firmware version and the selected regional settings and any variations to the default inverter settings in read-only mode. This is to prevent unauthorized modification of inverter settings. Documentation on the initial configuration and selection of regional settings and other settings at commissioning shall be provided to authorized persons.
Restricted information on accessing and changing the regional settings, other settings and firmware after initial configuration shall be provided to authorized persons only. -
Test the operation of the complete system prior to handover to the customer:
This includes confirming that the system;
is generating PV, charging the batteries, and supplying the loads
also, that the By-pass switch works, by actually switching to By-pass mode and confirming the operation.
also, confirm that the EPS function works as expected. This means that you MUST turn off the main house breaker and confirm the correct circuits are operating in the EPS mode. (e.g., fridge & home Wi-Fi)
NORMAL OPERATION:
In this operation mode the Sunrise will use solar, battery and grid depending
on the situation. All of the breakers and isolators should be on the ON
position and the By-pass Switch should be in the upwards position ( I ).
BYPASS OPERATION
In the By-pass operation mode, the system will completely bypass the
inverter and the grid will provide power directly to the EPS loads.
For this to happen, all breakers and isolators should be turned OFF and the
By-pass Switch should be in the downwards position ( II )
NOTE: The breaker in the switchboard (labelled “BATTERY SYSTEM CIRCUIT
BREAKER”) must always be tuned on.
NOTE: With the BYAPASS SWITCH In the middle position, all EPS circuit
will lose power. This is not a normal operating position for the BYPASS
switch. ![RedEarth ENERGY STORAGE SRS-1xx SunRise 1 Phase Home Battery System
- NORMAL](https://manuals.plus/wp-content/uploads/2023/08/RedEarth-ENERGY- STORAGE-SRS-1xx-SunRise-1-Phase-Home-Battery-System-NORMAL.jpg)
Fan Control Adjustment: The thermostat is located inside the unit next to
the fans. This automatically starts the fans once the temperature rises above
the set-point. This set-point can easily be adjusted with a small screwdriver.
It is set to 35⁰ Celsius in the factory.
DRM modes and operation: The SunRise system can operate in all DRM modes
from 0 to 8 as listed below. These are activated by adding a DRED device. The
image at right shows the DRM terminal within the Sungrow inverter. Contact
RedEarth if required.
The inverter provides a terminal block for connecting to a demand response
enabling device (DRED). The DRED asserts demand response modes (DRMs). The
inverter detects and ini-tiates a response to all supported demand response
commands within 2s. The following table lists the DRMs supported by the
inverter.
table 3-1 Demand Response Modes (DRMs)
Mode | Explanation |
---|---|
DRMO | The inverter is in the state of “Turn off’. |
DRM1 | The import power from the grid is O. |
DRM2 | The import power from the grid is no more than 50 % of the rated power. |
DRM3 | The import power from the grid is no more than 75 % of the rated power. |
DRM4 | The import power from the grid is 100 % of the rated power. but subject |
to the constraints from other active DRMs.
DRM5| The feed-in power to the grid is O.
DRM6| The feed-in power to the grid is no more than 50 % of the rated power.
DRM7| The feed-in power to the grid is no more than 75 % of the rated power.
DRM8| The feed-in power to the grid is 100 % of the rated power, but subject
to the constraints from other active DRMs.
The DRED may assert more than one DRM at a time. The following shows the priority order in response to multiple DRMs.
Multiple Modes | Priority Order |
---|---|
DRM1…DRM4 | DRM1 > DRM2 > DRM3 > DRM4 |
DRM5. .DRM8 | DRMS > DRM6 > DRM7 > DRMS |
Step 7 Activating Remote Monitoring & Communications
There are currently three options to enable remote access to the SunRise.
- Wi-Fi connection to customer’s internet (signal strength dependent)
- Hardwire to customer’s LAN (if feasible)
- Install RedEarth’s 4G modem system – “RedPi” (via QR code on the outside of the SunRise system. (See User manual for details)
The 3rd option requires positioning an antenna in a good 4G reception area. If installing in a closed area like a Shed, remember to check the 4G signal with the shed doors closed as this will affect the strength of the signal, otherwise position the supplied antenna outside. Pass the antenna cable through the 16mm hole in the SunRise. Use the supplied 16mm gland to seal around the cable.
Remote monitoring and control are then available via RedEarth’s EMU APP once the customer completes registration.
Step 8 Customer Handover
Handover to customer
- Confirm that the customer has downloaded the RedEarth EMU APP (or Switchdin APP) and is logged-in, otherwise provide the customer’s contact details to RedEarth to complete onboarding the customer at a later time.
- Explain to the customer how the system operates and demonstrate what happens during an outage, by turning off the Main breaker to the house and observing the EPS operation. Confirm that the correct circuits are supported. (Note that there will be delay of up to 1 minute before the EPS circuits activate after the Main breaker is opened)
- Also demonstrate the operation and effect of the By-pass switch
- Obtain any customer signatures required for claiming STC’s Finally, provide the required documentation to RedEarth. This also ensures the full RedEarth warranty applies.
Services & Options available for the SunRise
As a RedEarth SunRise system owner you have the choice of joining our customer
community. You just need to register your contact details with RedEarth.
You can receive regular relevant communications from RedEarth.
Other benefits include
- Access to RedEarth’s PPP (Private Power Plant) and the stream of financial benefits available to the customer
- Remote monitoring service if required. Includes recommendation for system upgrades.
- Additional batteries for system expansion
- Extended warranty option
In addition to the SunRise system RedEarth offers other systems for both on- grid and off-grid applications. Contact RedEarth for more information.
Appendix A – Single Line Diagrams
Single Line Diagram – Power Single Line Diagram – Communication
Single Line Diagram – Main Switchboard
Appendix B – Technical Specifications
Technical Specifications – SunRise System
| PV Input
---|---
MPP Voltage Range| | 125Vx — 560Vx
Max. Input Voltage (Vac)| | 600Vx
Max. Input Current| | 11/11Acc
Short Circuit Current (Ix)| | 15/15Ax
| Battery
Battery type| | Troppo-4841 Lithium-Ion Phosphate (or Battery Ready) *
Nominal Ener Cap acit y
gy| | 4.1kWh per Troppo-4841 battery
(4.1/8.2/12.3/16.4/20.5/24.6) **
| AC Input and Output
Rated AC Voltage| | 230V
Rated AC Frequency| | 50Hz
Rated Output Apparent Power| | 5000VA
Max. Input/Output Power| | 5000VA
Max Input/Output Current| | 21.7AAc
| EPS Output
Max. output power (Batt. + PV)| | 5000VA
Max. output power (Batt. Only)| | 3000VA
Max output current (Batt. Only)| | 13AAc
Supported DRM| | DRM 0 to 8 inclusive
Safety Class/Enclosure| Class I / IP43
---|---
Ambient Temperature| -25°C … +50°C
Overvoltage Category| III (MAIN), II (PV)(BATTERY)
Device Voltage Classification| DVC-C
* The SunRise system is designed to only use the RedEarth Troppo-4841
lithium-ion battery (LFP). The SunRise system can also be supplied without any
batteries. These can be installed at a later date.
The Nominal Energy Capacity depends on the number of Troppo-4841 batteries
installed in the SunRise system.
The model numbers reflect the total battery capacity installed in the system.
Technical Specifications – SunRise System**
“1: AS4777 . 4990 W, 4990 VA
°2: ASS777 : 21.7 A
“3: AS4777 : 34.84 ©2022 Sungrow Pewer Supply Co, Ltd. All rights reserved.
Subject to change without notice, Version 18
Electrical Charachadstics Nominal capacity | 4.IWh/79.8Ah |
---|---|
Useable capacity | 3 69kWh (90% of nominal capacity) |
Nominal DC voltage | 512V |
Maximum discharge current | 63A (Limited by circuit breaker) |
Lifetime continuous discharge current | 40amps (C21 |
Maximum charge current | 63A (Limited by circuit breaker) |
Lifetime continuous charge current | 16A |
Maximum power on discharge (kW) | approx 3Kw |
Recommended operating voltage range | 48.0 – 57.6Vdc |
Charge/discharge cycles of certified 3 80OrnAh cells at 1C rate (to 80%
residual capacity)| 2.00001—% DoD/4,00048096 DoD/
7.000050% DoD025’C operating temp.
Pro)ectedMWh delivered over battery lifetime| 13.08 MWh at 8094 DoD
Round trip efficiency| >96%
Parallel connection| from 4.1kWh to 100kWh.
Series connection| Not designed for series connection
Expected calendar life 425•C| >10 years when used as per warranty terms
Envinanmental Charactedstics
Operating temperature range – discharging| Discharge -20-C to 60•C (•/-5•C)
Operating temperature range – charging| Charge 0″C to 50″C (•-5″C)
Cooling
Physical characteditke Battery mounting options| Natural convection
In a standard 19′ rack of horizontally.
vertically or on either side
Battery terminal connections| Amphenol surlok 100A non keyed
Battery circuit breaker| 2-pole 63A 36OVDC (K-Curve)
Battery diensions| 725mm D x 438mm W x 88mmH
Battery weight| 42 5kg
IP rating
Sabty parameters and certification Short-circuit current| IP20
400 amps per battery In parallel
Lithium compostitlon| Lithium ferro phosphate (LiFePO4 or LFP)
Cerification – TPOPPO 4841 battery| IEC 62619 2017 & CEC listed
Cerlflcation – 1.IFe PO4 3.800m Ah cell| IEC62619.2017.UN38.3
Clean Energy Council (CEC) listing
Battery management system (BMS) protection settings| Yes
LiFePO4 (165)
Battery type and number of cells In series
BMS over-volt cut off| 59.4Vdc
BMS under-volt cut off| 40V
Charging over-current protection| 80.
Discharge over-current protection (2 levels)| 250.60A(20-400m5) &
400.100A00-100mS)
Inverter capacitors – starting capability| 14.600uF
High temperature – discharge protection| 60t5″C
High temperature – charge protection| 50t5’C
Low temperature – discharge protection| -20t5°C
Low temperature – charge protection| 0.5 C
Cell balancing method| Passive equalisation at 57.6Vdc
Short-circuit Current (ISC)
1x| 0.4 kA
2x| 0.8 kA
3x| 1.2 kA
4x| 1.6 kA
5x| 2.0 kA
6x| 2.4 kA
SunRise 1ph NS Install Version 1.4
Issue Date 6/03/2023
RedEarth Energy Storage Ltd
15 Fienta Place
Darra, Brisbane QLD 4076
Australia
Tel: 1800 733 637
Email: support@redearth.energy
Web: www.redearth.energy
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>