SpaceLogic KNX DALI Gateway Basic REG-K/1/16/64
Instruction Manual
Art. no. MTN6725-0003
SpaceLogic KNX DALI Gateway Basic
For your safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The safe electrical installation must be carried out only by skilled
professionals. Skilled professionals must prove profound knowledge in the
following areas:
- Connecting to installation networks
- Connecting several electrical devices
- Laying electric cables
- Connection and setup of KNX networks
- Connection and setup of DALI networks
- Connection and setup of emergency lighting systems
- Safety standards, local wiring rules, and regulations
Failure to follow these instructions will result in death or serious injury.
Getting to know the Gateway
The KNX DALI Gateway Basic REG-K/1/16/64 (referred to below as the gateway)
connects the KNX bus to the DALI bus. Lights with DALI electronic ballasts can
therefore be integrated into a complete KNX system in the form of a subsystem
and operated using the wide range of KNX devices available. The device
converts switching and dimming commands of the connected KNX system into
corresponding DALI telegrams or status information from the DALI bus into KNX
telegrams.
The electronic ballasts can be switched, dimmed or set to a defined value in
16 groups for each gateway.
Notes
-
Single Master Application Controller (EN 62386-103). The device may only be operated in DALI lines with electronic ballasts connected and not with other DALI control units within the line (no multi-master operation).
-
The power required for up to 64 connected electronic ballasts is supplied directly from the gateway. No additional DALI power supply is required, nor is this permissible.
-
The special interface for the configuration of the DALI segment is designed as a DCA (Device Control App) for the ETS5.
Note that, in addition to the product database (knxprod file), a corresponding ETS app (etsapp file) is also installed. Both files are available in the KNX
online catalog and on the manufacturer’s website. -
DALI devices for single-battery emergency lights of device type DT-1 can be read by the gateway and switched and operated via DALItelegrams if required. DALI commands for starting and reading test results are not supported.
Product Features
-
Addressing 16 DALI groups
-
Flexible DALI commissioning concept in ETS5
-
Colored light control with the support of ballasts of device type 8
-
Colored light control depending on ballast subtype:
– Colour temperature (DT-8 subtype Tc)
– XY color (DT-8 subtype XY)
– RGB (DT-8 subtype RGBWAF)
– HSV (DT-8 subtype RGBWAF)
– RGBW (DT-8 subtype RGBWAF)
– DT-8 subtype PrimaryN is not supported -
Support of timer programs for control of groups by value and/or color
-
Various operating modes for groups such as continuous operation, night mode, staircase mode
-
Integrated operating hours counter for each group, with an alarm once the end of the service life has been reached
-
Individual fault detection with objects for each individual light/electronic ballast
-
Complex evaluation of faults at group/device level with fault number and fault rate calculation
-
Fault threshold monitoring with individually adjustable threshold values
-
Scene module for the comprehensive programming of scenes
-
Quick exchange function for simple replacement of individual defective electronic ballasts
-
Manual operation of group and broadcast telegrams via operating buttons on the device
-
Signaling of fault states and statuses via LEDs on the device
Starting up the gateway
Several steps are necessary to start up the gateway fully:
- Wire the DALI segment
- Connect the gateway to DALI and KNX bus
- Connect the gateway to the mains voltage
- Load the ETS application program (.knxprod) and install the ETS app (.etsapp)
- Configure the ETS parameters and objects
- Assign the ETS-DCA DALI groups
- Start up the ETS-DCA DALI
- ETS download of application
For a precise description of the start-up procedure, read these operating instructions and the latest application description.
It is installed on a TH35 DIN rail acc. to EN 60715, with the bus connection made via a bus connecting terminal. Network and DALI cables are connected via screw terminals on the device.
Connections, displays, and operating elements
The appliance connections as well as the programming button and programming
LEDs required for KNX commissioning can only be accessed in the
distribution board when the cover is removed.
Manual mode buttons can be operated and indicator LEDs read with the
distributor cover closed.
A KNX bus connecting terminal
B Programming button, normal/programming mode
C Programming LED, normal/programming mode
D DALI output terminal
E Operating buttons with a status LED (red) for each group (1-8 and 9-16) for
manual mode (group operation/group status, broadcast and service functions)
F Mains connection
G Operating button with status LED (RGB) for activating a manual mode
Further information on operation, operating modes, and troubleshooting can be
found in the application description.
Mounting the Gateway
-
Position the gateway on the DIN rail.
-
Attach the connecting cable for the DALI bus to the lower left terminals.
The DALI control cables can be routed in a 5-core cable together with the wires for conducting mains voltage (single basic insulation is sufficient) in accordance with EN 60929.
Ensure they are labeled clearly, however. A maximum cable length of 300 m must not be exceeded for the entire DALI installation of a segment (recommended cross-section 1.5 mm 2 ). -
Connect the mains voltage.
-
Connect KNX.
**** Double basic insulation must be used between the KNX installation and the mains voltage!
For this purpose, additionally, insulate the wires of the KNX cable as far as the bus connecting terminal using the enclosed shrink hose.
Once all connections are complete and the supply voltage has been switched on,
the DALI line can be commissioned and programming carried out with the
ETS.
Please refer to the application description in order to perform these
operations.
Technical data
Supply voltage: | 100-240 V AC/DC, 50-60 Hz |
---|---|
Power consumption: | max. 9 W |
Power supply from KNX: | 24 V DC (SELV), approx. 5mA |
Operating elements: | |
Programming button: | Normal/programming mode |
1 Manual mode button: | Activating manual mode |
8x Group buttons: | Operation of the individual groups in manual mode |
Display elements: |
Programming LED,
red:| Normal/programming mode
LED RGB:| Manual mode and fault messages
8x LED, red:| Group statuses and fault messages
DALI:|
Outputs:| 1
Type:| Single Master Application Controller (EN 62386-103) From firmware
version 0.2.6 the gateway is certified according to EN
62386-101/103 ed2 -> DALI-2 compatible
Number of electronic
ballasts:| max. 64 ECGs according to EN 62386? 101 ed1 and ed 2
Output voltage:| typically 16 V DC, short-circuit proof max. 250 mA, basic
insulation (no SELV)
Wire cross-section:| min. 1.5 mm²
Output current:| max. 250 mA, min. 128 mA
Shutdown delay:| 600 ms after DALI short circuit shutdown occurs
Start-up attempt after
shutdown:| 5 s after short-circuit detection
Connections:|
Supply voltage:| Screw terminal 3x 12.5 mm 2 single-core and multi-core
DALI bus:| Screw terminal 2x 12.5 mm 2 single-core and multi-core
KNX:| Bus connecting terminal
Ambient operating temperature:| -5 °C to +45 °C
Relative humidity
(non-condensing):| 5% to 93%
Degree of contamination:| 2
Overvoltage category:| III
Device width:| 4 modules = approx. 72 mm
Schneider Electric -Contact
Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92500
France
If you have technical questions, please contact the Customer Care Centre in
your country.
se.com/contact
UK Representative
Stafford Park 5
Schneider Electric Limited
Telford, TF3 3 BL, UK
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>