Schneider Electric BDL16050 Molded Case Circuit Instruction Manual

June 13, 2024
Schneider Electric

Schneider Electric BDL16050 Molded Case Circuit

Schneider-Electric-BDL16050-Molded-Case-Circuit-PRODUCT-
IMG

Circuit Breakers and Automatic Switches

DOCA0094EN / DOCA0 95EN

  • Scan the QR code on the product for additional product information.

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-1

Before starting the installation read and understand all instructions. Retain instructions for future use.

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • The product has been designed for environment A (Class A, IEC 60947-1).
  • Use of this product in environment B (Class B, IEC 60947-1) may cause unwanted electromagnetic disturbances in which case the user may be required to take adequate mitigation measures.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
  • All pertinent state, regional, and local safety regulations must be observed when installing and using this product.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, NOM 029-STPS or local equivalent
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors, and covers before turning on power to this equipment.
  • Beware of potential hazards, and carefully inspect the work area for tools and objects that may have been left inside the equipment.
  • Failure to follow these instructions will result in death or serious injury.

WARNING: This product can expose you to chemicals including DINP, which is known to the State of California to cause cancer, and DIDP which is known to the State of California to cause birth defects or other reproductive harm. For more information go to:
www.P65Warnings.ca.gov.

Necessary Tools

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-2

Before Working on Equipment

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Turn off or use push-to-trip button to trip circuit breaker.
  3. Use a properly rated voltage sensing device to confirm power is off.

Safety Clearances

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Install circuit breaker so minimum clearance distance to grounded metal is maintained.
  • Failure to follow these instructions will result in death or serious injury.

Minimum Clearances

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-4

Standard (80% rated current)

A B C
14.6 in. 371 mm 8.5 in. 216 mm 3.16 in. 80 mm

100% rated current

  A B C
3P 18.13 in. 461 mm 8.63 in. 219 mm 4.13 in. 105 mm

Painted sheet metal/Bare sheet metal

  D E F D E D
No accessories 1.18 in. 0.19 in. 0 1.57 in. 0.19 in. 0.19 in.
Nessun accessorio 30 mm 5 mm 0 40 mm 5 mm 5 mm
Interphase barriers 0 0 0 0 0 0.19 in.
Separator 0 0 0 0 0 5 mm
Long terminal shield 0 0 0 0 0 0.19 in.
Copertura morsettiera lunga 0 0 0 0 0 5 mm

Compression Lug Safety Clearance

  • If G < 0.37 in. (< 9.5 mm) : an insulating screen or long terminal shield is required.

Live Part Minimum Safety Clearances Required

  • Live parts.
  H ≤ 2.36 in. (60 mm) H > 2.36 in. (60 mm)
I J I
V ≤ 600Y/347 V (UL) 690 V (IEC) 7.87 in. 200 mm 3.94 in. 100 mm
120 mm 2.36 in. 60 mm

Installation

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-7

DIN Rail

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-8

PLEASE NOTE

  • For DIN rail mounting, cable cross-sectional area should not exceed 1/0 AWG (50 mm²).

Door Cutout

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-9

Wiring

EverLink Lugs Connections

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-10

  1. For IEC applications, only copper wires allowed

Mechanical Lug Connections

NOTICE

HAZARD OF OVERHEATING

  • Do not allow wire strands to get caught in wire binding screw threads.
  • Failure to follow these instructions can result in equipment damage.

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-11

  1. For IEC applications, only copper wires allowed.

Compression Lugs

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-12

PowerPacT B DC Wiring Diagrams

Grounded Negative1

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-13

Grounded Middle Point

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-14

Ungrounded Source

Schneider-Electric-BDL16050-Molded-Case-Circuit-FIG-15

Circuit Breaker Removal

  1. Turn off all power supplying this equipment before working on or inside equipment.

  2. Turn off or trip circuit breaker before removal.
    Make sure the circuit breaker is in the open (O) position or in the trip ( ) position.

  3. Use a properly rated voltage sensing device to confirm power is off.

  4. Remove circuit breaker in reverse order of installation.

© 2019-2023 Schneider Electric All Rights Reserved Schneider Electric, Square D, and PowerPacT are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other trademarks are the property of their respective owners.

Schneider Electric Limited

Schneider Electric USA, Inc

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals