Intermatic’s IOS-DOV-DTD-WH dual technology 0-10 V dimming occupancy sensor can turn lights ON and OFF based on occupancy and allow the user to increase or decrease the lighting level. It combines the benefits of passive infrared (PIR) and ultrasonic occupancy detection technologies.
SPECIFICATIONS
Input Voltage | 120-277 VAC, 50/60 Hz |
---|---|
Electronic Ballast | 600 VA, 120 VAC; 1385 W, 277 VAC |
Tungsten | 1000 W, 120 VAC; 1385 W, 277 VAC |
Standard Ballast | 660 VA, 120 VAC; 1100 VA, 220 VAC; 1520 VA, 277 VAC |
Class 2 Dimming Output | 0-10 VDC, 120 mA maximum current sink |
General Use | 12 A, 120-277 VAC |
Resistive | 10 A, 125/250/277 VAC |
Motor | 1/6 HP, 120/240 VAC |
Coverage | • PIR: up to 35 ft. (10.67 m) |
• Ultrasonic: up to 27 ft. (8.23 m)
LED Indicators
- Red LED Blinking: PIR sensor detects motion
- Green LED Blinking: Ultrasonic detects motion
Manual Up / Down Buttons:
- To turn ON the light, press the up arrow when the light is OFF. To turn OFF the light, press the down arrow when the light is ON.
- To adjust the light level, Press and hold the up arrow to increase light level and release at desired light level. Press and hold the down arrow to decrease light level and release at desired light level.
INSTALLATION
- Always switch OFF the Electrical power before installing the sensor and make sure the sensor ratings are appropriate for the luminaire being controlled.
- Wire the sensor according to the wiring diagram. (Refer To Diagram 1)
- Attach sensor to junction box with 2 screws. (Refer To Diagram 2)
- Attach Panel cover and wall plate. (Refer To Diagram 2)
Diagram 1 – Wiring Diagram Diagram 2 –
Installation Diagram 3 – Traveler Wiring Diagram
*Note: Ground wire is REQUIRED for Multi-Way Wiring.
DIP SWITCH PROGRAMMING
Time Delay
Time Delay: The time delay setting assigns the duration for the lighting
to stay ON after no movement is detected. The time delay is controlled by DIP
switches 1 through 3. Refer to the following table to set the time delay.
Time Delay | DIP1 | DIP2 | DIP3 |
---|---|---|---|
30 sec | Off | Off | Off |
2 min | On | Off | Off |
4 min | Off | On | Off |
8 min | On | On | Off |
10 min | Off | Off | On |
15 min – Default | On | Off | On |
20 min | Off | On | On |
30 min | On | On | On |
Occupancy and Vacancy Mode Selection (DIP 4)
Use DIP 4 to select Occupancy or Vacancy mode
DIP Switch | Mode |
---|---|
ON | Occupancy (Auto On) |
OFF | Vacancy (Manual On) |
Dimmer Synchronization (DIP 5)
The DIP 5 controls the Dimmer Synchronization mode when the multi-way function
(Diagram 3) is used. If you turn DIP 5 ON, the second sensor can turn the
light fixture ON/OFF and control the dimming light level. If you turn DIP 5
OFF, the second sensor can only turn the light ON/OFF. (If using one sensor,
leave the setting in the ON position)
Walk-Through Mode (DIP 6)
Turn DIP 6 ON to enable “walk through mode”. In this mode, the load will be
turned ON for 2 minutes when motion is detected. If no motion is detected
after 90 seconds, the load will be turned OFF 30 seconds later. If a motion is
detected after 90 seconds, the load will refer to the Time delay setting.
Ambient Light Level (DIP 7)
To set the ambient light level, turn ON DIP 7 and wait for 30 seconds for the
light level to calculate the current ambient light in the room. Once
programmed, If there is greater ambient light than the setting the light will
not turn on. If there is less ambient light than the setting the light will
activate.
Ultrasonic Enable/ Disable (DIP 8)
Turn DIP 8 ON to enable Ultrasonic Technology. Turn DIP 8 OFF to disable
Ultrasonic Technology.
PIR/ULTRASONIC SENSITIVITY AND MODE SELECTION
Ultrasonic Sensitivity
Turn the variable resistor to adjust the ultrasonic sensitivity. It can be
adjusted from 20%
to 100%.
PIR Sensitivity
Turn the variable resistor to adjust PIR sensitivity. It can be set from 60%
to 100%.
Mode Selection
The mode selection switch is used to select ON, Auto or OFF mode
- ON: Lights Always ON
- Auto: Detection determines when the lights turn ON and OFF (Occupancy or Vacancy mode)
- OFF: Lights Always OFF
LIGHT LEVEL PROGRAMMING
High- Trim, Low-Trim and Initial On Light Level Activation Programming
Before setting the 3 light levels, you must enter the set/program mode. Put
the mode selection switch to the OFF position and press the UP and Down button
together. The sensor is in set/program mode when there is a solid Red LED
illuminated. To pick whichsetting you would like to change click the up-arrow
button until you see the Red LED blink in accordance to which setting you
would like to change. (1 Blink – High-Trim, 2 Blinks – Low-Trim, 3 Blinks –
Initial On Level)
A. High-Trim Setting:
When the Red LED flashes one time per period, press the “up” and “down” button
together to start to set the High-Trim level. Click the up arrow the number of
times in accordance with the chart below for your desired setting. Once
complete press the “up” and “down” button’s together to save. If complete with
all programming needs return sensor to auto mode.
Low End Trim | Number of clicks on Down Arrow to set |
---|---|
80% | 1- click |
90% | 2- click |
100% | 3- click -Default |
B. Low-Trim Setting:
When the Red LED flashes two times per period, press the “up” and “down”
button together to start to set to the Low-Trim level. Click the down arrow
the number of times in accordance with the chart below for your desired
setting. Once complete press the “up” and “down” button’s together to save. If
complete with all programming needs return sensor to auto mode.
Low End Trim | Number of clicks on Down Arrow to set |
---|---|
10% | 1- click -Default |
20% | 2- click |
30% | 3- click |
C. Initial On Activation Light Level Setting:
When the Red LED flashes three times per period, press the “up” and “down”
button together to start set the Initial On Activation Light level. Click the
up arrow the number of times in accordance with the chart below for your
desired setting. Once complete press the “up” and “down” button’s together to
save. If complete with all programming needs return sensor to auto mode.
Initial On Activation Level | Number of clicks on Up Arrow to set |
---|---|
10% | 1- clicks |
20% | 2- clicks |
30% | 3- clicks |
40% | 4- clicks |
50% | 5- clicks – Default |
60% | 6- clicks |
70% | 7- clicks |
80% | 8- clicks |
90% | 9- clicks |
100% | 10- clicks |
NOTE: You cannot program the initial on activation light level setting
below the selected Low-Trim or above the selected High-Trim. (Example: High-
Trim is set at 90%. Initial On Activation cannot be higher than 90%, Low-Trim
is set at 30%, Initial On Activation cannot be below 30%) (If error, LED will
blink constant red)
D. Factory/Default Reset:
If you want to reset the sensor to factory settings, put the mode switch to
the “ON” position and press the “Up” and “Down” arrows together and hold. The
Red LED will flash 2 times and the sensor will reset to the factory/default
settings. The factory/default settings are as follows: (High-Trim: 100%, Low-
Trim: 10%, Initial On: 50%)
5-YEAR LIMITED WARRANTY
Warranty service is available by either (a) returning the product to the
dealer from whom the unit was purchased or (b) completing a warranty claim
online at www.intermatic.com.
This warranty is made by: Intermatic Incorporated, Customer Service 1950
Innovation Way, Suite 300, Libertyville, IL 60048. For warranty service go to:
www.Intermatic.com or call
815-675-7000.
INTERMATIC INCORPORATED
1950 Innovation Way, Suite 300
Libertyville, Illinois 60048
www.intermatic.com
158–02530
Documents / Resources
|
INTERMATIC IOS-DOV-DTD-WH Dual Technology 0-10 V Dimming Occupancy
Sensor
[pdf] Instruction Manual
IOS-DOV-DTD-WH Dual Technology 0-10 V Dimming Occupancy Sensor, IOS-DOV-DTD-
WH, Dual Technology 0-10 V Dimming Occupancy Sensor, Dimming Occupancy Sensor,
Occupancy Sensor, Sensor
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>