hager ARR906U RCBO with Dangerous Arc Detection Instruction Manual

June 12, 2024
hager

hager ARR906U RCBO with Dangerous Arc Detection

ARR906U

  • RCBO with dangerous arc detection 1M 6A B 6kA

ARR910U

  • RCBO with dangerous arc detection 1M 10A B 6kA

ARR916U

  • RCBO with dangerous arc detection 1M 16A B 6kA

ARR920U

  • RCBO with dangerous arc detection 1M 20A B 6kA

ARR925U

  • RCBO with dangerous arc detection 1M 25A B 6kA

ARR932U

  • RCBO with dangerous arc detection 1M 32A B 6kA

Information

  • For more information, scan the QR-Code on the product.
  • For further technical information and for installation in Hager Distribution Board, review the Installation Guidance Notes available in the products download section on Hager website.

Safety notice

  • The AFDD (Arc Fault Detection Device) may only be installed, connected and serviced by a qualified electrician. Before mounting, the AFDD must be checked for external damage.
  • If any damage or other defect is found, the device must not be mounted.
  • The national regulations, safety regulations and installation standards BS 7671 must be observed. RCD characteristics 5 Idn compliance (according to table 1 & 2 BS EN 61009-1) for RCDs.

Design and layout of the device

hager-ARR906U-RCBO-with-Dangerous-Arc-Detection-FIG-1

  1. Test button
  2. LED status display
  3. Handle
  4. Yellow flag
  5. Mounting metal rail clip

Function

  • RCBO-AFD in 1 module ARRxxxU is a single device consisting of a miniature circuit breaker (MCB) unit and residual current detection (RCD) unit with integrated Arc fault detection (AFD) unit (3 in 1).
  • The AFDD mitigates the risk of a fire in the final electrical circuits of a fixed installation due to arcing fault currents, which under certain conditions present a fire ignition risk due to dangerous arc fault.

Tools

Installation and electrical connection

DANGER!

  • Electric shock when touching live parts! Electric shock can lead to death!
  • Before commencing work ensure suitable isolation procedures have been followed.

Mount device

  • Open the rail clip.
  • Insert the AFDD until it is connected.
  • Press the metal clamp down.
  • The AFDD is fixed on the rail.

Connect device

Wiring diagram

Disassembly

hager-ARR906U-RCBO-with-Dangerous-Arc-Detection-FIG-7

Testing
The test button T is used for testing the device. The AFDD should trip following a short press of the test button. Following this the device can be switched on again.

Test device

ATTENTION!

  • Insulation tests at 500V DC may damage this product!
  • Do this test only when the handle is off.
  • If the handle is OFF you don’t have to disconnect the cable.

Notice

  • The AFDD function must be tested after installation.The supply voltage must be present.

  • The RCBO-AFDD must trip within one second. If the device does not trip, it must be replaced by a competent electrician.

  • Short press the test button T. The RCBO-AFDD tripped, i.e. the circuit must switch off.

Notice
If the AFDD does not trip, check the status of the LED (table 1).

LED status for troubleshooting

  • The handle is in the OFF position.
  • Keep the test button T pressed, to open the color code.

hager-ARR906U-RCBO-with-Dangerous-Arc-Detection-FIG-11

Table 1: LED status display for standard troubleshooting.

Notice
In case of an internal failure, replace the AFDD and contact Hager technical support.

Connection to mobile phone

  • A mobile phone (iphone, operating with IOS14 or above, or Android, operating with Android 7 or above) is required to use those functions.

Notice

  • Using the connected functions with your mobile phone requires activating network functions (Bluetooth, WiFi) and to accept the application terms of use & privacy notice.
  • Only Bluetooth 4.2 or above is supported.
  • Install the Hager Pilot mobile application on your mobile phone.
  • Follow further instructions on the mobile application.

LED status for Bluetooth® connection

  • The handle is in the ON position.
  • Press the test button T for 5 seconds to activate bluetooth mode.

hager-ARR906U-RCBO-with-Dangerous-Arc-Detection-FIG-13

Table 2: LED status display for Bluetooth® connection

EU and UKCA Declaration

Hereby, Hager Electro SAS , declares that the AFDD products are in compliance with SI 2017/1206 Radio Equipment Regulations 2017 and with radio emission directive 2014/53/EU  Operating frequency band 2.4 to 2.483 GHz.  Maximum radio frequency power 10mW. Declarations of conformity can be downloaded on www.hager.com.