INTERMATIC IOS-DSIF Occupancy Sensor Switch Instruction Manual

June 12, 2024
Intermatic

INTERMATIC logo

INTERMATIC IOS-DSIF Occupancy Sensor Switch

Ratings:

  • Input Voltage: 120 VAC, 60 Hz
  • Electronic Ballast (LED): 500 VA
  • Tungsten (Incandescent): 500 W
  • Fluorescent / Ballast: 500 VA
  • Motor: 1/8 HP
  • Time Delay: 15 Sec – 30 Min
  • Light Level: 30 Lux – Daylight
  • Operation Temperature: 32° – 131° F / 0° – 55° C No minimum load required

WARNING Risk of Fire, Electrical Shock or Personal Injury

  • Turn OFF power at circuit breaker or fuse and test that the power is OFF before wiring.
  • To be installed and/or used in accordance with appropriate electrical codes and regulations.
  • If you are not sure about any part of these instructions, consult a qualified electrician.
  • Use this device only with copper or copper clad wire.
  • INDOOR USE ONLY

INSTALLATION INSTRUCTIONS

Description
The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load ON and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turns OFF automatically. The sensor switch has one relay (equal to single pole switch), it also includes Ambient Light Level Sensor.

Coverage Area
The coverage range of the sensor switch is specified and illustrated in Figure

  1. Large objects and some transparent barriers like glass windows will obstruct the sensor’s view and prevent detection, causing the light to turn off even though someone is still in the detection area.

LOCATION/MOUNTING
Since this device responds to temperature changes, care should be taken when mounting the device.
DO NOT mount directly above a heat source, in a location where hot or cold drafts will blow directly on the sensor, or where unintended motion will be within sensor’s field-of-view.

INTERMATIC IOS-DSIF Occupancy Sensor Switch 1

INSTALLATION

  1. Connect lead wires as shown in WIRING DIAGRAM (see Figure 2): Black lead to Line (Hot), Red lead to Load wire, White Lead to Neutral wire, Green lead to Ground.

  2. Gently position wires in wall box, attach sensor switch to the box.

  3. Mount device “TOP” up.

  4. Restore power at circuit breaker or fuse, wait one minute.

  5. Remove the small cover plate. (Illustrated as Figure 3.)

  6. Locate the adjustment knobs on the control panel to perform test and adjustments.
    (Illustrated as Figure 4.)

  7. Replace the small cover plate after testing and adjusting.

  8. Attach the wallplate.
    NOTE: If twist on wire connector is provided, use to join one supply conductor with one 16 AWG device control lead.

INTERMATIC IOS-DSIF Occupancy Sensor Switch 2

ADJUSTMENT

Time Delay Knob
Default position: 15 Seconds (Test mode)
Adjustable: from 15 Seconds to 30 Minutes (clockwise)

Sensor Sensitivity Range Knob
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4)
Note: Turn clockwise for larger rooms. Turn counter clockwise to avoid false alerts in smaller rooms or near doorway or heat source.
Ambient Light Level Knob: Default position: Daylight (100% at position 4)
Adjustable: Daylight to 30 Lux (Counter clockwise)

OPERATION
Band Switch

Mode Position Description
OFF LEFT Circuit is permanently opened (switched off)
AUTO Center Occupancy Mode:

Automatic ON when occupancy is detected. Automatic OFF after the set time delay.

ON| RIGHT| Load stays ON always.

INTERMATIC IOS-DSIF Occupancy Sensor Switch 3

Push-button:
As illustrated in Figure 5, the Load stays OFF when the button is pushed in and locked. (switched OFF) As illustrated in Figure 6, the Load turns ON after the button is pressed and released. The sensor switch stays at the AUTO Mode until the button is pressed OFF next time.

INTERMATIC IOS-DSIF Occupancy Sensor Switch 4

TROUBLESHOOTING

For proper operation, the Sensor Switch has to consume power from hot and Neutral. Therefore, a Secured Neutral Wire is required.

Initial run
The Sensor Switch needs initial run within one minute. During the initial run, the load might turn On and Off several times.
The Time Delay knob is set to 15 seconds default, do not adjust until initial run is finished and proper operation function is confirmed. The load is flashing frequently.

  1. It can take up to one minute for initial run.
  2. Check the wiring connections, especially the Neutral Wire.

The Load does not turn ON without LED flashing or LED flashing regardless of motion.

  1. Verify the Mode is set to On (for IOS-DSIF); push and release the button (for IOS-DPBIF). If the load does not turn On go to step 2.
  2. Verify the Sensitivity Range is on high.
  3. Check the wiring connections.

The Load does not turn ON while LED is flashing and motion is detected

  1. Check if Ambient Light Level is enabled by covering the lens by hand.
  2. Verify the Mode is set to ON (for IOS-DSIF); push and release the button (for IOS-DPBIF). If the load does not turn On go to step 3.
  3. Verify the Sensitivity Range is on high.
  4. Check the wiring connections.

The Load does not turn Off

  1. Verify that the Mode is ON. (for IOS-DSIF)
  2. There can be up to a 30 minute time delay after the last motion is detected. To verify proper operation, turn the Time Delay Knob to 15s (Test Mode), make sure there is no motion (no LED flashing). The Load should turn Off in 15 seconds.
  3. Check if there is a significant heat source mounted within six feet (two meters), that may cause false detection such as, high wattage light bulb, portable heater or HVAC device.
  4. Check the wiring connections.

The Load turns On unintentionally

  1. Mask the Sensor Switch’s lens to eliminate unwanted coverage area.
  2. Turn the Sensitivity Level knob counter-clockwise to avoid false alerts in smaller rooms or near doorway.

NOTE: If problems continue, consult a qualified electrician.

LIMITED WARRANTY

Warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.intermatic.com. This warranty is made by: Intermatic Incorporated, 1950 Innovation Way, Suite 300, Libertyville, IL 60048. For additional product or warranty information go to: http://www.Intermatic.com or call 815-675-7000.