DKC PDU 600 Uninterruptible Power Supply User Manual

June 12, 2024
DKC

DKC PDU 600 Uninterruptible Power Supply

Product Information:

  • Product Name: Info PDU 600/800/1000 Uninterruptible Power Supply
  • Model Variants: INFOPDU600 / INFOPDU600PL / INFOPDU600LCD, INFOPDU800 / INFOPDU800PL / INFOPDU800LCD, INFOPDU1000PL / INFOPDU1000LCD
  • VA Capacity: 600 VA, 800 VA, 1000 VA
  • User’s Manual : Available in multiple languages including English, Italian (Manuale d’uso), and Russian
  • Input Voltage: 360 V – 600 V
  • Output Voltage: 480 V – 1000 V
  • Battery Type: AGM VRLA (Absorbent Glass Mat Valve Regulated Lead Acid)
  • Battery Backup Time : 8-10 minutes at full load, 6-10 minutes at half load, 2 minutes at full load with LCD display
  • LED/LCD Display : LED- only or LED-/LCD-display options available
  • Outlet Type: Schuko outlets with options for 6 outlets (3 without LCD) or 8 outlets (4 without LCD)
  • Protection Rating : IP20 (Ingress Protection Rating 20)

Product Usage Instructions:

  1. Initial Setup:
  2. Ensure the product is placed on a stable surface.
  3. Connect the power supply cable to the input port of the Info PDU.
  4. Connect the load devices to the output ports of the Info PDU.
  5. Connect the communication cables (USB, RJ11, RS232) if required.
  6. Turn on the Info PDU using the power switch.
  7. Basic Operation:
  8. Power Supply: – The Info PDU provides uninterrupted power supply to connected devices. – In case of a power outage, the Info PDU will automatically switch to battery power. – The battery backup time depends on the load and battery capacity. – When the power is restored, the Info PDU will switch back to the main power source.
  9. Load Management: – Monitor the load status of the Info PDU to ensure it does not exceed the maximum capacity. – Use the Info PDU’s LCD display or LED indicators to check the load status. – If necessary, disconnect non-essential devices to reduce the load. – Avoid overloading the Info PDU to prevent damage.
  10. Communication and Control: – The Info PDU supports USB, RJ11, and RS232 communication interfaces. – These interfaces allow for remote
    monitoring, control, and configuration of the Info PDU. – Use appropriate software or devices to communicate with the Info PDU through these interfaces.

Safety Precautions:

Operations

  1. Read the safety instructions carefully before using the UPS and keep this manual for the future use.
  2. Pay attention to all warning labels and follow instructions.
  3. Do not use the UPS in places with direct sun exposure and exposure to rain and other hazards.
  4. The UPS must not be installed near heat sources, such as electric stoves.
  5. Do not place the UPS closely to partitions and walls. Follow the instructions in the technical manual to install the UPS (see section 3).
  6. Clean the UPS with a dry cloth.
  7. In case of fire, use powder fire extinguishers, since wetting agent fire extinguisher can damage the UPS.

Electrical safety

  1. Do not connect the cable from the output of the UPS to the input of the UPS.
  2. Do not connect extension cords to the UPS.
  3. Info PDU UPS are designed to power computers, small information networks, workstations and other computer equipment. Do not use the UPS to power medical devices or other critical devices.
  4. It is forbidden to connect devices of a very high power.
  5. The length of the power cable must not exceed 10 meters.
  6. In case of emergency, press the power key and unplug the UPS power cord from the mains.

Battery safety

  1. Ensure that the UPS is not exposed to open flame, since it may cause an explosion and damage to property and people.
  2. It is forbidden to perform any operations with the battery to personnel who do not have the appropriate access level. The substances contained in it can cause injury to the skin and eyes. In case of contact with electrolyte, immediately wash the affected area with plenty of water and contact the nearest hospital.

Troubleshooting:

In case of UPS failures, refer to the table below for troubleshooting. If the following measures do not help, immediately stop using the UPS and contact an authorized service center.

  1. Additional Information:
  2. Product Variants: –
    The Info PDU is available in different variants with varying VA capacity and features. – Refer to the product name and model variants mentioned above for specific details.

Note: This respons is based on the provided text-extract from the user manual. For complete and accurate information, refer to the official user manual or contact the manufacturer’s customer support.
Thank you for purchasing our UPS. Before using the device, please read this manual.

Introduction

UPS (uninterruptible power supply) is a device designed to protect computer or other equipment from interruptions in power supply, reduction of mains voltage, short-term dips and voltage and current surges.
Under normal conditions, the UPS supplies the connected devices directly from the mains. When operating from the mains, the UPS batteries are maintained in a charged state. In case of mains failure, the UPS supplies the user from the battery, the direct current of which is converted into alternating using a special device called an “inverter”. The battery supplies the load until the mains supply with acceptable characteristics is restored, or until the battery is completely discharged. When switching to the battery, there is a short failure in the power supply of the load, which, however, does not create problems for users.

Terms and Conditions of Installation, Storage, Transportation,

Implementation

  1. The device is installed on any flat, stable, dry surfaces and does not require additional mounting / reinforcement.
  2. Storage is allowed only in places where the temperature and humidity do not exceed the values specified in section 5 “Technical parameters”.
  3. The transportation conditions of the device are identical to the conditions of its storage. Do not transport the device together with power heat sources, containers with liquids, or in places with large accumulations of dust / dirt.
  4. The operation of the device must be carried out in accordance with the current legislation of the Russian Federation.
  5. After the end of the product’s service life, it must not be disposed of together with ordinary household garbage. Instead, it is subject to disposal at the appropriate collection station of electrical and electronic equipment for further processing and disposal in accordance with federal or local law. By ensuring proper disposal of this product, you help to save natural resources and prevent damage to the environment and human health, which is possible in case of improper handling.
    More detailed information about collection and utilization points of this product can be obtained from local municipal authorities or at the enterprise for the removal of household waste.

Installation and Start-up Procedure

UPS installation
  1. Delivery kit:
    • UPS
    • Power cable
    • USB cable (only for models with USB)
    • User manual
    • Product certificate
  2. Upon receipt of the product, check that all contents have no damage that may have occurred during transportation. Retain the packaging and, in the event of damage, contact the transport company or distributor.
  3. Place the device in an appropriate place with sufficient ventilation and away from water, combustible and corrosive gases.
  4. The ambient operating temperature must be in the range of 0-40 °C. Leave at least 20 cm from all the UPS sides to ensure sufficient ventilation.

UPS location
Top view. Buttons and LEDs on the front side of the UPS

  1. Network led (green)
  2. Battery charge led (yellow)
  3. Battery mode led (red)
  4. On/off button
  5. USB – memory inputs

Side view. Buttons, LEDs and connectors on the side of the UPS

  1. USB (optional)
  2. RJ11 (optional)
  3. RS232 (optional)
  4. AC input
  5. Redundant output connector (if there is no voltage at the UPS input, the load connected to this output will receive power supply from the UPS batteries)
  6. Output connector without redundancy (if there is no voltage at the UPS input, the load connected to this output will be disconnected)

INFO PDU model with 8 sockets
The RJ11 connector is used to protect the phone, modem or fax from power surges. One end of the cable must be connected to the “IN” input; the other, coming from the load, must be connected to the “OUT” output.
The RS232 / USB connector is used to automatically turn off / on and monitor the UPS status. It’s necessary to connect one end of the cable with a USB / RS232 connector to the UPS, and connect the other end of the cable to the computer.
During mains operation, the UPS monitors the input frequency and sets the value at 50 or 60 Hz when operating from an inverter.

Connection of the UPS to the mains and the load
  1. Plug the UPS power cable into a mains socket. Before use, it is recommended to charge the battery for 10 hours. The battery automatically recharges while the UPS is connected to the mains.

  2. Connect the consumers to the UPS output.

  3. Phone/modem/fax connection (only for devices with RJ-11).
    The telephone pair must be connected to the “in” connector on the rear panel of the device. The phone / modem / fax is connected to the “out” connector.

  4. Connecting the communication cable (only for models with USB / RS232).
    It allows remote monitoring of the UPS. Connect the device to the computer with the cable. Using the software, it’s possible to turn on / off the UPS, as well as monitor its status from a computer.

Turning the UPS on and off
  1. Press the power button and make sure there are no alarms.
  2. Turn on connected user devices.
  3. In case of a mains failure or a power surge of the UPS, switch to battery power mode. The red LED will light up and a beep will be given. In this case, the UPS supplies electric power to those users who are connected to redundant output connectors. Users connected to the output connectors without redundancy stop receiving electric power. It is recommended to disconnect non-priority devices to extend battery life. When the battery is completely discharged, the UPS turns off, and when the mains voltage is restored, it automatically starts again.
  4. Press the “off” button to stop the system.

ATTENTION! In case of the mains failure, the user can turn on the UPS to supply the load (the “cold start” function).
Laser printers and scanners, as well as non-computer equipment (medical equipment, microwave ovens, vacuum cleaners) must not be connected to the output sockets with redundancy, because it can lead to overload due to high value of starting current.

Technical Specifications

UPS technical specifications
Note: The specifications given are subject to change without prior notice.
Battery life
Each UPS of the Info PDU series has a built-in battery, the capacity and quantity of which varies depending on the model:

  • INFOPDU600 / INFOPDU600PL / INFOPDU600LCD– 1 × 7 Аh
  • INFOPDU800 / INFOPDU800PL/ INFOPDU800LCD– 1 × 8 Аh
  • INFOPDU1000PL / INFOPDU1000LCD – 1 × 9 Аh

Below are graphs showing the dependence of battery life on load power.
Runtime INFOPDU600 / INFOPDU600PL / INFOPDU600LCD

  • the runtime is approximate, depends on the age of the batteries, the condition of the batteries, provided the ambient temperature is 20-25 degrees Celsius. These values may vary in the range of +/- 10%
  • the recommended load level of the UPS should not exceed 80%

Runtime INFOPDU800 / INFOPDU800PL / INFOPDU800LCD

  • the runtime is approximate, depends on the age of the batteries, the condition of the batteries, provided the ambient temperature is 20-25 degrees Celsius. These values may vary in the range of +/- 10%
  • the recommended load level of the UPS should not exceed 80%

Runtime INFOPDU1000PL / INFOPDU1000LCD

  • the runtime is approximate, depends on the age of the batteries, the condition of the batteries, provided the ambient temperature is 20-25 degrees Celsius. These values may vary in the range of +/- 10%
  • the recommended load level of the UPS should not exceed 80%

UPS connectors

UPS of the Info PDU series has the following output connectors:

  • with battery backup – 4 Schuko connectors (INFOPDU600PL, INFOPDU600LCD, INFOPDU800PL, INFOPDU800LCD, INFOPDU1000LCD), 3 Schuko connectors (INFOPDU600, INFOPDU800)
  • without redundancy – 4 Schuko (INFOPDU600PL, INFOPDU600LCD, INFOPDU800PL, INFOPDU800LCD, INFOPDU1000LCD), 3 Schuko (INFOPDU600, INFOPDU800 only)
  • 2 USB connectors for mobile devices charging (INFOPDU600, INFOPDU800 only)
  • 1 USB communication port
  • 1 RJ11 communication port

Storage and Maintenance

Maintenance

  1. Make sure that the air vents are not blocked.
  2. Make sure that the UPS is not covered with dust.
  3. Make sure that there are no traces of moisture on the UPS.
  4. Monitor the battery status in accordance with paragraph 8.3.

Storage
Connect the UPS to the mains to charge the UPS for at least 8-10 hours before storage.
Disconnect the UPS, turn it off and place it in a clean and dry place.
If the UPS is not supposed to be used for a long period, it is necessary to charge it at the intervals indicated in the table below.
Recommended battery charging frequency
The permissible storage temperature is in the range from 0 to +40 ° C.
Battery monitoring
Batteries are a key component of the UPS. Their service life depends on the temperature, as well as on the charging and discharging time. High temperature and deep discharge can shorten the battery life.

  1. Keep the air temperature in the range from +15 to +25°C.
  2. In case of prolonged system downtime, it is need to fully charge the battery once every 6 months.
  3. Batteries must not not be replaced separately.
  4. Under normal conditions, the battery life is about 5 years. If the batteries were kept in a humid, dusty environment, or in low temperature conditions, their service life will be shortened.

Battery testing methods are described below (battery performance may decrease dramatically as the end of service life approaches, it is recommended to check it at least once every 6 months):

  1. Connect the UPS to the mains and leave it on charge for 8-10 hours.
  2. Turn the system on, connect users and measure their power consumption.
  3. Disconnect the mains so that the UPS switches to battery mode and control the discharge time before shutting down.
  4. Check whether the discharge time corresponds to the values given in figures 4 to 5. If the discharge time decreases by more than 50%, replace the batteries. UPS works with V.R.L.A. type lead-acid batteries, which are charged in the presence of a mains supply.

Note :

  1. Before performing operations in the batteries, make sure that the UPS is turned off and disconnected from the mains.
  2. Remove rings, watches and other conductive materials before performing operations.
  3. Use a tool with an insulated handle and do not put metal objects on batteries.
  4. It is strictly forbidden to make a connection between the positive and negative poles of the battery.
  5. It is strictly prohibited to open the battery due to risk of damage.
  6. It is strictly forbidden to throw batteries into the fire. The battery may explode!
  7. Never dispose of the operated-off batteries in the environment.

Warranty and Service Information

AO DKC guarantees that its products are free from defects in the production and packaging of materials and finished products. The warranty period is 2 years from the date of product purchase. The manufacturer provides warranty service, including through Authorized Service Centers (ASC). A warranty case is the loss of equipment performance, provided it is properly operated and maintained during the warranty period.
In case of UPS failure for a reason covered by the warranty, the UPS must be delivered to the service center together with the product certificate included in the delivery package. Addresses and phone numbers of authorized service centers of the manufacturer can be specified on the www.batt.dkc.ru website or by email support@dkc.ru .
These warranty obligations do not apply to equipment damaged by accident, as a result of negligence or as a result of its improper use, as well as to equipment transformed or modified in any way. If there are additional components in the equipment that are not provided for by the configuration (for example, network or other adapters), warranty claims are accepted only in case of a defect that is not a direct consequence of the use of such components, and only for components sold by AO DKC.
With the exception of the obligations specified above, AO DKC is not responsible for direct, indirect, actual, accidental or secondary losses associated with the use of these products. In particular, AO DKC is not liable to the buyer for any actual damage or lost benefits related to the use or inability to use the equipment, data loss, software loss, costs of equipment and software replacement, costs of satisfying claims of third parties and other costs.
For all additional questions, you can contact the unified technical support service at: