REGIN CTDT2 CO2 and Temperature Sensor Instructions
- October 30, 2023
- REGIN
Table of Contents
REGIN CTDT2 CO2 and Temperature Sensor
Product Information and Usage Instructions
Function: The CTDT2 is a device that measures the amount of CO2 in the air and provides an output signal of 0-10 V DC with -1mA.
Technical Data:
- Supply Voltage: The CTDT2 requires a supply voltage of 2 VA, 15 mA, max. 0.5 A for 0.3 s.
- Ambient Temperature: The CTDT2 can operate within an ambient temperature range.
- Storage Temperature: The CTDT2 can be stored within a temperature range.
- Ambient Humidity: The CTDT2 can operate within an ambient humidity range of 0 to 95% RH, non-condensing.
- Long-term Stability: The CTDT2 has a typical long-term stability of 20 ppm per year.
- Protection Class: The CTDT2 has an IP65 protection class when the probe is facing downwards, otherwise it has an IP20 protection class.
Usage Instructions:
- Step 1: Before using the product, read and understand the instruction manual carefully.
- Step 2: Ensure that the installation of the product complies with local safety regulations.
- Step 3: Before installation or maintenance, disconnect the power supply.
- Step 4: Installation or maintenance of this unit should only be carried out by qualified personnel. The manufacturer is not responsible for any eventual damage or injury caused by inadequate skills during installation, or through removal of or deactivation of any security devices.
- Step 5: Once the CTDT2 is installed and powered on, it will measure the amount of CO2 in the air and provide an output signal of 0-10 V DC with -1mA.
Caution! Read and understand the instruction before using the product.
Caution! Ensure that the installation complies with local safety
regulations.
Caution! Before installation or maintenance, the power supply should
first be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible for
any eventual damage or injury caused by inadequate skills during installation,
or through removal of or deactivation of any security devices
Function
- CTDT2 is a transmitter for measuring carbon dioxide concentration and temperature.
- The transmitter has a probe in the shape of a so-called venturi tube with two air channels. The CO2 sensor element is mounted in the housing and the temperature sensor element is located inside the probe.
- The air in the ventilation duct is transported to the CO2 sensor element through one half of the probe and then back to the duct through the other half. The temperature sensor is located inside the probe. (see Figure 1)
Technical Data
Supply voltage| 24 V AC ±20 %, 50…60 Hz
15…35 V DC
---|---
Power consumption| 2 VA, 15 mA, max. 0.5 A for 0.3 s
Ambient temperature| -20…+60 °C
Storage temperature| -20…+60 °C
Ambient humidity| 0…95 % RH, non-condensing
Long-term stability| Typ. 20 ppm / year
Protection class| IP65 with probe downwards, otherwise IP20
CO2
Output signal| 0…10 V DC, -1 mA <IL <1 mA
4…20 mA, RL <500 Ω
---|---
Measurement principle| NDIR (Non-Dispersive Infrared Technology)
Measuring range| 0…2000 ppm
Accuracy (at 25 °C)| < ± (50 ppm + 2 % of the measured value)
Time constant (re- sponse time)| < 100 s at 3 m/s air speed
in the duct
Temperature dependance| Typ. 1 ppm CO2/ °K (-20…+45 °C)
Warm-up time| < 5 min
Temperature
Output signal | 0…10 V DC, -1 mA <IL <1 mA |
---|---|
Working range | 0-10 V: 0…50 °C PT1000: -20…+60 °C |
Accuracy (at 20°C) | ±0.3 °C |
Time constant (re- sponse time) | < 50 s |
Installation
Mount CTDT2 at a place in the duct where it can be expected to give a representative reading. It should be placed at least 4 duct diameters from a bend or other obstacle, e.g. a damper, for minimal turbulence.
- Unscrew the spring-loaded screws to open the cover and access the terminals
- Place the transmitter in the airflow direction of the ventilation duct according to the marks on the cover. The air flow direction is either from right to left (as in Figure 1) or from left to right. The hole in the duct should measure 13 mm in diameter.
- Connect the wires to the terminals according to the wiring diagram.
- Screw the cover back on and ensure that it is properly fastened and that the cable gland makes a tight seal around the cable.
Figure 1 The airflow direction is either from right to left (as in the example) or from left to right
Wiring
1 | Supply voltage 24 V AC or 15…35 V DC |
---|---|
2 | System neutral |
3 | Signal neutral |
4 | CO2 output 0…10 V DC or 4…20 mA |
5 | Temperature output 0…10 V DC |
6 | Temperature output PT1000 |
7 | Temperature output PT1000 |
Note! System neutral and signal neutral are internally connected
Settings
Flipping the internal DIP-switch located at the lower right-hand side of the circuit board will change the CO2 output signal from 0…10 V (“U”) to 4…20 mA (“I”). This change will not affect the CO2 output range
Calibration
CTDT2 is factory calibrated before delivery and does not need to be calibrated at installation. It has automatic CO2 calibration, which means that manual recalibration is not required during the lifetime of the transmitter.
Start-up
After applying power to CTDT2, it will take a few minutes for it to show correct values
This product carries the CE-mark. More information is available at www.regincontrols.com.