nilfisk food MU421-P Control Panel for Hybrid Units User Manual

June 4, 2024
nilfisk food

Software Manual
Control Panel for Hybrid Units
Models: **
MU421-P MU422-P
BW4-P BW7-P BF4-P BF8-P Software Manual V. 5.15**

Description

This software manual describes the operation of the control panel of the advanced Single Booster unit (SB and SBHL).
The advanced SB unit is operated via the control panel (see the below illustration).

  1. OFF
    Button (1) switches OFF the unit.

  2. ON/STANDBY
    Button (2) switches ON the unit.

  3. ERROR
    Error light indicator (3).

  4. NAVIGATION BUTTONS
    The four ”arrow” navigation buttons (4) are used for navigation in the display menu. Pressing the ”OK” button activates the menu and confirms any activity displayed.

  5. DISPLAY

nilfisk food MU421-P Control Panel for Hybrid Units - fig
1 110007943
Software Manual

Display layout

nilfisk food MU421-P Control Panel for Hybrid Units - fig
2

  1. When switched on the display will show an arrow symbol in the top right corner equivalent to the active navigation buttons on the control board.
    The arrows illustrate that it is possible to scroll up and down between the menus. Scrolling to the right makes it possible to enter a value. Set the value scrolling up (+) or down (-) to set the value higher or lower accordingly. Confirm by pressing ok.

  2. A letter combination for easy reference in connection with service work will appear in the top right corner of the display.

Modes

3.1 Power On
The very first time the unit is switched on, we recommend setting the date and time in the Setup menu, settings, and display EP. If the date and time is not set, date and time will count from the pre-set default date and time.

Set date and time using navigation buttons.

Confirm by pressing OK button.

3.2 Standby
The start-up display will look as the one below.

Display for SB model with High- and Low-pressure – Select either HP or LP using arrows up & down.
3.3 Run Mode
3.3.1 Single Booster with high and low pressure
The following screen displays will appear when the unit is in Run Mode. Screen display for High-pressure unit in Run Mode. Scroll down to return to STANDARD pressure. Screen display STANDARD pressure. Scroll up to choose HP and scroll down to choose LP.

Screen display for Low-Pressure unit in Run Mode. Scroll up to return to STANDARD pressure.
Please note that you will remain in HIGH or LOW-pressure Run Mode until otherwise is selected.
3.4 Power Off

When the unit is off the display will only show a small dot in the top right corner.
In Off mode, it is possible to access all menus without the pump running by pressing the OK button on the panel.
Dot is equivalent to the OK confirm button on the panel.
3.5 Error/Warning

In case of an error, “ ERROR” will appear on the display screen.
Press the OFF button to switch of the unit.
If the error remains when the unit is switched ON again, please Press the right arrow to see the current error.
In case of a warning, “WARNING” will appear on the display screen. When a warning is detected the machine will either stop or run with limited performance until the cause of the warning has been improved (eg. inlet pressure). To see a further error/warning list and possible causes and remedies go to section 5.2.

Main Menus

The control panel contains the below main menu screen displays.
Scroll between the menus using the navigation buttons.
Each main menu contains submenus which will be described subsequently.

Overview of Main- and Sub-menus

  1. Info (A)
    1.Σ Counters total (AA)
    2.Σ Counters trip (AB)
    3. Service center(AD)
    4. Machine info (AE)
    Errors (B)

  2. Setup (C) (default password 6802)1 Password (CA)
    **** 2 Settings (E)
    Post run time (ED)
    Dry run level (EE)
    Standard pressure (ER)
    High pressure (EA)
    Low pressure (EB)
    Startup method (EY)
    Pressure start level(EX)
    Startup delay (EW)
    Quick Start level (EC)| Auto-off delay (EZ)
    Accelleration time (EU)
    Date & Time (EP)
    Service text (EJ)
    Inverter power (EO)
    Backlight intensity (EI)
    Display contrast (EV)
    User password (EL)
    Standard settings (EK)
    ---|---

  3. Languages & units (F)
    Language (FA)
    Units (FB)

  4. Supply Tank (H)
    Tank control (HA)
    LLA Detect Delay (HB)

  5. Communication (I)
    Firmware Upgrade by cable (IC)
    Firmware Upgrade by infrared (ID)

  6. I/O Settings (J)
    Output 1 (JA)
    Output 2 (JB)
    Input (JC)

  7. Installation (K)
    Install password (KA)

  8. Resets (D)
    Reset trip counters(DA)

4. Readings (R)
Pump state (RA)
Outlet pres. (RB)
Water temp (RC)
Supply pressure (RD)
Flow Status (RF)
Please note that the Info menu is only for display – all data must be typed in via the setup menu!
5.1 Info Menu Displays accumulated consumption of power and operation hours.

Displays accumulated consumption of power and operation hours.To reset the trip counter go to the setup menu. Displays name and tel. no. of a service technician.

This display view is only meant as an example, SW ID and CT ID show the current SW version.
Displays Software version and Pump size, machine configuration and inverter software version.
5.2 Errors Menu – CAUSE & REMEDY
Example of Error log screen display:
All error occurrences will be stamped with the date and time.
E indicates the Error number. P indicates the Pump number. The error log stores up to 1000 occurrences. When max. memory is reached, the errors will be deleted according to the”First in” First out” principle.
5.2.1 Error List

Error Cause Remedy
C1 Inverter Error 1. Frequency inverter in error state 1. Switch off the

power on the service switch. Wait 180 sec. Switch on the unit again. If error still occurs, please contact your local service technician.
C2 Low Supply Pressure| 1. Insufficient water supply| 1.Secure sufficient water supply pressure.
2.Check inlet filter for impurities/rinse filter
3.Contact your local service technician.
C3 High Water Temp.| 1.Water pump top temperature is above 80°
2.Water consumption is too low (pump column has been overheated)| 1.Lower the inlet water temp. (max 70°C)
2.Secure sufficient water consumption
3.Contact your local service technician.
C4 High Motor Temp.| 1. Insufficient cooling of motor
2.The ambient temperature is above 40°| 1.Secure that all air channels are open and not blocked by impurities
2.Lower ambient temperature
C5 High Supply Temp.| 1. Water inlet temperature is above 70°| 1.Lower the water temp. (max 70°C)
2. Contact your local service technician.
C6 Low Sensor Supply Voltage| 1. Voltage supply for sensors too low| 1.Press the “off” button
2. Contact your local service technician.
C7 No Response Error| 1. No communication between display and control board| 1. Contact your local service technician.
C8 Low Tank Level| 1. Insufficient water supply
2. Water supply valve not open| 1. Check correct water supply
2.Secure sufficient air supply to valve
3. Contact your local service technician.
C9 High Tank Level| 1. Water supply valve not closed| 1. Secure sufficient air supply to the valve.
2. Contact your local service technician.
C11 Warning Cri. Inlet press.| 1. Insufficient water supply
2. Booster will return to standby mode after 20 sec. If this error occurs 3 times within 20 min. Error C2 occurs.| 1.Secure sufficient water supply or reduce consumption
2. Check inlet filter for impurities/rinse filter
3. Contact your local service technician.
C13 Warning Low inlet press.| 1. Insufficient water supply.
The machine will keep on working as always, but the maximum speed of the pump will be reduced until sufficient inlet pressure is present.| 1.Secure sufficient water supply or reduce consumption
2. Check inelt filter for impurities/Rinse filter
C14 Warning
leakage start| 1. Booster start condition changed to flow, due to leakage in pipe| 1. Check for leakage in the pipe system.
2.Press the “off’ button
3. Contact your local service technician.
C20 Low Sensor Signal P-Pump top| 1. Pressure signal from pump top sensor, out of range| 1.Press the “off” button
2. Contact your local service technician.
C21 Low Sensor Signal T-Pump top| 1. Temperature signal from pump top, sensor, out of range| 1.Press the “off” button
2. Contact your local service technician.
C22 Low Sensor Signal P-Inlet| 1. Pressure signal form inlet sensor, out of range| 1.Press the “off” button
2. Contact your local service technician.
C23 Low Sensor Signal T-Inlet| 1. Temperature signal from inlet sensor, out of range| 1.Press the “off” button
2. Contact your local service technician.
C24 Low Sensor Signal block| 1. Signal from block sensor, out of range| 1.Press the “off’ button
2. Contact your local service technician.
C25 Low Sensor Signal flow| 1. Signal from flow sensor, out of range| 1.Press the “off’ button
2. Contact your local service technician.
C30 High Sensor Signal P-Pump- top| 1. Pressure signal from pump top sensor, out of range| 1.Press the “off’ button
2. Contact your local service technician.
C31 High Sensor Signal T-Pump top| 1. Temperature signal from pump top sensor, out of range| 1.Press the “off button
2. Contact your local service technician.
C32 High Sensor Signal P-Inlet| 1. Pressure signal from inlet sensor, out of range| 1.Press the “off” button
2. Contact your local service technician.
C33 High Sensor Signal T-Inlet| 1. Temperature signal from inlet sensor, out of range| 1.Press the “off’ button
2. Contact your local service technician.
C34 High Sensor Signal block| 1. Signal from block sensor, out of range| 1. Press “off” button
2. Contact your local service technician.
C35 High Sensor Signal flow| 1. Signal from flow sensor, out of range| 1.Press the “off’ button
2. Contact your local service technician.
C40 Sensor Load Pump top Sensor| 1. Supply voltage for pump top sensor too low.
2.Pump top sensor using too much current| 1.Press the “off” button
2. Contact your local service technician.
C41 Sensor Load Inlet sensor| 1. Supply voltage for inlet sensor too low
2. Inlet sensor using too much current| 1.Press the “off” button
2. Contact your local service technician.
C42 Sensor Load Block sensor| 1. Supply voltage for block sensor too low
2. Block sensor using too much current| 1.Press the “off” button
2. Contact your local service technician.
C43 Sensor Load Flow sensor| 1. Supply voltage for flow sensor too low
2. Flow sensor using too much current| 1.Press the “off” button
2. Contact your local service technician.
C44 Chemistry can low| 1. Chemistry can almost empty| 1. Replace or refill selected chemistry to can
C45 Inverter Module temp.| 1. Water consumption too high
2. Ambient temperature too high”| 1. Lower the load for the inverter
2.Lower the ambient temperature”
C46 Inverter Board temp.”| 1. Water consumption too high
2. Ambient temperature too high
3. Load at Board high”| 1. Lower the load for the inverter
2.Lower the ambient temperature
3. lower the load at board”

5.3 Setup Menu
The Setup Main menu contains the below submenus, which will be described subsequently.

Password Note: The default user password is 6802. Enter the settings menu to change the default password. To avoid unintended access to the system your local service technician. can insert a blocking preventing access to the password-controlled menus.

|
---|---

5.3.1 Settings

| nilfisk food MU421-P Control
Panel for Hybrid Units - fig23
---|---

Enter name and tel. no of Your local service technician. Set rated power of frequency inverter

Set the backlight intensity.nilfisk food MU421-P Control Panel for Hybrid
Units - fig 26

Create new user password (default 6802).nilfisk food MU421-P Control Panel
for Hybrid Units - fig 27Reset to standard factory settings.
5.3.2 Language & Unitsnilfisk food MU421-P Control Panel for Hybrid
Units - fig 28

5.3.3 Supply tanknilfisk food MU421-P Control Panel for Hybrid Units - fig
29

5.3.4 Communication
nilfisk food MU421-P Control Panel for Hybrid Units - fig
30*For the use of authorized Your local service technician only.
5.3.5 I/O Settingsnilfisk food MU421-P Control Panel for Hybrid Units -
fig31

Output 1 options:

  • None – No function
  • Error – Active if an error is detected
  • Run/Stop – Active if a booster is running and not active when it is stopped.
  • Standby /off – active if a booster is running or in standby.

Output 2 options:

  • None – No function
  •  Delay start – Gives a signal at this port, before starting the pump.
    The length of the delay is set in the settings menu, startup delay.
    This function could for instance be used to secure the start-up of the pressure pump before starting the unit.

Input

  • None – No function
  • Release – unit unable to start before this signal is present.
  • Setpoint – Output pressure is controlled by an external voltage source.
  • Chem. Low – Low levels in chemistry can

5.3.6 Installation

  • For the use of authorized Your local service technician only.

5.3.7 Resetnilfisk food MU421-P Control Panel for Hybrid Units - fig
33

5.4 Readings

| nilfisk food MU421-P Control Panel for Hybrid Units -
fig36
---|---

Upgrade Firmware

Upgrading from software 5.02 or higher.

6.1 Upgrade display using USB Cable

  1. Connect the USB cable (Item No. 110007947)  to the PC USB port (Remove other USB cables connected to PC)
  2. Connect the Display cable to the USB cable
  3. In the menu go to, Setup->” password”->Communication-> Firmware upgrade by cable-  >Confirm Firmware upgrade and press “OK”
  4. The display should now be looking like this:
  5. Disconnect the display from usb cable and connect it again (Power cycle)
  6. Make sure the Green “ON” led and the red “OFF” led at the display is both on, display is blank
  7. Startup PC program FWU200.exe (can be downloaded from Nilfisk Food website)
  8. A window should be looking like this
  9. Press the” Browse” button
  10.  Select the file you will use for the upgrade. Software File can be downloaded from the Nilfisk Food website. The name of the file should end with “.hex”. Ex V5.14_SB_DISP.hex
  11. When the file is located press “Open” in the browser window
  12. The file name will now be written in file text line
  13. Press the UPGRADE button in FWU 200 tool
  14. After a short while the FWU tool should start upgrading, the upgrade button should turn  Yellow and change to “RUNNING”
  15. The progress bar “Program” must go to the end before the upgrade is complete (less than 1 minute)
  16. When the upgrade is complete the FWU tool should be looking like this, Button turns Green and text changes to “DONE/NEW”
  17. Now the display is upgraded
  18. To verify the software version in the display, in the menu go to, Info->Machine info
  19. Here you will find the display software version and the control software version. SW ID “Display software”, HW ID “type of device”, CT ID Controller board software(if the display is not connected to a control board, control software will be 0/300)

6.2 Upgrade display using IrDA Cable

  1. Connect power to equipment

  2. In the menu go to, Setup->” password”->Communication-> Firmware upgrade by Infrared-  >Confirm Firmware upgrade and press “OK”

  3. The display should now be looking like this:

  4. Turn Off the equipment and turn it on again (Power cycle)

  5. Make sure All three leds are on (Green “ON”, red “ERROR” and red “OFF”) and the display is blank

  6. Connect Irda module (Item No. 110001558) to the PC USB port

  7. Place Irda module on display module like this

  8. Startup PC program FWU200.exe (can be downloaded from Nilfisk Food website)9.

  9. A window should be looking like this

  10.  Press the”Browse” button

  11.  Select the file you will use for the upgrade. Software Files can be downloaded from the Nilfisk Food website. The name of the file should end with “.hex”. Ex V4.14_SB_DISP.hex

  12. When the file is located press “Open” in the browser window

  13. The file name will now be written in the file text line

  14. Press the UPGRADE button in FWU 200 tool

  15. After a short while the FWU tool should start upgrading, the upgrade button should turn  Yellow and change to “RUNNING”

  16. The progress bar “Program” must go to the end before the upgrade is complete (less than 1 minute)

  17. When the upgrade is complete the FWU tool should be looking like this, Button turns Green and text changes to “DONE/NEW”

  18.  Now the display is upgraded

  19. To verify the software version in the display, in the menu go to, Info->Machine info

  20. Here you will find the display software version and the control software version. SW ID “Display  software”, HW ID “type of device”, CT ID Controller board software(if the display is not connected to a control board, control software will be 0/300)

6.3 Upgrade Inverter

  1.  Power off unit using service switch (wait for unit to discharge approximately 5 min.)
  2. Open Inverter box
  3. Disconnect the Display cable connected to either of the two Modbus terminalsnilfisk food MU421-P Control Panel for Hybrid Units - fig 52
  4. Connect the usb cable (110007946) to either one of the modbus connectors
  5. Connect usb cable to PC
  6. Power on inverter by using service switch (AWARE OF HIGH VOLTAGE IN INVERTER!)
  7. Start up Firmware upgrade program (Can be downloaded from Nilfisk FOOD web)nilfisk food MU421-P Control Panel for Hybrid Units - fig53
  8. Click browse to select upgrade file *.hex (Can be downloaded from Nilfisk FOOD web)9.
  9. Click in Serial port up/down to select the com port for a USB cable, if comport is not showing press the “refresh” button
  10. If necessary change inverter ID to match Inverter ID, Default is 1
  11. Press Upload Firmware, and wait for the progress bar to reach the end and turn green
  12. The progress bar will start movingnilfisk food MU421-P Control Panel for Hybrid Units - fig 54
  13. Power off unit using service switch (wait for unit to discharge approximately 5 min.)
  14. Disconnect the usb cable from the inverter
  15. Connect the display to Modbus connector again
  16. Mount the lit of the inverter box
  17. Turn unit back on.

© 2014 All rights reserved
Distributor:No.: 110007943E 07/2022
Printed in Denmark

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals