LG LMU601HV Eight Zone Multi F Max Outdoor Unit Instructions
- June 4, 2024
- LG
Table of Contents
LMU601HV
Multi F MAX Outdoor Unit
5.0 Ton Heat Pump
Performance:
Cooling Capacity (Min.‐Rated‐Max., Btu/h)
Heating Capacity (Min.‐Rated‐Max., Btu/h)
Max. Heating Capacity at 17°F (Btu/h)
Max. Heating Capacity at 5°F (Btu/h)
Max. Heating Capacity at ‐4°F (Btu/h)
Cooling COP @95°F (Rated)
Heating COP @47°F (Rated)| 12,420~64,000~68,000
57,590
3.31
46,220
10,800~60,000~65,000
3.45
52,840
---|---
Cooling Nominal Test Conditions:
Indoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB| Heating Nominal Test Conditions:
Indoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB
Electrical:
Power Supply (V/Hz/Ø)1
MOP (A)
MCA (A)
Cooling Rated Amps (A)
Heating Rated Amps (A)
Compressor (A)
Fan Motor (A)
Locked Rotor Amps (A)| 208‐230V, 60, 1
40
32.7
22.0
1.6 x 2
22
30.4
30.4
---|---
MOP ‐ Maximum Overcurrent Protection
MCA ‐ Minimum Circuit Ampacity
Piping:
Refrigerant Charge (lbs.)
Liquid Line Connection (in., O.D.)
Vapor Line Connection (in., O.D.)
Maximum Total Piping² (ft.)
Min. / Max. ODU to IDU Piping(ft.)
Piping Length3
(no add’l refrigerant, ft.)
Maximum Elevation between ODU and IDU (ft.)
Maximum Elevation between IDU and IDU (ft.)4| Ø3/8 x 1
Ø3/4 x 1
475.7
32.8 / 229.6
180.4
98.4
49.2
11.46
---|---
ODU = Outdoor Unit
IDU = Indoor Unit
Features:
- R1 Scroll (Variable Speed) Compressor
- Auto operation
- Auto-restart
- Self-diagnosis
- Defrost / Deicing
- Low ambient cooling down to 14°F
- Soft start
- Restart delay (three [3] minutes)
Optional Accessories:
- PI‐485 ‐ PMNFP14A1
- AC Smart 5 ‐ PACS5A000
- ACP 5 ‐ PACP5A000
- MultiSITE™ Comm. Mgr. ‐ PBACNBTR0A
- Power Distribution Indicator (PDI) Premium ‐ PQNUD1S41
- Mobile LGMV ‐ PLGMVW100
- Low Ambient Wind Baffle (Cooling Operation Down to ‐4°F) ‐ ZLABGP04A x2
- Drain Pan Heater ‐ PQSH1200
Required5 Accessories:
- 2 Port BD Unit ‐ PMBD3620
- 3 Port BD Unit ‐ PMBD3630
- 4 Port BD Unit ‐ PMBD3640
- 4 Port BD Unit ‐ PMBD3641
Operating Range:
Cooling (°F DB)¹5
Heating (°F WB)| 14 to 118
‐4 to +64
---|---
Unit Data:
Refrigerant Type
Refrigerant Control
Sound Pressure (Cool / Heat) ±1 dB(A)6
Net / Shipping Weight (lbs.)
Heat Exchanger Coating
Minimum No. of Indoor Units
Maximum No. of Indoor Units| R410A
REV
56 / 58
218 / 243
Gold Fin™
2
8
---|---
Compressor:
Type
Quantity
Oil / Type| R1 Scroll
1
FVC68D
---|---
Fan:
Type
Quantity
Motor / Drive
Max. Airflow Rate (CFM)| Propeller
2
Brushless Digitally Controlled/Direct
2,119 x 2
---|---
Notes:
- Acceptable operating voltage: 187V ‐ 253V.
- Piping lengths are equivalent.
- 180.4 ft. of Main Piping + 49.2 ft. of Branch Piping.
- 49.2 ft. of Main Piping + 131.2 of Branch Piping.
- At least one branch distribution (BD) unit is required for system operation; a maximum of two can be installed per ODU with the use of a Y‐branch accessory (PMBL5620).
- Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
- All power/communication cables to be a minimum of 14 AWG from the ODU to the BD unit, and 14 AWG from the BD unit to the IDU.
- All power/communication cables to be 4‐conductor, stranded, shielded, or un-shielded, and must comply with applicable local and national codes. If shielded, the wire must be grounded to the chassis at the ODU only.
- Power wiring size must comply with the applicable local and national codes.
- See the Engineering Manual Capacity Tables for ODU sensible and latent capacities.
- See the Engineering Manual Combination Tables for allocation of ODU-rated capacity to each connected IDU when all are calling for full capacity. Allocation percentages should be applied to ODU capacity at design conditions.
- This data is rated 0 ft. above sea level, with 115 ft. of refrigerant line, and a 0 ft. level difference between ODU and IDUs. All capacities are net with a combined ratio between 95 ‐ 105%.
- Must follow installation instructions in the applicable LG installation manual.
- See the Engineering Manual Capacity Tables for ODU capacity at design conditions.
- Installation of an optional Low Ambient Wind Baffle Kit will allow operation down to ‐4°F in cooling mode.
Notes:
- The unit must be installed in compliance with the installation manual.
- The unit must be grounded in accordance with local or state regulations and applicable national codes.
- All field-supplied electrical components and materials must comply with local, state, and national codes.
- Electrical characteristics must be considered for electrical work and design. The capacity of the power cable and circuit breaker for the outdoor unit must follow local, state, national, and manufacturer requirements.
Example: an outdoor unit with eight (8) indoor units and two (2) branch
distribution units connected.
ODU: Outdoor Unit.
IDU: Indoor Unit.
BDU: Branch Distribution Unit(s).
A: Main Pipe.
B: Branch Pipe (Branch Distribution Unit[s] to Indoor Unit[s]).
Multi F MAX Outdoor Unit Refrigerant Piping System Limitations.
Pipe Length
(ELF = Equivalent Length of pipe in Feet)| Total piping length (IA + 1B)|
5475.7 feet
---|---|---
Main pipe (Outdoor Unit to Branch Distribution Units: A)| Minimum for Each (A)
Piping Segment| 16.4 feet
Maximum (IA)| 5180.4 feet
Total branch piping length (IB)| 5 295.3 feet
Branch pipe (Branch Distribution Units to Indoor Units: B)| Minimum| 16.4 feet
Maximum| 549.2 feet
Elevation Differential (All Elevation Limitations are Measured in Actual
Feet)| If the outdoor unit is above or below the indoor unit (h1)| 598.4 feet
Between the farthest two indoor units (h2)| 549.2 feet
Between branch distribution unit and the farthest connected indoor unit(s)
(h3)| 532.8 feet
Between branch distribution units (h4)| 549.2 feet
Installing the Unit
Multi F MAX Piping Sizes.
Piping | Main Pipe A (inch) | Branch Pipe B |
---|---|---|
Liquid | Ø3/8 | Depends on the size of the indoor unit piping. |
Vapor | Ø3/4 |
For continual product development, LG reserves the right to change
specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved.
“LG Life’s Good” is a registered trademark of LG Corp.
/www.lghvac.com