Coal-trol Digital CM2-OEM TS2BL Digital Thermostat
Product Information: Coal-trol DigitalTM TS2BL Thermostat
The Coal-trol DigitalTM TS2BL Thermostat is a product designed to improve the performance and convenience of your anthracite coal stove. The thermostat and solid-state control module work together to provide efficient heating. The product comes with a user manual that provides detailed instructions on how to install and use it.
Contents of the User Manual
- Welcome
- Safety and Warnings
- For Service or Repair
- Coal-trol DigitalTM Limited Warranty
- Locating and Mounting the Thermostat
- QuickStart
- Recommended Settings by Stove Brand
- Adjusting IDLE and MAX Fuel Limits
- Setpoint Modes and TS2 & TS2ES Compatibility
- Power Outages
- Test Mode
- Menus
- Round-Robin / Home
- Quick Menu
- Press and Hold MENU Sequence
- FEED
- SETUP
- Setpoint Programming
- TS2 SPM Mode
- ES SPM Mode
- ADVANCED
- RESET
- Advanced Topics
- Control Module Type
- Dual Stoker
- Tri-burner Stoves
- Manual Fan Safe Threshold and Time Settings
- Where did HLF go?
- The Temperature Keeps Overshooting Way Above Setpoint
- Generator and Off-Grid Power
- Boiler, Biomass, Gasifier, and Other Heating Appliance Types
- Troubleshooting Your Stove
- Specifications
Product Usage Instructions
- Mount the TS2BL thermostat on an interior wall, out of direct sunlight, using the mounting hardware provided. The thermostat should not be placed on a shelf or couch or placed in a location where it will be insulated from the flow of air in the space you are heating.
- Connect the TS2BL to your Control Module using the thermostat control cord. Power will be supplied to the TS2BL thermostat once the control module is plugged into an electrical outlet and your thermostat is connected to your control module.
- Refer to the Control Module manual for installation instructions or contact a local automatic coal stove installer.
- Do not connect either the TS2BL or control module to an ethernet network. It may result in damage to the Coal-trol or your ethernet equipment.
- Follow all manufacturer instructions that came with your stove or furnace. The Coal-trol Digital is designed to complement and enhance the safe operation of your appliance. Specifically, the Coal-trol Digital control system has been designed for use with appliances tested to ANSI Standard Designation: E1509-95, Standard Specification for Room Heaters, Pellet Fuel-Burning Type and/or UL1482, Room Heaters, Solid Fuel Type.
Coal-trol Digital™ TS2BL Thermostat
User Manual
© 2022 Automation Correct, LLC
The Coal-trol Digital™ system has been specifically developed to improve the
performance and convenience of your anthracite coal stove. The TS2BL
thermostat and solid-state control module make this possible.
An investment of a small amount of time to review this manual will ensure the
proper performance of your Coal-trol Digital™ system.
Features, compatibility and benefits of the TS2BL Thermostat:
- Fully compatible with Coal-trol TS2 Thermostat. Must be used with CM2-OEM, CM2-4, and CM2-4-XX Control Modules.
- Custom backlit display for easy use and setup.
- Single Setpoint Mode (default, super easy to use), TS2 Mode (two setbacks), TS2ES Mode (formerly Energy Star – 4 setbacks Weekdays, 4 setbacks Weekends). You choose.
- New – power loss timer recovers fire or prevents fuel feed when fire is out after power interruption.
- Variable speed convection fan speed – Automatic or manual control.
- New – two RJ45 connectors – choose behind wall or surface wiring.
- Standard on appliances by Leisure Line Stove and Hitzer Stoves.
- Use to upgrade control systems on Alaska, Keystoker, Reading, Harman (Magnum), Triburn and other anthracite stoker stoves and furnaces.
Welcome
To a new era in solid fuel heating. You have chosen to improve your household
comfort and increase the efficiency of your heating dollars.
The TS2BL is designed to be mounted to an interior wall, out of direct
sunlight. Mounting hardware is provided and two thermostat control cord
receptacles are available to accommodate different mounting situations. The
thermostat should not be placed on a shelf or couch or placed in a location
where it will be insulated from the flow of air in the space you are heating.
In your thermostat’s packaging you will find an insert that has thermostat
wall mounting instructions and a drilling template.
This manual assumes you have already installed and connected the Control
Module to your stove’s motors. Please reference the Control Module manual for
installation instructions, or contact a local automatic coal stove installer.
Connect the TS2BL to your Control Module using the thermostat control cord.
Automation Correct can supply you cords of different lengths if the one
included in your system purchase is not long enough. You can also use standard
ethernet patch cords to connect the thermostat to the control module. Do not
connect either the TS2BL or control module to an ethernet network. It may
result in damage to the Coal-trol or your ethernet equipment.
Power will be supplied to the TS2BL thermostat once the control module is
plugged into an electrical outlet and your thermostat is connected to your
control module. Any switch integrated in your CM-OEM or CM2 control module
only controls power to the motor outputs, not to the connected thermostat.
Safety and Warnings
ATTENTION – Please follow all manufacturer instructions that came with
your stove or furnace. The Coal-trol Digital is designed to complement and
enhance the safe operation of your appliance. Specifically, the Coal-trol
Digital control system has been designed for use with appliances tested to
ANSI Standard Designation: E1509-95, Standard Specification for Room Heaters,
Pellet Fuel-Burning Type and/or UL1482, Room Heaters, Solid Fuel Type.
Use of the Coal-trol Digital™ on appliances not permanently marked with one of
the above designations voids all warranties and may be unsafe. Contact us or
your stove manufacturer if you are not sure that your stove/furnace is built
in compliance with these safety standards.
WARNING – The Coal-trol Digital™ is capable of regulating a coal fire
smaller than required to maintain a proper chimney draft. Follow all
manufacturer’s recommendations for minimum draft pressures and temperature.
The use of mechanical means such as a draft inducer fan may be required to
ensure proper draft at low fire. Installation of a carbon monoxide detector
(not included) is highly recommended.
Please keep reading… Additional Safety Information:
THIS PRODUCT HAS A GROUNDING TYPE PLUG AND REQUIRES A GROUNDING TYPE OUTLET.
IF THE PLUG DOES NOT FIT, CONTACT A QUALIFIED ELECTRICIAN. DO NOT MODIFY THE
PLUG IN ANY WAY.
TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT CONNECT TO A CIRCUIT AT MORE THAN
150 VOLTS TO GROUND.
RISK OF ELECTRICAL SHOCK: THE CONTROL MODULE AND THERMOSTAT HAVE NO
SERVICEABLE PARTS INSIDE. SEE WARRANTY FOR SERVICE.
WARNING: BYPASS OF MECHANICAL VENT SPILLAGE SWITCH (FUME SWITCH) OR
BONNET TEMPERATURE LIMIT, IF INSTALLED IS DANGEROUS. OPERATION MAY CAUSE
SERIOUS INJURY OR DEATH, DUE TO CO POISONING OR FIRE.
FOR INDOOR USE ONLY
For Service or Repair
Contact your dealer or our company.
Phone: 315-299-3589 (Leave a message.
We get too many junk calls)
Email: coaltrol@automationcorrect.com
Web: www.automationcorrect.com
Coal-trol Digital™ Limited Warranty
THREE-YEAR WARRANTY – Automation Correct LLC (us) warrants TS2BL Thermostat
and Control Module to be free from defects in material and workmanship. If a
defect is found within three years from the date of original installation of
the product (whether or not actual use begins on that date) Automation Correct
LLC will provide a new or remanufactured part, at our sole option, to replace
any defective part, without charge for the part itself.
This warranty does not include labor or other costs incurred for diagnosing,
repairing, removing, installing, shipping, servicing, or handling either
defective parts or replacement parts.
Warranty Conditions:
- Warranties only apply to products in their original installation location.
- Installation, use, care, and maintenance must be normal and in accordance with the instructions contained in the Operation Manual, Installation Manual and Automation Correct LLC’s Service Information.
- Defective parts must be returned to us or an authorized dealer for credit.
- All work is performed during normal business hours.
- This warranty applies only to residential use.
LIMITATIONS OF WARRANTIES – All implied warranties (including implied
warranties of merchantability and fitness for a particular purpose) are hereby
limited in duration to the period for which the LIMITED WARRANTY is given and
applies. Some states do not allow limitations on how long an implied warranty
lasts, so the above may not apply to you. The expressed warranties made in
this warranty are exclusive and may not be altered, enlarged, or changed by
any distributor, dealer, or other person whatsoever.
Automation Correct LLC will not be responsible for:
- Damage or repairs as a consequence of faulty installation, misapplication, abuse, improper servicing, unauthorized alteration or improper operation.
- Failure to operate due to voltage conditions, blown fuses, open circuit breakers or other conditions beyond the control of Automation Correct LLC.
- Parts not supplied or designated by us, or damages resulting from their use.
- Automation Correct LLC products installed outside the 50 US states or Canada.
- Cost of heating fuel of any kind whatsoever including electricity.
- Any special indirect or consequential property or commercial damage of any nature whatsoever. Some states do not allow the exclusion of incidental or consequential damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights, and you also may have other rights, which vary from state to state.
Locating and Mounting the Thermostat
Mount the TS2BL thermostat at eye level, preferably on an interior wall. For
proper operation the thermostat must either be in the same room as the stove,
or must readily sense the diffuse heat from a heat discharge and return air
duct system. Avoid the direct breeze of warm discharge air on the thermostat.
To the side or rear, or across the room from a stove is good.
The TS2BL connects to the Control Module on the appliance with a RJ45 wire.
Choose either behind the wall wiring method or wall surface wiring method. Use
the template included with your thermostat to assist in mounting.
QuickStart **
**
The TS2BL is compatible with the vast majority of forced air automatic coal stoker stoves on the market and in use. It can be used straight out of the box with no setup needed for users of Leisure Line and Hitzer brand stoker stoves. If you are using a Coal-trol Digital system on a Keystoker, Alaska, Reading, Harman, or other brand automatic stoker stove you will need to adjust your IDLE, MAX, and possibly your TRBN settings. The recommended settings for which are detailed in the Recommended Settings by Stove Brand section below. Applying those settings is detailed in the SETUP and ADVANCED menu sections below.
TS2BL DISPLAY
- If display is unlit, first button press turns it on.
- Round-robin is normal cycle between room temperature and fuel feed rate [FR].
- On powerup, display may flash “Power Loss”.
- Tap the Menu button to enable outputs. Display will show RUN and begin the Round-robin.
- TS2BL is shipped in Single Setpoint Mode.
- Full capabilities of TS2BL are detailed in the full user manual.
BUTTONS & STATUS LED
- Tap UP or DOWN button to adjust temperature setting. Display will show set temperature.
- Jump back to Round-robin – press and hold Menu button for 3 seconds. Fast feed fuel for 5 minutes – press and hold Menu for 5 seconds. Display will show FEED 5.
- Change warm air fan speed – Tap Menu. Use Up/Down adjust speed. Display will show AUTO FAN or MAN FAN % speed.
Button and Display Basic Description
Operation of the TS2BL thermostat is accomplished with two types of button
presses. First is the “tap” which is a short duration press and release of a
button lasting no more than one second. The second type of press is the “press
and hold” where you press a button and hold it down for an extended period of
seconds, releasing only after reaching a desired screen or result.
Upon power up from an extended loss of power, the thermostat will go through
an initialization that displays the version number of the software, the
manufacturer the thermostat is sold by, and then “PWR LOSS” with the LCD
flashing. The Coal-trol Digital Control Module outputs will all be off in this
power outage recovery mode. This is a safety that waits for the user to
acknowledge the restart from complete loss of power before it will operate the
stove’s feeder. This will prevent the Coal-trol system from dumping a hopper
of coal into the ash pan after a power outage event that lasted long enough
for the fire to have gone out.
Acknowledge the power up and get your stove running by tapping the MENU
button. More information on how the TS2BL handles power outages and the four
different restart modes is contained in the Power Outages section.
The thermostat comes pre-configured for Single Setpoint mode (SSP). In this
mode there is only one setpoint used for all times and days of the week.
Adjusting that setpoint is as simple as tapping the UP/ DOWN buttons (or
pressing and holding them to make larger adjustments) while the unit is in the
round-robin screens. The thermostat will adjust the stove’s fire to reach and
maintain the set temperature. More details on the three available setpoint
modes can be found in the Setpoint Modes and TS2 & TS2ES Compatibility
section.
For many people, that’s all there is to it!
If you wish to use multiple setpoints, as were available with the TS2 or
TS2ES; if you need to adjust settings for one of the above mentioned stove
brands; if you have a dual stoker Coal-trol Digital system or other customized
configuration; or if you wish to learn more about the capabilities and
features of your new Coal-trol Digital TS2BL thermostat, please read on.
Recommended Settings by Stove Brand **
**
The TS2BL comes pre-loaded with settings appropriate for most Leisure Line and Hitzer brand automatic stoker stoves. If you have another brand stove please reference this table and adjust the TS2BL’s settings to the recommended defaults for your stove. These, like the pre-loaded settings, are our recommended starting points. Manufacturing differences, tolerances, and parts changes can result in the user needing to adjust from these recommendations to achieve the optimal range of operation for their stove.
Setting| Display| Leisure Line and Hitzer Stoves| Hitzer
710 Furnace| Keystoker 90/105/Koker| Reading (Tri-burner
)| Reading (separate combustion blower)| Alaska
(paddle)| Harman (Magnum)
---|---|---|---|---|---|---|---|---
Idle Feed Rate| IDLE| 6| 6| 10| 50| 5| 4|
Maximum Feed Rate| MAX| 40| 30| 85| 99| 25| 30| 99
Triburn| TBRN| N| N| N| Y| N| N| N
Mechanical| | N/A| N/A| Set feeder screw to full clockwise.|
Set red nut to ⅝” from acorn nut.
| Set red nut to tight against the acorn nut, then back off 2 turns.| N/A| Set adjustment handle to 11/16” from the acorn nut.
Follow the instructions in the sections below for accessing the IDLE and MAX settings in the SETUP menu and, if necessary, the TBRN setting in the ADVANCED menu, to apply these recommended settings.
Adjusting IDLE and MAX Fuel Limits
The TS2BL thermostat uses values set by IDLE (formerly MIN) and MAX as limits
to the minimum and maximum fuel feed allowed. IDLE sets the smallest fire size
and MAX sets maximum fire size. The recommended settings, above, should be the
starting point for any adjustment. The need for large adjustment from the
recommended settings may indicate mechanical problems with the stove that will
not be solved by IDLE/MAX adjustment. See Troubleshooting Your Stove.
While displaying IDLE or MAX, the TS2BL runs the fuel feeder at the IDLE or
MAX value shown. It is NOT doing temperature control.
When finished making an IDLE or MAX adjustment, be sure to return to RUN so
temperature control resumes.
To adjust the IDLE feed rate go to the IDLE setting in the SETUP menu. Observe
the fire. Allow the fire to “settle into” its idle firing rate. Adjust IDLE
value up or down to achieve a desired minimum fire size. Allow enough time
between adjustments for fire to settle into a new value. IDLE values typically
range between 2 and 12. If IDLE is set too low, the fire may go out. If too
large, unnecessary heat may be produced on warm days.
To adjust the maximum fuel rate, go to MAX and observe the fire. Allow the
fire to settle into its MAX rate setting. Adjust MAX value to the desired fire
size. Allow enough time between adjustments for fire to settle into a new
value. MAX values typically range between 17 and 85. If MAX is set too high,
partially burned or glowing coal may be driven off the grate. Coal should be
completely burned about 1 to 2 inches from the discharge edge of the grate.
WARNING – The Coal-trol Digital™ is capable of regulating a fire smaller than required to maintain proper chimney draft. Follow all manufacturers recommendations for minimum draft pressures and temperature. The use of mechanical means such as a draft inducer fan may be required to ensure proper draft at low fire. Installation of a carbon monoxide detector is highly recommended.
Setpoint Modes and TS2 & TS2ES Compatibility
As mentioned in the QuickStart section above, the Coal-trol Digital TS2BL
thermostat comes with the Single Setpoint, or SSP, mode of operation pre-
loaded from the factory. In this mode there is only one setpoint and it is
adjustable directly from the round-robin screens by using the UP/DOWN buttons.
The TS2BL offers two additional modes of operation:
The TS2 mode provides the setpoint experience of the original TS2 thermostat
by providing 2 programmable set points, one for daytime and one for nighttime.
These two setpoints are used on all days of the week. You get to control the
time of the setpoint as well as the temperature setting. While in this mode,
on the round-robin screens, you can perform a temporary override of the
currently programmed setpoint by using the UP/DOWN buttons to adjust the
temperature setting. When the next programmed setpoint time comes, the
programmed setpoint will take over. In this mode, you will need to set the
thermostat’s time setting in the SETUP menu. Setpoint programming is also
available in the SETUP menu, detailed in the SETUP menu section below.
Lastly, there is the ES mode, which replicates the setpoint programming
capability of the original TS2ES thermostat. In this mode, you have 8
programmable setpoints, 4 for weekdays
(morning, day, evening, and night) and 4 more for weekends. Like with the TS2
mode, setpoint programming is accomplished in the SETUP menu. You will have to
set a time as well as the day, also done in the SETUP menu. Temporary
overrides of setpoint temperatures is accomplished by using the UP/DOWN
buttons from the round-robin screens. An override will revert to the
programmed setpoint temperature when the next programmed setpoint time is
reached.
If you wish to make a long-term override of programmed setpoints, such as for
a vacation, it is recommended you switch the thermostat back into Single
Setpoint (SSP) mode and set the temperature where you want it. Any programmed
setpoints you have set up while in TS2 or ES mode will be remembered and
reinstated when you return the TS2BL back to the TS2 or ES mode.
Power Outages
The TS2BL has a new feature that better handles power outage situations. In the event of a power outage, one of four things will happen.
Nothing will Happen| Less than 4 minutes| If power is removed for less than 4
minutes the TS2BL will restart and operate normally as if nothing has
happened. Time will be kept during the outage and the clock adjusted
accordingly if using TS2 or ES mode, but there will be no
---|---|---
| | change in the operation of the stove from before the power outage.
“PRW IDLE”| 4 to 6 minutes| If power is removed for between 4 and 6 minutes,
the TS2BL will restart into an idling mode and flash “PRW IDLE” on the screen.
This is to attempt to maintain a fire, but allow you time to check on the fire
condition before normal operation resumes. Normal operation will not resume
until you acknowledge the warning by tapping the MENU button.
While in this power outage recovery mode the stove will operate at the IDLE feed rate. Normal temperature control will not happen until you acknowledge the warning. Time is kept during the outage and will be adjusted automatically when power is restored, if using TS2 or ES mode.
“PRW OUT”| Greater than 6 minutes| If power is removed for more then 6
minutes, but not long enough for the thermostat’s backup power to be depleted,
the TS2BL will restart into a power out mode and flash “PRW OUT” on the
screen. In this mode the stove motors will be turned off and the control will
wait for you to acknowledge the warning screen by tapping the MENU button,
when it will resume normal operation. This mode assumes that the fire has gone
out after 6+ minutes and will prevent coal being dumped into the ash bin. Time
is kept during the outage and will be adjusted automatically when power is
restored, if using TS2 or ES mode.
“PWR LOSS”| 1 hour or more| If power is removed for more than about an hour
the TS2BL’s backup power will likely be depleted. When power is restored the
control will startup in the power loss mode and flash “PWR LOSS” on the
screen. Tap the MENU button to start normal operation. This is the mode the
thermostat will start up in when you first power it up after installation.
Time will not be kept during this outage duration, so you will need to
manually adjust the time setting as needed if you are using TS2 or ES mode.
Test Mode
When setting up your stove, after reconnecting it from the off-season, or when
you’re troubleshooting a problem it is often useful to run the TEST mode of
the thermostat, to cycle through the outputs of the control module. The TEST
mode is located in the SETUP menu under the TEST action item.
To enter the TEST mode:
- Press and hold the MENU button for 10 seconds, until the screen reads “SETUP”, then release.
- Tap the MENU button until you see the word “TEST” on the display.
- To start the TEST mode cycle, tap the UP or DOWN button.
If you go past the TEST item, you can keep tapping MENU to loop through the
SETUP menu, until you get back to it.
While in the TEST mode cycle, the display will show what stage of the test is
being run. These stages will auto-advance in a continuous cycle, changing
every 10 seconds.
The stages and what it’s doing are:
Stage | Description |
---|---|
“ALL OFF” | Turn off all outputs. |
“STOKER” | Turn on only the stoker output. |
“COMBSTN” | Turn on only the combustion blower output. |
“CONVCTN” | Turn on only the convection blower output. |
“VENT” | Turn on only the power vent output. Only shown if CMT mode is set to |
“SV” or “SFV”, see ADVANCED menu for more information.
“SUPP FAN”| Turn on only the supplemental/aux fan output. Only shown if the
CMT mode is set to “SF” or “SFV”.
“ALL ON”| Turn on all outputs at the same time.
The cycle will repeat until you turn off the mode by tapping any button.
If you are using a CMT setting of “D” (Dual Stoker) please see below in the
Control Module Type, SETUP, and ADVANCED sections for more details on how to
use Dual Stoker features in the TS2BL thermostat and to find out how TEST mode
and its cycle stages when Dual Stoker mode is set.
Menus
In this section you’ll learn all about the menus of the TS2BL. Here are some general principles to help you navigate around.
- Tapping any button while the backlight is off will turn the backlight on. This tap to turn on the backlight will not modify any setting or influence the menus. The backlight will turn off after 2 minutes of no button presses.
- In almost all menu screens if you wait for 60 seconds the TS2BL will return to the round-robin display. This is called round-robin auto-return. If you do not want to wait, you can exit from most menu screens back to the round-robin by pressing and holding MENU for about 3 seconds (you will see the current temperature screen show up on the display). This is called jumping to the round-robin. The few menu screens where these two behaviors do not work will be noted in the descriptions below.
- Use the UP and DOWN buttons to adjust menu settings. Tap for minimum increments. Press and hold to move faster through the available setting range.
- Some items in the menus are sub-menus or action locations. To enter the sub-menu or activate the action, tap the UP or DOWN button.
Round-Robin / Home
The round-robin screens auto-advance on a timed loop to show important
information quickly, at a glance.
Screen Example | Name | Description |
---|---|---|
“ 75°F” | Current Temperature | Displays current temperature. |
“DAY 71°F” “OVR 82°F” | Setpoint Temperature | Displays current setpoint. |
In SSP mode this is not shown. It will only show when the thermostat is in |
“TS2” or “ES” mode (see ADVANCED menu section).
| | In TS2 or ES modes this will show “MOR”, “DAY”, “EVE”, “NIT”, “OVR” for
Morning, Day, Evening, Night, or Override as is appropriate for the mode and
the current setpoint setting being used.
“FR 99%”| Feed Rate| Displays the current fuel feed rate.
That’s the end of the round-robin screens. If you use the UP/DOWN buttons while in the round-robin screens, you will be brought to the Change Setpoint screen.
“SET “OVR “NIT| 76°F”
73°F”
62°F”| Change Setpoint| By using UP/DOWN buttons from any round-robin screen,
you will be put into this screen where you can adjust the setpoint. You will
notice that the display flashes rapidly to help indicate you are in
temperature adjustment mode.
---|---|---|---
| | | In SSP this screen will read “SET” followed by the setpoint setting.
This setting will be maintained until you change it again.
| | | In TS2 or ES modes this adjustment is a temporary override until the
next programmed setpoint time is reached. When the setpoint temperature does
not match the currently programmed setpoint, it will read “OVR” followed by
the temperature setting. If the setting matches the currently programmed
setpoint, it will show the currently programmed setpoint name – “MOR”, “DAY”,
“EVE”, or “NIT” – followed by the temperature setting.
| | | Tap the MENU button to return to the round-robin, or wait 5 seconds.
Lastly, if the thermostat detects a temperature higher than 95℉, it will go
into a “HITEMP” alarm mode where the control will shut down all outputs and
flash “HITEMP” on the screen. To exit this alarm state you must wait until the
room temperature has fallen below 95℉ and then tap the MENU button to
acknowledge the condition and allow the control to start operating normally
again.
The round-robin screens will look like this when you’re in “SSP” (Single
Setpoint) mode (default):
These screens will look like this in “TS2” mode:
In “ES” mode the screens will look like this:
Quick Menu
Enter the quick menu by tapping MENU once while in any of the round-robin
screens. Tap MENU to move through each screen. Tap MENU again on the last
screen to return to the round-robin screens.
Screen Example | Name | Description |
---|---|---|
“AUTO FAN” “FS 25%” | Fan Speed | Displays the fan speed setting. It will read |
“AUTO FAN” when the fan is being controlled by the TS2BL’s logic. It will read
“FS” followed by a percentage value between 1 and 99% when you have it in
manual fan speed mode.
You can adjust from auto control to manual by using the UP/DOWN buttons. Reset
it to AUTO mode by trying to set a value of 0% or 100%.
“ 5:10AM” “THU 10:13PM”| Current Day and Time| Displays the current day
and time. This screen is not shown if the SPM setting (see ADVANCED section)
is set to “SSP” (default). If set to “TS2” then only the time will be shown.
If set to “ES” then both day and time will be shown.
If you tap UP or DOWN while on this screen you will be able to adjust your
time and day settings. The display initially show just the time and it will
flash rapidly to indicate you are in adjustment mode. Press and hold UP/DOWN
to make large adjustments.
Once time is set, tap MENU. If you are in “TS2” SPM mode the control will
return to the normal time display. If you are in “ES” SPM mode you will see
the day setting flashing rapidly. Use the UP/DOWN buttons to adjust the
setting. Tap MENU to return to the day/time display.
Press and Hold MENU Sequence
To reach the menus described in the sections below you need to press and hold
the MENU button. As you press and hold the menus will show up in sequence at
roughly the number of seconds listed. Press and hold until you see the menu
you wish to enter, then release the MENU button and you will be placed at the
first setting in that menu section.
3 seconds| Jump back to the round-robin. This works in most locations,
exceptions are noted in screen descriptions in the sections below.
---|---
5 seconds| FEED Fuel (action item)
10 seconds| SETUP Menu
20 seconds| ADVANCED Menu
30 seconds| RESET (action item)
FEED
The “FEED” display is an action item. Press and hold MENU for 5 seconds until
you see the word “FEED” on the screen, then release. You will enter the FEED
cycle upon releasing the MENU button, shown by a countdown starting (“FEED 5”
on the screen). While in this mode the stoker motor will run at full speed.
The number will countdown each minute. At the end of the FEED cycle the
thermostat will return to the FEED entry screen. You can exit the FEED mode
countdown by tapping any button, which will return you to the FEED action item
screen.
While in the FEED countdown, round-robin auto-return and jump to round-robin
with a 3 second press and hold of the MENU button will not work. You must exit
the FEED countdown first with a button tap.
SETUP
The SETUP menu is where the most commonly used and accessed settings options
are located. To enter the SETUP menu press and hold MENU button for 10
seconds, until you see the word “SETUP” on the screen, then release. Once in
the menu, tap the MENU button to move through the different settings, sub-
menus, and action items. Tap the UP or DOWN button to enter sub-menus or
activate action items. This menu wraps to the first item when you tap MENU
button on the last item.
Screen Example | Name | Description |
---|---|---|
“SETPTS” | Setpoints Sub-menu | Entry point for setpoint programming sub-menu. |
Tap UP or DOWN to enter this sub-menu. See below for details on
| | the items inside this sub-menu. Only shows in SPM mode “TS2” or “ES”, not
in “SSP” (see ADVANCED menu section).
“IDLE 6”| Idle Stoker Rate| Adjust the idle (or minimum) fire setting. Lower
values will reduce the fire size. Higher will increase. See the “Recommended
Settings by Stove Brand” for suggested values. While on this screen
temperature control is disabled and the stoker is forced to run at the idle
rate indicated. This menu screen will not auto-return to round-robin. This
screen remains displayed indefinitely and the stoker is run at the speed
indicated as long as you stay on this screen. Use this screen to adjust your
minimum stable fire setting. Use care when you have a natural draft chimney so
that you maintain a proper draft pressure.
“MAX 40”| Max Stoker Rate| Adjust the maximum fire setting. Lower values will
reduce the fire size. Higher will increase. See the “Recommended Settings by
Stove Brand” for suggested values. While on this screen temperature control is
disabled and the stoker is forced to run at the max rate indicated. This menu
screen will not auto-return to the round-robin. This screen remains displayed
indefinitely and the stoker is run at the speed indicated as long as you stay
on this screen. Use this screen to adjust your maximum fire size, without
pushing burning coal off the end of the grate. Use care not to overheat your
stove by running on this screen for extended periods of time. If you’re having
trouble adjusting, leave the screen, let the stove cool down, and return to
making adjustments later.
“PVS 99%”| Power Vent Speed| Adjust the speed of the power vent. This is only
available with a properly equipped control module and when the TS2BL’s “CMT”
setting is set to “SV” or “SFV” (see ADVANCED menu section). Use care to
maintain a proper draft pressure when adjusting. Follow your stove or power
vent manufacturer’s recommendations on power vent installation, draft
pressure, and motor speed settings.
“CFT 12”| Convection Fan Threshold| Adjusts the minimum feed rate at which
the convection fan will first turn on when fan speed is in the “AUTO FAN” mode
(see above in the Quick Menu section). The default setting is usually good,
but some stoves benefit from a higher or lower setting to let more or less
heat build-up in the stove body before the fan is turned on.
“FDR 2”| Feeder Selection| This controls whether 1 or 2 stokers are being run
on a Dual Stoker stove setup. Can only be used with a properly equipped
control module and is only shown when the CMT
| | advanced menu setting is set to “D” (see ADVANCED menu section).
“TEST”| Test Mode| This is the action item to enter the control module output
TEST mode. Press the UP or DOWN button to activate it. When in this mode the
display will cycle through the outputs of the control module, turning them all
off first, then each output on individually, and then finally all them on
together. This cycle will repeat until you exit the TEST cycle. To exit back
to the “TEST” prompt, tap any button.
While running the TEST cycle, the thermostat will not auto-return to the
round-robin and the jump to the round-robin by pressing and holding MENU for 3
seconds will not work. You must exit the TEST cycle by tapping a button first.
More information on TEST mode can be found in the Test Mode section.
“INFO”| About Info Sub-menu| Tap the UP or DOWN button on this menu screen to
enter the INFO sub-menu. Once in this sub-menu, you will be able to tap the
MENU button to cycle through the screens that display version information and
manufacturer information. The last item in this sub-menu is “EXIT”. Tap the UP
or DOWN button on this item to EXIT back to the “INFO” menu screen.
“EXIT”| Exit the SETUP menu| Tap the UP or DOWN button on this menu screen to
exit the SETUP menu back to the round-robin screens.
Tapping MENU on this screen will cycle you back to the top of this SETUP menu
screen set.
Setpoint Programming
Setpoints are programmed via the SETPTS sub-menu in the SETUP menu. To enter
the sub-menu tap UP or DOWN on the SETPTS sub-menu item. This sub-menu is only
displayed if the thermostat is in the “TS2” or “ES” mode (see SPM in ADVANCED
menu section below and the Setpoint Modes and TS2 & TS2ES Compatibility
section above for more information on this setting).
Remember, after making any adjustments, you do not need to exit via the “EXIT”
menu options, you can press and hold the MENU button for 3 seconds to jump
back out to the round-robin, or you can simply leave the thermostat alone and
in 60 seconds it will auto-return to the
round-robin.
“TS2” SPM Mode
If your control is in the “TS2” SPM mode, you will see these options:
Screen Example | Name | Description |
---|---|---|
“DAY 6:00AM” | Day Setpoint Time | Used to set the day setpoint time. |
“DAY 75°F” | Day Setpoint Temperature | Used to set the day setpoint |
temperature.
“NIT 10:00PM”| Night Setpoint Time| Used to set the night setpoint time.
“NIT 62°F”| Night Setpoint Temperature| Used to set the night setpoint
temperature.
“EXIT”| Exit Setpoint Menu| Tap the UP or DOWN button to exit the SETPTS sub-
menu.
“ES” SPM Mode
If your control is in the “ES” SPM mode, you will see these options:
Screen Example | Name | Description |
---|---|---|
“WKDAY” | Weekday Setpoint Sub-Menu | Tap the UP or DOWN button to enter the |
weekday setpoint sub-menu.
“WKEND”| Weekend Setpoint Sub-Menu| Tap the UP or DOWN button to enter the
weekend setpoint sub-menu.
“EXIT”| Exit Setpoint Sub-Menu| Tap the UP or DOWN button to exit the SETPTS
sub-menu.
Within the “WKDAY” and “WKEND” submenus you will find this set of options:
Screen Example | Name | Description |
---|---|---|
“MOR 6:00AM” | Morning Setpoint Time | Use to set the morning setpoint time. |
“MOR 75°F” | Morning Setpoint Temperature | Use to set the morning setpoint |
temperature.
“DAY 10:00PM”| Day Setpoint Time| Use to set the day setpoint time.
“DAY 62°F”| Day Setpoint Temperature| Use to set the day setpoint
temperature.
“EVE 6:00AM”| Evening Setpoint Time| Use to set the evening setpoint time.
“EVE 75°F”| Evening Setpoint Temperature| Use to set the evening setpoint
temperature.
---|---|---
“NIT 10:00PM”| Night Setpoint Time| Use to set the night setpoint time.
“NIT 62°F”| Night Setpoint Temperature| Use to set the night setpoint
temperature.
“EXIT”| Exit weekday or weekend sub-menu| Tap UP or DOWN button to exit the
WKDAY or WKEND sub-menu.
ADVANCED
WARNING: You can modify settings in this menu that can make your stove
and the thermostat behave unexpectedly. It is highly suggested that you write
down current settings before making adjustments, so you can return back to the
prior setting if an adjustment does not work the way you expect. This menu is
intended for infrequent use and only by those who have a specific need to do
so.
To access the ADVANCED menu press and hold the MENU button for 20 seconds,
until the screen reads “ADVNCD”, then release the button. Tap the MENU button
to move through the various settings. Use the UP and DOWN buttons to make
adjustments to settings. Exit via the EXIT item at the end of the menu set, or
press and hold MENU for 3 seconds, or wait for 60 seconds to auto-return to
the round-robin.
Screen Example | Name | Description |
---|---|---|
“A 76.3°F” | Temperature Calibration | Use this screen to adjust the |
temperature reading calibration. If you notice that the TS2BL’s temperature
readings do not match with another thermostat. Tap or press and hold the UP
and DOWN buttons to adjust to the value you believe the temperature should
read. The temperature will change in the smallest increments the TS2BL is able
to work in, but you will notice that it is not a consistent change of 0.1℉.
There are roughly 7 UP/DOWN taps per degree Fahrenheit of resolution
available.
“DEG F”| Degree Mode| Use this screen to change the thermostat between
degrees Fahrenheit and Celcius.
“SPM SSP”| Setpoint Mode| Use this screen to select the Setpoint Mode the
thermostat will use. By default, it is shipped in Single Setpoint Mode (SSP).
In this mode, there is only one
| | setpoint and it is used all the time. Changes to it carry forward until
you change it again. There are also the “TS2” and “ES” settings. These modes
are described in the Setpoint Modes and TS2 & TS2ES Compatibility section of
this manual.
“TBRN OFF”| Tri-burn Mode| Use this screen to adjust the control to operate a
“Tri-burn” equipped coal stove. These stoves operate both the stoker and convection air blower with a single motor. When set to “ON” this stoker output will operate using a hybrid speed controlled and time-proportioned scheme, in order to supply more consistent combustion air at lower feed rates. In “OFF” mode (default) the stoker output is time-proportioned only and combustion air blower is always running to provide for the most efficient burn. Please read the Tri-burner Stoves section for more information on this setting and using the Coal-trol Digital system with Tri-burner style stoves.
“CMT S ” “CMT SFV”| Control Module Type| Use this screen to set what kind of
control module you have connected to the thermostat. The options include: “S”
– Stoker (default and used by 95% of users)
“SF” – Stoker & Aux Fan (used if you had an optional Aux-Fan “dry contact”
output added to your system). “SV” – Stoker & Vent (used in some OEM
configurations that include an integrated motorized exhaust vent) “SFV” –
Stoker, Aux-Fan, Vent“D” – Dual Stoker (used on select OEM configurations that
feature thermostat controlled dual stoker feeder selection and control)
For more details on this setting please look below in the Control Module Type section.
“SFT 15”| Supplemental Fan Threshold| Use this screen to control the minimum
feed rate your Aux-Fan output will engage at. Aux-Fan is most typically used
to integrate the Coal-trol system with a central air furnace blower, for
whole-house heated air circulation.
This is an optional add-on feature available with Coal-trol control modules.
This will only be shown if you are using a CMT setting of “SF” or “SFV”.
“CFMN 18”| Convection Fan Minimum| Use this screen to set the slowest speed
your convection fan will turn at. In other words, the speed the motor will
turn when a manual fan speed of 1% is used. This is useful if you have a
“sticky” convection blower fan, that hums but doesn’t turn at minimum speed
(increase the setting). Likewise, if you have a very easy-to-turn convection
blower, you may find you can lower this setting to get an even slower minimum
fan speed.
| | In general you should not adjust this setting unless there is a problem
with the fan turning at low speed settings, or you are guided to adjust it
during a customer service contact.
Use with care, it is possible to set this low enough that your convection
blower will not turn, but will generate heat in the motor.You should always
use a CFMN setting that reliably turns the motor.On prior versions of the
Coal-trol thermostat, this was called the CFM setting.
When on this screen the convection fan control will be overridden and it will
be run at the speed associated with the setting value.
This number should not be thought of as a percentage. It is an electrical
timing control value. The lower it is, the less power will be applied at
minimum fan speed settings.
“CFMX 80”| Convection Fan Maximum| Use this screen to set the maximum speed
your convection fan will turn at. In other words, the speed the motor will
turn when a manual fan speed of 99% is used. This is useful if your fan is
noisy at maximum speed and you wish to set a quieter maximum speed setting.
This is a new setting that wasn’t available on prior Coal-trol thermostats.
Like CFMN, when on this setting screen the convection fan control will be
overridden and the fan will be run at the speed associated with the setting
value.
Also like with CFMN, this number should not be thought of as a percentage. It
is an electrical timing control value. The higher it is, the more power is
applied to the motor at maximum fan speed settings.
“PVM 15”| Power Vent Minimum| Use this to control how fast the power vent
motor spins at a PVS setting of 1%. This is only shown when CMT is set to “SV”
or “SFV”.
It is very similar to the CFMN setting, but applied to the vent motor output,
if your control module is so equipped.
All the same warning apply about modifying the setting.
It is used to overcome “sticky” vent motors to ensure reliable fan turning at
minimum speed.
| | When on this setting the vent output will be overridden to run at the
speed associated with the setting value. And this should not be thought of as
a percentage, rather it is an electrical timing value.
“PLM ON“| Power Loss Modes| This defaults to “ON”. Use this to disable the
power outage recovery modes of “PWR IDLE” and “PWR OUT”. Total power loss,
which depletes the reserve power of the thermostat, will still still start up
in “PWR LOSS” mode where you have to acknowledge the screen to get into the
running mode. All other power outage scenarios will restart into a running
state without waiting for a user MENU button acknowledgement.
“MF 60”| Manual Fan Safe Threshold| This and the following setting, MT, are
used together to control under what conditions the thermostat will take fan
speed control back to AUTO FAN when the user has it set for a manual fan
speed.
“MT 60”| Manual Fan Safe Time|
“EXIT”| Exit the ADVANCED menu| Tap the UP or DOWN button on this menu screen
to exit the ADVANCED menu back to the round-robin screens. Tapping MENU on
this screen will cycle you back to the top of the ADVANCED menu screen set.
RESET
WARNING! Activating this action item is irreversible. Use only as a last
resort.
The RESET entry is an action item. To reach it press and hold MENU for 30
seconds, then tap UP or DOWN to activate it. Doing so will factory reset your
thermostat to default settings and then reinitialize the control as if it had
been powered up for the first time.
All settings modifications that you have made since first powering it up will
be lost. If your stove dealer or manufacturer modified the default settings,
those settings will also be reset to Automation Correct factory settings.
This is useful if you get into a configuration that isn’t working and you
don’t know how to fix it. This should be a last resort step. Please contact
Automation Correct customer support before taking this action.
Advanced Topics
Control Module Type
Both through optional customized orders of our standard control module and the
various stove OEM manufacturer configurations that we support for different
styles of stove equipment, we have supported a variety of features over the
years. In the prior TS2 and TS2ES thermostats, these different kinds of
systems have required purpose specific firmware to be loaded that’s intended
for use with those system configurations. With the TS2BL, this is no longer
the case. The new thermostat supports many of these configurations with a
single firmware and an ADVANCED menu setting called “CMT”, or Control Module
Type.
By adjusting CMT to match your control module’s supported features, you or
your stove dealer can take advantage of all the enhanced functionality your
Coal-trol Digital system and heating equipment have to offer.
The options supported by the CMT setting are:
- “S” – Single Stoker: This is the default setting and applies to the vast majority of users and stove OEM configurations. This supports the standard single stoker and combustion blower (both Tri-burn single motor setups and the more standard 2 motor setups), and a speed controlled convection blower.
- “SF” – Single Stoker & Aux-Fan: Select this if your control module has the “dry contact” option as an add-on, which is typically used to integrate with and control a central air furnace fan. Selecting this option will cause the “SFT” setting in the ADVANCED menu to become available. The “SUPP FAN” output in the TEST mode will also be enabled.
- “SV” – Single Stoker & Vent: Select this if your control module has support for a speed controlled power vent output. Control modules of this type are only available to stove OEMs and only used on specific models. When selected, both the “PVS” setting in the SETUP menu and the “PVM” setting in ADVANCED menu will become available. The “VENT” output in the TEST mode will also be enabled.
- “SFV” – Single Stoker & Aux-Fan & Vent: Select this if your control module has support for both an Aux-Fan dry contact output and a speed controlled power vent. Control modules of this type are only available to stove OEMs and only used on specific models. This setting combines the effect of “SF” and “SV” settings of CMT. When selected, the “PVS” setting in the SETUP menu and the “SFT” and “PVM” settings in the ADVANCED menu will become available. The “SUPP FAN” and “VENT” outputs in the TEST mode will be enabled.
- “D” – Dual Stoker: Select this if your control module has support for independent control of the motors on each stoker. There will be two individual stoker motor output receptacles available on your control module (not plugged into a Y-Splitter cord) and two combustion blower motor receptacles, as well. Control modules of this type are only available to stove OEMs and only on specific models of dual stoker furnaces. Selecting this will make the “FDR” setting in the SETUP menu available. It will also modify the TEST mode sequence to: “ALL OFF”, “COMB 1”, “STOKER 1”, “COMB 2”, “STOKR 12”, “CONVCTN”, “ALL ON”. COMB 2 and STOKR 12 phases will only be included in the cycle if the FDR setting in SETUP is set to 2.
In general almost all users have a Single Stoker “S” type of control module.
These have a stoker, combustion, and convection plug/receptacle on or attached
to the control module. They may also include an “Igniter” output, that was for
a now discontinued feature. Those that optionally purchased an Aux-Fan dry
contact set should generally select the “SF” setting. If the Coal-trol Digital
control module has a vent plug/receptacle on it, you should use the “SV”
setting. Select “SFV” if you have both dry contact outputs and a vent output
on or attached to the Coal-trol Digital control module. Lastly, if your
control module has two independent outputs for two stokers, and another two
for two combustion blowers, and one for a convection blower (or convection
blower pair, supported by a Y-Splitter cord) select setting “D” for Dual
Stoker.
If you happen to have one of our early “Advanced” system control modules that
are labeled either “CM1”, “PB1”, or “CM1-4” that had five three prong power
receptacles, as well as two 2 prong receptacles for safety switch support, and
a aux-fan dry contact set on the side: Thank you for your early support of our
products! Your control module supports the features of “SF” for the CMT
setting. However, if you were using your original thermostat still, not an
upgrade to the TS2 or TS2ES, you should contact Automation Correct customer
support. Particularly if you hear a buzzing or chattering sound from the
control module while running it with the TS2BL. Your control module may need a
modification to be fully compatible with the TS2BL control.
If you are unsure of what kind of control module you have and have reason to
believe your control module may support options besides those offered by the
“S” setting, please consult the documents included with your stove, contact
your stove dealer or manufacturer, or contact Automation Correct customer
support.
Dual Stoker
In addition to the details provided in the Control Module Type, SETUP, and
ADVANCED sections above, please consult the original documentation that came
with your stove. If you have questions or are having a problem using the dual
stoker features with your stove with the TS2BL, please contact your stove
dealer, stove manufacturer, or Automation Correct customer support for one-on-
one support.
Tri-burner Stoves
Tri-burner style stoves use a single motor to drive both the stoker mechanism
and the combustion air blower, instead of the more common arrangement of a
motor driving the stoker and a separate motor turning the combustion blower.
The Coal-trol Digital system does run these stoves (see TBRN setting in the
ADVANCED menu) and we do have a recommended mechanical setup to go along with
our recommended IDLE and MAX settings in the Recommended Settings by Stove
Brand section. The nature of the single motor driving both stoker and
combustion air results in a less efficient low fire system than what is
capable with a 2 motor arrangement. Tri-burn stoves have limited turn down
potential at IDLE. While the Coal-trol Digital can and does run Tri-burner
style stoves and furnaces, we do recommend people convert to two separate
motors to drive the stoker and combustion blower to get the best range of low
fire and high fire performance from your stove with the Coal-trol Digital
system.
There are some coal fired heating appliances that, similarly to Tri-burn
stokers, also utilize one motor to drive both stoker and combustion air, but
they also employ a solenoid to disengage the stoker linkage from the motor.
This allows the motor to run continuously to drive combustion air, while the
stoker is switched on and off as needed. Unfortunately, the Coal-Trol Digital
control system is not designed to work with this style of stoker system, at
least not without modifications. If you have one of these stoker systems,
please contact Automation Correct for support.
Manual Fan Safe Threshold and Time Settings
When using the Manual Fan speed setting, Man Fan, the thermostat is still
regulating room temperature. If the manual fan setting is a slower speed the
stove body may become quite hot if the fire is or is commanded to become large
(FR > 50%). To prevent this overheating situation the TS2BL will automatically
change from Man Fan setting to Automatic Fan control.
Two settings, MF (Manual Fan Safe Threshold) and MT (Manual Fan Safe Time) act
together to provide a safety against running the stove at a consistently high
feed rate for an extended period of time while the control is in manual fan
mode.
Most people use Manual Fan mode to run the convection fan at a fixed, slow
speed, to keep a constant light, low noise circulation in the room the stove
is in. We discovered that some lower cost, lower quality stoves were
experiencing damage to their convection fans, particularly units with the fans
mounted relatively high on the back of the stove body. The damage was the
result of overheating due to users running low manual fan speeds while the
stoves were running on the higher end of the feed rate capability of their
stove. The fans were not moving enough air to cool themselves nor the stove
body.
To combat this problem the Manual Fan Safe system was added to the Coal-trol
Digital thermostats several years ago.
These two values, MF and MT (located in the ADVANCED menu), when multiplied
together cannot exceed a value of 3600. If you increase one of the two so that
the value of 3600 would be exceeded, the control will automatically reduce the
other setting to maintain a maximum multiplied value of 3600. Why 3600?
Because the two numbers when multiplied in effect represent a BTU type of
value. Through trial and error we arrived at 60 minutes running at a FR of 60
being a sweet spot for total heat generation before this fan overheating
effect became a concern. This 3600 value serves as a target total heat output
value we want to protect against exceeding without automatic fan control
kicking in to run the fan at an appropriate speed to get rid of the heat in
the stove body and convection fan motor.
The way these values are used is that if feed rate is over the MF setting, the
control will start a timer. As long as the FR remains over the MF setting and
manual fan speed is still in use, the timer will continue until it reaches MT
minutes. At that point AUTO FAN mode will be reinstated. Any dip in feed rate
below MF or the user setting fan control back to AUTO FAN will result in the
timer being reset.
TIP: If you like to run a constant low fan speed, even when the stove is at
IDLE feed rate, instead of using manual fan speed, try this: set a CFT setting
of 0 (SETUP Menu) and then adjust the CFMN setting (ADVANCED menu) to suit
your desired, always-on low fan speed. And use the new CFMX setting (also in
ADVANCED menu) to set a top fan speed that you can live with and that will
move enough heat off of the stove in a high feed rate condition. Then run the
fan speed in AUTO FAN. This will allow the control to ramp up when needed to
meet a high FR condition, but keep a constant low fan speed going when in
lower feed rate, and set a fan speed range that is acceptable to you from both
a noise level and safety perspective.
Where did HLF go?
HLF (Heat Loss Factor) in the TS2 and TS2ES thermostats was a good idea that
was poorly implemented. We’ve discontinued it for now while we work on an
alternative setting that will allow users to adjust the tuning of the control
to better match some particular installation needs.
We’ve found that most people are able to address the problem HLF was intended
to solve by using a combination of increasing air circulation, increasing the
IDLE setting, or mounting their thermostat in a better location.
If you find you are having trouble with far too sluggish response, please
contact our support through phone or email so we can help troubleshoot your
situation and try to get you satisfied with your Coal-trol Digital coal stove
control system.
The Temperature Keeps Overshooting Way Above Setpoint
Some Coal-trol users run into a problem where the temperature in the house or
room overshoots significantly past the setpoint. This can happen due to
external heating (dramatic outside temperature swing upward, swings caused by
the sun and the particular construction of the house, etc.) or due to a
setpoint change upward and the space being heated much more quickly than the
control’s tuning is set up to expect.
Like with the HLF setting discussed above, we are working on a new setting
that will help address the need for faster response to externally generated
temperature swings and situations where upward setpoint changes result in
large overshoots past setpoint. For now, our recommendations are to make sure
your thermostat has good air circulation around it. If it is in an alcove or
otherwise insulated from registering temperature changes in the dwelling, it
will be slower than normal to react. You can also try adjusting your MAX
setting down. The better insulated and air sealed the house is (particularly
the case in newer construction or recently updated houses) the faster the air
space will heat up. Similarly, if you “oversized” your coal stove for your
dwelling size or average heat loss you may encounter the same situation of
overshooting target temperature setting. In both cases lowering your MAX
setting, even going so far as to cut it in half, can dramatically help the
problem. Sometimes this adjustment is seasonal, where in the Fall and early
Spring you may need to use a lower MAX setting, but as colder days set in you
can adjust it upward toward the original setting.
Generator and Off-Grid Power
Most Coal-trol Digital users operating with generator and other off-grid power
supply options have success. The power supply should be a pure sine-wave, 60
hz, 120VAC type. Modified sine-wave and other power supply distortions can
cause problems for both the time keeping circuit and the speed control
circuits of the Coal-trol Digital system. Even with non-inverter, pure-sine
wave generators, if the generator has dirty or worn brushes or other
mechanical/electrical issues, the output can be quite “noisy” and result in
erratic behavior by the Coal-trol Digital system. Because of the wide
variability in power output type and condition of the output power from non-
grid sources, we offer no guarantees as to how the Coal-trol will function
with these alternative power sources. If you encounter a problem using the
Coal-trol with an alternative power generation system, please contact customer
support for assistance.
Boiler, Biomass, Gasifier, and Other Heating Appliance Types
The Coal-trol Digital is designed to run forced air automatic stover stoves
and furnaces. We do offer controls to manufacturers for other types of heating
appliances, such as corn and pellet furnaces, biomass and coal boilers, and
wood gasifier appliances, but we do not currently sell these control types
directly to end users. These are only sold to manufacturers for use as an OEM
component.
There is too much variation in installation enclosures, motor types, feed
system types, etc. to make a good, low cost, general purpose control that most
users would be able to install and configure properly.
If you’re interested in such a control to retro-fit to your heating appliance,
please let us know. If there’s enough interest to support making a product it
may just happen.
Troubleshooting Your Stove
The Coal-trol Digital System is only the command and control component of a properly operating appliance. If the Control Module power light is ON, and the Thermostat is displaying normally, the easiest way to determine the source of an electrical or mechanical problem is to go to TEST mode and observe for proper operation of the controlled item.
Problem | Possible Cause(s) | Possible Solution(s) |
---|---|---|
Power Light on Control Module is not ON |
- No power to Control Module.
- Fuse blown in Control Module.
| Check power.
Turn Power switch ON.
Before replacing fuse, test each motor by unplugging it from Coal-trol and
plugging it directly into an outlet.
Replace fuse.
Bad Motor or bad wiring. Bad Control Module.
Thermostat has no display.|
- No power to Control Module.
- Cable not snapped in.
- Bad cable.
| Check power.
Snap in both ends of cable. Replace cable.
Bad Thermostat. Bad Control Module.
Fire goes out now, but was working before.|
- Stoker mechanism jamming or dragging.
- Hopper clogged or empty.
- Stoker motor defective.
- Combustion blower defective.
| Go to TEST mode and verify that the Stoker motor and Combustion blower are
working.
Troubleshoot mechanicals. Verify fuel quality and sizing. Bad control cable.
Bad Thermostat Bad Control Module.
Hot coals falling off of grate.|
- MAX set too high.
- Combustion blower is dirty or needs lubrication.
- Control problem.
|
- Go to TEST mode and verify that the Stoker motor and Combustion blower are working properly. If not, replace Control Module.
- Perform MAX/MIN adjustment.
Hardware Troubleshooting
Instructions:
With Coal-trol Control Module plugged in, begin at START box and
systematically work to identify problem cause. For for service contact your
dealer or call Automation Correct at
315-299-3589.
Specifications
Automation Correct LLC is constantly working to improve our products. For this
reason, all specifications are subject to change without notice. Not all
versions include all control options.
TS2BL Thermostat: For Indoor Use Only
Temperature:
- Displayed Precision 1°F/1°C
- Accuracy ±2°F/±1.8°C @ 68°F/20°C
Electrical:
- Input Power 8VAC, 2.5VA CLASS 2
- Connection to Power Module RJ45 – 8 PIN, 100ft Maximum (Standard Ethernet Straight Cable)
Mechanical:
- Dimensions 4″ L x 4 ¾ ” W x 1 1/4″ H
- Construction ABS Plastic, UL94V-0
Environmental:
- Operating Temperature 95°F/35°C (Limited by software)
- Storage Temperature 40°F to 120°F
- Weight Less than 1 lb./0.45Kg
Designed for use with the Coal-trol Digital System only.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
Syracuse • NY
www.automationcorrect.com
Copyright 2004-2022 Automation Correct LLC. All rights reserved. Coal-trol Digital™, Pelli-stat™, Corn-trol™, by Automation Correct LLC All others trademarks by the respective owners.
© 2022 Automation Correct, LLC
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>