BG ELECTRICAL CURAFDB10A-01 Tall Body Combined AFDD Instruction Manual

June 11, 2024
BG Electrical

ELECTRICAL CURAFDB10A-01 Tall Body Combined AFDD
Instruction Manual
Fortress Circuit Protections AFDD

Combined RCBO/AFDD
Electronic line voltage dependent device 1P + N (switch neutral) with flying lead insulated flexible copper wire

Installation Advice

This device must be installed by a qualified skilled person (electrically) in accordance with all relevant regulations including wiring regulations BS7671.
Insulation resistance test:
SWITCH OFF the device before an insulation resistance test between live conductors of the final load circuit as defined in the standard BS EN 62606. During commissioning the device must be tested using the test button, marked “T”; the device must trip immediately. This test must be repeated throughout the installed life of the device at intervals defined by relevant regulations including wiring regulations BS7671. This verifies the electrical and mechanical parts of the device only. Only for use within BG Consumer Units.
Test after installation
The interference transmission requirements as defined in the standards CISPR 14-1 and DIN EN 61000-6-3 (limit value class B) must be observed for the devices operated in the electrical installation (equipment). Non-compliant or defective devices (equipment) may cause interference which can influence the response sensitivity of the arc fault detection device.

Description

B or C MCB tripping characteristics
Type A RCD classification
30mA Rated residual operating current I Δ n
~230V/240V Rated voltage Un 50/60 Hz
Rated short circuit breaking capacity (A) / lcn=6000A
Energy limiting class
Ambient temperature range -25°C to + 40°C

Connection Diagram

BG ELECTRICAL CURAFDB10A 01 Tall Body Combined AFDD - Connection
Diagram

LED indication

LED Indication after tripping and re closing Description
Overcurrent Fault

or
Residual Current Fault
| Series Arcing Fault
or
Parallel Arcing Fault
BG ELECTRICAL CURAFDB10A 01 Tall Body Combined AFDD - Bkink
1| Overvoltage Fault (U>275V)
BG ELECTRICAL CURAFDB10A 01 Tall Body Combined AFDD - Bkink
2| Internal Self-Test Fault

Torque settings

| Cross section| Screw torque
---|---|---
Line terminal| 16mm²| 2Nm
Load terminals| 10mm²| 1.2Nm

Notes

| ALWAYS SWITCH OFF THE MAINS POWER BEFORE INSTALLING THIS DEVICE INTO A CONSUMER UNIT
---|---
| COMPLETE ALL CONNECTIONS, INCLUDING BLUE N FLYING LEAD,BEFORE RESTORING MAINS POWER

AFDD part operating criteria

Series Arcing Fault

Load current (A) Maximum allowed tripping time (s)
2.5 1
5 0.5
10 0.25
16 0.15
32 0.12
40 0.12

Parallel Arcing Fault

Test current (A)| Maximum allowed number of arcing half-waves within 0.5s (N)
---|---
75| 12
100| 10
150| 8
200| 8
300| 8
500| 8

Batch Code explanation
yyWxx Manufacturing date code, year of manufacture (yy) and week of manufacture (Wxx)

Address/Helpline

Luceco PLC
Stafford Park 1
Telford TF3 3BD
ENGLAND
(EU) Luceco SE
C/ Bobinadora 1-5
08302 Mataró
SPAIN
If you have further technical assistance you can get in touch with our
Technical Helpline on:
+44 (0)3300 249 279
technical.support@bgelectrical.co.uk

Environmental Protection

This symbol is known as the “Crossed-out Wheelie Bin Symbol”. When this symbol is marked on a product or battery, it means that it should not be disposed of with your general household waste. Some chemicals contained within electrical/electronic products or batteries can be harmful to health and the environment. Only dispose of electrical/electronic/battery items in separate collection schemes, which cater for the recovery and recycling of materials contained within. Your co-operation is vital to ensure the success of these schemes and for the protection of the environment.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

BG Electrical User Manuals

Related Manuals