Schneider Electric XW Pro 8548 Hybrid Inverter Charger Installation Guide

June 9, 2024
Schneider Electric

Schneider Electric XW Pro 8548 Hybrid Inverter Charger

Schneider-Electric-XW-Pro-8548-Hybrid-Inverter-Charger-
PRO

Product Information

The XW Pro AC Coupling Solutions Guide is a user manual provided by Schneider Electric. The guide provides information and instructions on designing an AC coupled installation using XW Pro battery inverters and PV inverters. It is intended for use by qualified personnel who have training, knowledge, and experience in installing electrical equipment and applying all applicable installation codes.

Product Usage Instructions

  • Before attempting to install, operate, service or maintain the XW Pro AC Coupling Solutions, it is important to read the instructions carefully and become familiar with the device. The user manual contains important safety information that should be followed to avoid personal injury or damage to the equipment.
  • Only qualified personnel should install, operate, service, and maintain electrical equipment. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. If you are unsure whether you are qualified to use this product, please seek assistance from a qualified electrician or contact Schneider Electric for more information.
  • The XW Pro AC Coupling Solutions Guide provides detailed instructions on designing an AC coupled installation using XW Pro battery inverters and PV inverters. It is important to follow these instructions carefully to ensure proper installation and operation of the equipment. For country-specific details or further assistance, please contact your local Schneider Electric Sales Representative or visit the Schneider Electric Solar Business website at https://solar.schneider-electric.com.

Safety Information

Important Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

  • The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
  • This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
  • DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
  • WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
  • CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
  • NOTICE is used to address practices not related to physical injury.

Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. For more information, see Audience.

Audience

This guide is intended for use by qualified personnel who plan to design an AC coupled installation using XW Pro battery inverters and PV inverters.
The qualified personnel have training, knowledge, and experience in:

  • Installing electrical equipment.
  • Applying all applicable installation codes.
  • Analyzing and reducing the hazards involved in performing electrical work.
  • Installing and configuring batteries.
  • Selecting and using Personal Protective Equipment (PPE).

Configuration, servicing, and maintenance must be performed by authorized service personnel only. Authorized service personnel meet the requirements for a qualified installer, plus they have received specific training from the manufacturer on servicing the XW Pro battery inverters and PV inverters. The qualified personnel must refer to XW Pro Installation Guide (document number 990- 91228 or 990-91403) for full safety information.

DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This document is in addition to, and incorporates by reference, the relevant product manuals for XW Pro inverter/charger. Before reviewing this document, you must read the relevant product manuals. Unless specified, information on safety, specifications, installation and operation is as shown in the primary documentation received with the product. Ensure you are familiar with that information before proceeding.
Failure to follow these instructions will result in death or serious injury.

About

Purpose This Solutions Guide provides planning information and safety guidelines for designing an AC-coupled system beyond what is available in the Installation and Owner’s guides.

Scope

  • This Solutions Guide applies to XW Pro battery inverters and compatible Schneider Electric or 3rd party PV inverters.
  • The information provided below does not modify, replace or waive any of the terms and conditions mentioned in the Installation and Owner’s guides, including but not limited to the limited warranty.
  • This document also specifies typical XW Pro and PV inverter settings but the user must also consult the PV inverter manufacturer.

Related Documents

  • XW Pro Li-Ion Battery Solution Guide (document number 990-6359)
  • XW Pro Installation Guide (document number 990-91228 or 990-91403)
  • XW Pro Multi-unit Design Guide (990-91373)

Introduction

Prerequisites
It is recommended to upgrade to the latest XW Pro and Conext Gateway firmware before configuring the equipment. Consult Conext Gateway Owner’s Guide (975-0806-01-03) and XW Pro Owner’s Guide (document number 990-91227 or 990-91402) for firmware upgrade instructions. To find the latest firmware, go to https://solar.schneiderelectric.com/products/inverterchargers/>yourproduct>Downloads>Firmware.

RISK OF INJURY AND EQUIPMENT DAMAGE

  • To prevent battery damage in a micro-grid AC system, always use the latest firmware available for your inverter.
  • If Li-ion batteries are used, ensure they have an external battery management system (BMS).

Failure to follow these instructions can result in injury or equipment damage.

Overview
When a PV inverter is connected to the AC output of a battery inverter, the system is referred to as an AC-coupled system. In this configuration, the PV inverter is exposed to the AC output voltage of the battery-based inverter, which is responsible for grid forming during off-grid/backup operation. The PV inverter injects power to the critical load panel and the AC output of the battery-based inverter. The inverters are thus “AC-coupled” with each other and are able to share PV solar and/or battery energy to the loads.Schneider-
Electric-XW-Pro-8548-Hybrid-Inverter-Charger- \(1\)

An example of AC Coupling with the XW Pro is shown in Figure 1. The PV system is connected to the grid through the internal relay located on the AC bus inside the XW Pro inverter. This allows power to be produced and supplied or “sold” back to the grid if it exceeds the power consumed by the critical loads. When the grid goes out of limits, the XW Pro switches to back-up and powers the critical load panel to support the loads. Thus, the XW Pro forms the grid to keep the PV inverters operating. The XW Pro switchover to back-up is almost instantaneous. In some cases, the PV inverter does not detect the transition and continues to operate without interruption. If the PV inverter detects the switch over, it will disconnect and then reconnect after re- qualifying the grid formed by the XW Pro, according to its settings.

Surplus Power in Off-Grid/Backup Modes
The most critical element of AC coupling is the use of the surplus power that the PV system produces when operating in off-grid or backup mode. The surplus power is the power that is not used by the loads. For instance, if the PV inverter produces 4 kW and the load is 1 kW, there is a surplus of 3 kW .Schneider-Electric-XW-Pro-8548-Hybrid-Inverter-Charger-
\(2\)

If there is more power being generated than can be consumed by the loads, the surplus power will flow to the XW Pro and will be converted to DC power which flows into the battery. Once the battery approaches full charge, power generation by the PV inverter must be curtailed to maintain the balance between generation and consumption. As the battery bank approaches full charge or its charge voltage, charge SOC, or current limits, XW Pro curtails PV inverter generation by raising the AC output frequency, causing compatible PV inverters to reduce their power output. This is called Frequency Shift power curtailment.

NOTICE RISK OF EQUIPMENT DAMAGE
Follow all instructions related to AC-coupled PV sizing, battery sizing, and charge settings in the following sections of this document. Failure to follow these instructions can result in equipment damage.

Planning and Installation

Supported Architectures
XW Pro inverters use Frequency Shift to regulate battery charge current coming from AC coupled PV. PV inverters used in AC coupled systems are recommended to have frequency-watt controls. Legacy inverters without frequency-watt controls can be used with some limitations (see “Operation with Legacy PV Inverters” on page 14 for more details).
Figure 3 and Figure 4 show two supported AC-coupling architectures by XW Pro battery inverter:

  • Critical loads are connected on the AC Out side of the XW Pro output (without external contactor)
  • Critical loads are connected on the AC1 side of the XW Pro output (with external contactor)

For systems using Li-ion batteries, it is recommended to operate the XW Pro with State of Charge Control enabled for enhanced AC coupling performance and DC voltage regulation at high SOC. State of Charge Control can be used when a Conext Battery Monitor or a compatible battery listed in the XW Pro Li-Ion Battery Solution Guide (document number 990-6359) is connected to the system .Schneider-Electric-XW-Pro-8548-Hybrid-Inverter-Charger-
\(3\)Schneider-Electric-XW-Pro-8548
-Hybrid-Inverter-Charger- \(4\)

Sizing
The XW Pro can be connected in various configurations from just a single unit to multiple units in parallel, or in a three-phase configuration. Regardless of the system configuration however, the maximum continuous allowable rating of AC-coupled PV inverter(s) is the lesser of:

  • 125% of maximum allowable charge power of the battery (calculated as rated continuous charge current times rated charge voltage).
  • 125% of continuous rating of XW Pro inverter(s).

For example, if battery inverter is rated for 6.8 kW of continuous power at 40°C and battery pack is rated for 3.75 kW at 40°C, then the PV inverter must be no more than 125% of lesser of two which is 4.68 kW at 40°C. In three phase configurations utilizing XW Pro battery inverters, it is recommended to use three-phase PV inverters, such as the Schneider Electric CL series, in order to provide balanced power on the three phases.

AC Coupling with a Generator
NOTICE RISK OF DAMAGE TO THE GENERATOR OR PV INVERTER
In an AC-coupled system, never connect a generator to the AC2 (GEN) port of XW Pro without an interlocked contactor to prevent parallel operation of the generator and PV inverters. XW Pro will not be able to regulate power being pushed by PV inverters into the AC2 (GEN) port and may backfeed AC power into the generator. Failure to follow these instructions can result in equipment damage.

While running a generator in an AC-coupled system, the generator provides AC power to XW Pro and PV inverters. The PV inverter detects this (it recognizes the generator as regular grid) and begins to inject power into the system. However, generators are not designed to accept backfed power, so the concurrent operation of the AC source and PV inverters must be disallowed. While the generator is running, the PV inverter must be disconnected from the circuit and therefore PV harvest is only possible when the generator is not running and XW Pro is grid-forming. This can be done with an interlocked contactor whose coil is driven by the generator output. Normally-open contacts are placed between the generator output and the AC2 (GEN) port of the XW Pro, and normally-closed contacts placed between the PV inverters and the load panel.Schneider-Electric-XW-Pro-8548-Hybrid-Inverter-Charger-
\(5\)

Operation with Legacy PV Inverters
For AC-coupled systems with legacy PV inverters without frequency-watt capability, the battery inverter will have reduced ability to regulate the battery charge. When surplus power from AC-coupled PV charges the batteries and the battery parameters (voltage, current or SOC) reach limits, the battery inverter frequency is ramped up and the PV inverter will cease producing power and disconnect. When the battery parameter which caused frequency shift drops below the limit due to loss of PV charge power, its output frequency returns to normal (50 or 60 Hz). This return to normal frequency causes the PV inverter to initiate its reconnect delay timer (usually 5 minutes), and come online. Depending on the available array power and loads, any surplus power will be used to charge the batteries and the cycle will repeat. It is recommended to set the Absorbtion Time limit to the minimum value to help reduce cycling. Where possible, it is generally recommended to install smart PV inverters with frequency-watt capability for AC coupled systems. However, operation with legacy PV inverters can be considered for grid-tied applications with less frequent outages.

Installing
Each PV inverter requires its own AC breaker in the panel to which it is connected. Although there is room to add breakers for the PV inverters directly into the XW Pro Power Distribution Panel, it is easier to install the breakers in the AC sub panel. These breakers must be installed according to the XW Pro Installation Guide (document number 990-91228 or 990-91403). The sub-panel may also contain load breakers.
To install an AC-coupled system:

  1. Install one or more XW Pro inverters according to its Installation Guide.
  2. Install one or more PV inverters according to their Installation Guides, and connected to the panel that is backed up by the XW Pro battery inverters.

Recommended Settings
NOTICE RISK OF DAMAGE TO THE BATTERY OR BATTERY INVERTER
Always follow the recommended settings described below. The battery and the XW Pro may be subject to DC over-voltage and/or over-current events in backup power or off-grid operation. The below settings aim to achieve maximum system stability. Failure to follow these instructions can result in equipment damage.

The XW Pro AC coupling controls may temporarily disconnect the PV inverters, as needed, based on battery state of charge, voltage, and the amount of power coming from the PV system.
Table 1 Battery inverter settings

Setting Value Notes
AC Coupling Enabled Enables frequency-shifting mechanism in the

battery inverter.
AC PV Charge SOC| 90%| Recommended. Threshold for SOC-based frequency shifting. Increased PV curtailment at high SOC helps regulate the battery voltage and charge within the target range.
SOC Control| Enabled| Recommended. This requires external BMS or Conext Battery Monitor.
Grid Code| The battery inverter grid code must be set according to local utility interconnect requirements.| Ensure that grid code settings match the PV inverter.

For advanced off-grid configuration refer to “Off- Grid Operation” on the next page.

For advanced grid code configuration or troubleshooting see “Troubleshooting” on page 1.

Table 2 PV inverter settings

Setting Value Notes
Grid Code The battery inverter grid code must be set according to local
utility interconnect requirements. Ensure that grid code settings match the

PV inverter.

For advanced off-grid configuration refer to “Off-Grid Operation” below.

For advanced grid code configuration or troubleshooting see “Troubleshooting” on page 1.

Off-Grid Operation
For off-grid operation (with or without a generator), as a first option, both the battery and PV inverters are recommended to be set to the same grid code. For example for 60Hz, the recommended grid code is Rule 21 and for 50Hz – Australia AS4777. The battery’s inverter frequency-shifting settings are auto-configured to match the grid code and, consequently, the PV inverter’s P(f) settings.
As a second option, when it is not possible to set the battery and PV inverter to the same grid code, it is recommended to disable Freq-Watt P(f) Droop and Freq-Watt P (f) PreDist on the battery inverter (Figure 6) in Grid Codes settings. The smart AC-coupled PV inverter’s P(f) curve should be set to start active power reduction at nominal frequency 50/60 Hz and finish it (fully reduce to zero) at 54/64 Hz. This is what the battery inverter frequency shift is configured to in case when grid code P(f) is not activated on it .Schneider-Electric-XW-Pro-8548-Hybrid-Inverter-Charger-
\(6\)

Legacy PV inverters without frequency-watt function must be set so that they trip instantly once frequency is approaching 54/64 Hz.

Copyright © 2020 Schneider Electric. All Rights Reserved.
Trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Other trademarks are owned by their respective companies.

Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER

  • MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION;

  • ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH
    INFORMATION WILL BE ENTIRELY AT THE USER’S RISK; AND

  • REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT https://solar.schneider-electric.com.
    Document Number: 990-6421
    Date: December 2020

Contact Information
For country-specific details, please contact your local Schneider Electric Sales Representative or visit the Schneider Electric Solar Business website at: https://solar.schneider-electric.com.

https://solar.schneider-electric.com