NOTIFIER NMM-100-10 Ten Input Monitor Module Instruction Manual
- June 9, 2024
- NOTIFIER
Table of Contents
NMM-100-10(A)
Ten-Input Monitor Module
Addressable Devices
Instruction Manual
General
The NMM-100-10 ten-input monitor module is an interface between a FireWarden
series control panel and normally open contact devices in intelligent alarm
systems such as pull stations, security contacts, or flow switches.
The first address on the NMM-100-10 is set from 01 to 90 and the remaining
modules are automatically assigned to the next nine higher addresses.
Provisions are included for disabling a maximum of two unused addresses.
The supervised state (normal, open, or short) of the monitored device is sent
back to the panel. A common SLC input is used for all modules, and the
initiating device loops share a common supervisory supply and ground —
otherwise each monitor operates independently from the others.
Each NMM-100-10 module has panel-controlled green LED indicators. The panel
can cause the LEDs to blink, latch on, or latch off.
NOTE: Unless otherwise specified, the term NMM-100-10 is used in this
data sheet to refer to both the NMM-100-10 and the NMM100-10A (ULC-listed
version).
Features
- Listed to UL Standard 864, 9th edition.
- Ten addressable Class B or five addressable Class A initiating device circuits.
- Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²) plug-in terminal blocks.
- Status indicators for each point.
- Unused addresses may be disabled.
- Rotary address switches.
- Class A or Class B operation.
- Flexible mounting options.
- Mounting hardware included.
Specifications
Standby current: 3.5 mA (SLC current draw with all addresses used; if some
addresses are disabled, the standby current decreases).
Alarm current: 55 mA (assumes all ten LEDs solid ON).
Temperature range: 32°F to 120°F (0°C to 49°C) for UL applications; –10°C to
+55°C for EN54 applications.
Humidity: 10% to 85% noncondensing for UL applications; 10% to 93%
noncondensing for EN54 applications.
Dimensions: 6.8″ (172.72 mm) high x 5.8″ (147.32 mm) wide x 1.25″ (31.75 mm)
deep.
Shipping weight: 0.76 lb. (0.345 kg) including packaging.
Mounting options:
- CHS-6 chassis: Up to 6 modules.
- BB-25 cabinet: Up to 6 modules.
- BB-XP cabinet: One or two modules.
Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).
Power-limited circuits must employ type FPL, FPLR, or FPLP cable as required
by Article 760 of the NEC.
NMM-100-10 supports both Class B and Class A wiring; remove shunt for Class A
operation.
Maximum SLC wiring resistance: 40 or 50 ohms, panel dependent.
Maximum IDC wiring resistance: 1500 ohms.
Maximum IDC voltage: 10.2 VDC.
Maximum IDC current: 240 μA.
Agency Listings and Approvals
The listings and approvals below apply to the NMM-10010(A)Ten-Input Monitor Module. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL Listed: S635
- ULC Listed: S635 (NMM-100-10A)
- CSFM approved: 7300-0028:256
- FM approved
Product Line Information
NMM-100-10: Ten-input monitor module.
NMM-100-10A: Same as above with ULC Listing.
BB-XP: Optional cabinet for one or two modules. Dimensions, DOOR: 9.234″
(23.454 cm) wide (9.484″ [24.089 cm] including hinges), x 12.218″ (31.0337 cm)
high, x 0.672″ (1.7068 cm) deep; BACKBOX: 9.0″ (22.860 cm) wide (9.25″ [23.495
cm] including hinges), x 12.0″ (30.480 cm) high x 2.75″ (6.985 cm); CHASSIS
(installed): 7.150″ (18.161 cm) wide overall x 7.312″ (18.5725 cm) high
interior overall x 2.156″ (5.4762 cm) deep overall.
BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis
(below). Dimensions, DOOR: 24.0″ (60.96 cm) wide x 12.632″ (32.0852 cm) high,
x 1.25″ (3.175 cm) deep, hinged at bottom; BACKBOX: 24.0″ (60.96 cm) wide x
12.550″ (31.877 cm) high x 5.218″ (13.2537 cm) deep. CHS-6: Chassis, mounts up
to six modules in BB-25.
FlashScan®, NOTIFIER®, FireWarden®, and System Sensor® are registered
trademarks of Honeywell International Inc. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of
this document is strictly prohibited.
This document is not intended to be used for installation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
subject to change without notice.
For more information, contact Notifier.
Phone:203-484-7161, FAX:
203-484-7118.
www.notifier.com
Made in the U.S. A.
DN-6990:A
06/10/2009
firealarmresources.com
Documents / Resources
|
NOTIFIER NMM-100-10 Ten Input Monitor
Module
[pdf] Instruction Manual
NMM-100-10, NMM-100-10 Ten Input Monitor Module, Ten Input Monitor Module,
Monitor Module, Module
---|---