wheelock AS-2415C AS Audible Strobe Appliances Instruction Manual
- June 9, 2024
- Wheelock
Table of Contents
- wheelock AS-2415C AS Audible Strobe Appliances
- GENERAL
- SPECIFICATIONS
- LIGHT DISTRIBUTION PER UL 1971
- SOUND OUTPUT (SPL) SETTINGS
- WIRING INFORMATION
- MOUNTING OPTIONS
- MOUNTING PROCEDURES
- MOUNTING NOTES
- Limited Warranty
- Limitation of Liability
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
wheelock AS-2415C AS Audible Strobe Appliances
GENERAL
Wheelock’s AS Audible Strobe Appliances are the industry’s first 2-wire horn
strobe alarm appliances that can provide a selectable continuous or code 3
horn tone and continuous strobe when connected directly to the Fire Alarm
Control Panel (FACP), or provide a synchronized code 3 and synchronized strobe
when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or
Power Supply (PS-12/24-8). The AS Appliances are UL Listed under Standard 1971
for Emergency Appliances for the Hearing Impaired and UL Standard 464 for
Audible Signal Appliances. They are listed for ceiling mounting and indoor use
only and equipped with a Universal Mounting Plate (UMP) that can be mounted to
single-gang, double-gang and 4” backbox, 100mm European backbox or SHBB
surface backbox (See Mounting Options). The AS Appliances use a xenon
flashtube with solid state circuitry enclosed in a rugged Lexan lens to
provide maximum visibility and reliability for effective visible signaling.
Series AS Appliances can be field set to provide either High (HI) dBA, Medium
(MED) dBA or Low (LO) dBA sound output. All Series AS models are designed for
use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (FWR)
input voltage. All inputs are polarized for compatibility with standard
reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel
(FACP).
NOTE: The code 3 horn incorporates the temporal pattern (1/2 second on,
1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and
repeat) specified by ANSI/NFPA for standard emergency evacuation signaling.
The code 3 horn should be used only for fire evacuation signaling and not for
any other purpose.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS
PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS
AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE AUDIBLE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED
dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY
INSERTING A JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT
SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS
Table 1: UL Ratings
Models
| Regulated Voltage (VDC/VRMS)| Voltage Range (VDC/VRMS)| Strobe Candela (cd)
AS-2415C| 24| 16.0-33.0| 15
AS-2430C| 24| 16.0-33.0| 30
AS-2475C| 24| 16.0-33.0| 75
AS-24100C| 24| 16.0-33.0| 100
NOTE: THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE MAXIMUM NUMBER OF STROBES ON A SINGLE NAC CIRCUIT SHALL NOT EXCEED 47.
Table 2: dBA Sound Output
Description| Volume| Reverberant Per UL 464| Anechoic dBA
16VDC| 24VDC| 33VDC| 16VDC| 24VDC| 33VDC
Continuous Horn
| Low| 80| 83| 86| 86| 90| 92
Medium| 85| 88| 91| 91| 95| 98
High| 88| 91| 93| 95| 99| 101
Code 3 Horn
| Low| 75| 79| 82| 86| 90| 92
Medium| 80| 84| 86| 91| 95| 98
High| 84| 87| 90| 95| 99| 101
- Strobe will produce 1 flash per second over the “Regulated Voltage” range.
- Anechoic dBA is measured on-axis in a non-reflective (free field) test room using fast meter response. For peak dBA (measured with peak meter response), add 5dBA to anechoic values shown in Table 2. Reverberant dBA is a minimum UL rating based on sound pressure measurements in a reverberant test room.
- All models are UL Listed for indoor use with a temperature range of +32oF to +120oF (0oC to +49oC) and maximum humidity of 85%RH.
- WARNING: THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS FOR 24V
- MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES.
Table 3: Current Ratings (AMPS) for 24VDC Models with Hi dBA Setting
Rated Average Current
Voltage| AS-2415C| AS-2430C| AS-2475C| AS-24100C
MEAN| RMS| MEAN| RMS| MEAN| RMS| MEAN| RMS
16.0VDC| 0.137| 0.137| 0.187| 0.195| 0.376| 0.376| 0.425| 0.458
24.0VDC| 0.112| 0.115| 0.142| 0.176| 0.261| 0.304| 0.292| 0.375
33.0VDC| 0.107| 0.128| 0.138| 0.155| 0.211| 0.290| 0.258| 0.362
16.0VRMS| —–| 0.182| —–| 0.244| —–| 0.483| —–| 0.544
24.0VRMS| —–| 0.152| —–| 0.196| —–| 0.381| —–| 0.426
33.0VRMS| —–| 0.159| —–| 0.183| —–| 0.339| —–| 0.398
Rated Peak Current *
Voltage| AS-2415C| AS-2430C| AS-2475C| AS-24100C
16.0VDC| 0.160| 0.255| 0.510| 0.670
24.0VDC| 0.180| 0.280| 0.610| 0.710
33.0VDC| 0.195| 0.300| 0.640| 0.750
16.0VRMS| 0.210| 0.320| 0.560| 0.690
24.0VRMS| 0.245| 0.360| 0.640| 0.770
33.0VRMS| 0.500| 0.550| 0.660| 0.825
Rated Inrush Current
Voltage| AS-2415C| AS-2430C| AS-2475C| AS-24100C
16.0VDC| 0.110| 0.110| 0.110| 0.110
24.0VDC| 0.165| 0.165| 0.165| 0.165
33.0VDC| 0.230| 0.230| 0.230| 0.230
16.0VRMS| 0.155| 0.155| 0.155| 0.155
24.0VRMS| 0.235| 0.235| 0.235| 0.235
33.0VRMS| 0.325| 0.325| 0.325| 0.325
Table 3A: Rated Average Current (AMPS) for 24VDC Models with Medium and
Low dBA Setting**
Rated Average Current (Medium)
Voltage| AS-2415C| AS-2430C| AS-2475C| AS-24100C
MEAN| RMS| MEAN| RMS| MEAN| RMS| MEAN| RMS
16.0VDC| 0.122| 0.124| 0.173| 0.175| 0.357| 0.362| 0.409| 0.435
24.0VDC| 0.096| 0.097| 0.126| 0.141| 0.238| 0.295| 0.272| 0.363
33.0VDC| 0.083| 0.084| 0.108| 0.133| 0.188| 0.272| 0.228| 0.307
16.0VRMS| —–| 0.155| —–| 0.225| —–| 0.461| —–| 0.529
24.0VRMS| —–| 0.126| —–| 0.171| —–| 0.352| —–| 0.406
33.0VRMS| —–| 0.120| —–| 0.153| —–| 0.304| —–| 0.372
Rated Average Current (Low)
Voltage| AS-2415C| AS-2430C| AS-2475C| AS-24100C
MEAN| RMS| MEAN| RMS| MEAN| RMS| MEAN| RMS
16.0VDC| 0.118| 0.118| 0.168| 0.168| 0.349| 0.355| 0.402| 0.455
24.0VDC| 0.086| 0.086| 0.119| 0.136| 0.230| 0.277| 0.265| 0.355
33.0VDC| 0.073| 0.073| 0.100| 0.106| 0.173| 0.253| 0.218| 0.301
16.0VRMS| —–| 0.149| —–| 0.220| —–| 0.464| —–| 0.528
24.0VRMS| —–| 0.118| —–| 0.166| —–| 0.342| —–| 0.402
33.0VRMS| —–| 0.109| —–| 0.144| —–| 0.294| —–| 0.366
WARNING: MAKE SURE THAT BOTH THE TOTAL AVERAGE CURRENT, TOTAL PEAK
CURRENT AND TOTAL INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED
TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM, DSM
SYNC MODULES OR PS-12/24-8 POWER SUPPLY DO NOT EXCEED THE POWER SOURCES’ RATED
CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE
APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS
COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN
EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.
When calculating total average, peak or inrush currents: Use Table 3 and 3A to
determine the highest value of “Rated Average Current” for an individual
strobe (across the expected operating voltage range of the strobe) or the
highest value of “Rated Inrush current” or “Rated Peak current” (whichever is
higher) of an individual strobe (across the expected operating voltage range
of the strobe) then multiply the value by the total number of strobes; be sure
to add the currents for any other appliances, including audible signaling
appliances, powered by the same source and include any required safety factor.
if the inrush current or peak current exceeds the power supplies’ inrush
capacity, the output voltage provided by the power supplies may drop below the
listed voltage range of the appliances connected to the supply and the voltage
may not recover in some types of power supplies. For example, an auxiliary
power supply that lacks filtering at its output stage (either via lack of
capacitance and/or lack of battery backup across the output) may exhibit this
characteristic.
LIGHT DISTRIBUTION PER UL 1971
Table 4: Horizontal Plane
Horizontal
Angle (in deg.)
| 15cd| 30cd| 75cd| 100cd
UL Min.| Typ. 15cd| UL Min.| Typ. 30cd| UL Min.| Typ. 75cd| UL Min.| Typ.
100cd
0| 15.0| 21| 30.0| 42| 75.0| 90| 100| 132
5| 13.5| 20| 27.0| 40| 67.5| 92| 90| 129
| | | | | | | |
10| 13.5| 20| 27.0| 40| 67.5| 89| 90| 127
15| 13.5| 20| 27.0| 40| 67.5| 86| 90| 121
20| 13.5| 20| 27.0| 40| 67.5| 86| 90| 116
25| 13.5| 20| 27.0| 40| 67.5| 83| 90| 109
30| 11.3| 19| 22.5| 38| 56.3| 77| 75| 113
35| 11.3| 17| 22.5| 34| 56.3| 70| 75| 100
40| 11.3| 17| 22.5| 34| 56.3| 65| 75| 96
45| 11.3| 15| 22.5| 30| 56.3| 62| 75| 92
50| 8.3| 10| 16.5| 20| 41.3| 42| 55| 86
55| 6.8| 8| 13.5| 16| 33.8| 35| 45| 79
60| 6.0| 8| 12.0| 16| 30.0| 33| 40| 76
65| 5.3| 8| 10.5| 16| 26.3| 31| 35| 59
70| 5.3| 8| 10.5| 16| 26.3| 31| 35| 45
75| 4.5| 8| 9.0| 16| 22.5| 31| 30| 43
80| 4.5| 7| 9.0| 14| 22.5| 30| 30| 42
85| 3.8| 7| 7.5| 14| 18.8| 27| 25| 41
90| 3.8| 6| 7.5| 13| 18.8| 26| 25| 36
Table 5: Vertical Plane
Vertical
Angle (in deg.)
| 15cd| 30cd| 75cd| 100cd
UL Min.| Typ. 15cd| UL Min.| Typ. 30cd| UL Min.| Typ. 75cd| UL Min.| Typ.
100cd
0| 15.0| 21| 30.0| 42| 75.0| 90| 100| 132
5| 13.5| 21| 27.0| 42| 67.5| 88| 90| 129
10| 13.5| 21| 27.0| 42| 67.5| 87| 90| 127
15| 13.5| 20| 27.0| 40| 67.5| 83| 90| 121
20| 13.5| 19| 27.0| 38| 67.5| 79| 90| 116
25| 13.5| 19| 27.0| 38| 67.5| 74| 90| 109
30| 11.3| 18| 22.5| 36| 56.3| 70| 75| 113
35| 11.3| 18| 22.5| 36| 56.3| 68| 75| 100
40| 11.3| 16| 22.5| 32| 56.3| 66| 75| 96
45| 11.3| 14| 22.5| 28| 56.3| 63| 75| 92
50| 8.3| 12| 16.5| 24| 41.3| 59| 55| 86
55| 6.8| 12| 13.5| 24| 33.8| 54| 45| 79
60| 6.0| 9| 12.0| 18| 30.0| 52| 40| 76
65| 5.3| 8| 10.5| 16| 26.3| 40| 35| 59
70| 5.3| 8| 10.5| 16| 26.3| 31| 35| 45
75| 4.5| 8| 9.0| 16| 22.5| 29| 30| 43
80| 4.5| 8| 9.0| 16| 22.5| 29| 30| 42
85| 3.8| 8| 7.5| 16| 18.8| 28| 25| 41
90| 3.8| 8| 7.5| 16| 18.8| 24| 25| 36
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER’S ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SOUND OUTPUT (SPL) SETTINGS
- (Use needle nose pliers to pull and properly set the jumper plugs)
- No jumper plug is needed for continuous horn setting. However, it is recommended that the jumper plug be retained in the unit for future use (if needed) as shown in Figure 3.
NOTE: The AS must be set for code 3 when used with the sync module. Continuous horn operation without sync module.
WIRING INFORMATION
When the sync module is used, the audible tone will be the code 3 sound only. Refer to Sync Module installation instruction sheets SM (P83123), DSM (P83177) or PS-12/24-8 (P83862) for additional information.
- AS Appliances have in-out wiring terminals that accepts two #12 to 18 American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8” inches for connection to screw terminals.
- Break all in-out wire runs on supervised circuit supervision as shown in Figure 5. The polarity as shown in the wiring diagrams is for the operation of the appliances. The polarity is reversed by the FACP during supervision.
MOUNTING OPTIONS
CAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring.
MOUNTING PROCEDURES
Use this mounting procedure to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
- Thread the 4 field wires through the opening of the UMP.
- Mount the UMP to backbox.
- Connect 4 field wires to the AS terminal block (polarity must be observed).
- Bend the 4 field wires up 90o at the connection to the terminal block.
- Carefully push the 4 field wires into the backbox through the opening of the UMP by hand.
- Hook the 2 slots on the inside wall of the AS onto the 2 tabs of the UMP and screw the AS to the UMP using the #6-20 X 1-3/4” screw supplied.
MOUNTING NOTES
CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4″ conduit fittings are used.
- All models can be flush mounted to a standard single-gang backbox (Figure A), 4” backbox (Figure B) or double-gang backbox (Figure C). They can also be surface mounted to a 4” or 100mm backbox (Figure B), a double-gang backbox (Figure C) or a SHBB surface backbox (Figure D).
- All models are equipped with a Universal Mounting Plate (UMP).
- Mounting hardware for each mounting option is supplied. For proper mounting, be sure to use the mounting screws supplied with the unit.
- Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.
- When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the signaling appliance.
- Do not pass additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for the signaling appliance.
CAUTION: If audible strobe appliances are operated within 15 inches of a
person’s ear, they can produce a sound pressure level that exceeds the maximum
120dBA permitted by ADA and OSHA rules. Exposure to such sound levels can
result in damage to a person’s hearing.
WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES
WITHIN A PERSON’S FIELD OF VIEW, UNDER CERTAIN CIRCUMSTANCES, MIGHT INDUCE A
PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS
POSSIBLE HAZARD, WHEELOCK STRONGLY RECOMMENDS THAT THE STROBES INSTALLED
SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS
FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. WHEELOCK ALSO STRONGLY
RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES
COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS,
CODES AND GUIDELINES.
NOTE: NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation
Guidelines in using fewer, higher intensity strobes within the same protected
area.
These appliances can produce a distinctive three pulse Temporal Pattern Fire
Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72,
1999 Edition.
CAUTION: Check the installation instructions of the manufacturers of
other equipment used in the system for any guidelines or restrictions on
wiring and/or locating Notification Appliance Circuits (NAC) and notification
appliances. Some system communication circuits and/or audio circuits, for
example, may require special precautions to assure electrical noise immunity
(e.g. audio crosstalk).
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital appliance, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures: 1) Reorient or relocate
the receiving antenna, 2) Increase the separation between the equipment and
receiver, 3) Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected, and 4) Consult the dealer or an
experienced radio/TV technician for help. The Audible Strobe products and
these instructions are copyrighted by Wheelock and the Audible Strobe products
contain proprietary, confidential and trade secrets of Wheelock. No part of
the Audible Strobe products and these instructions may be photocopied, printed
or reproduced in any form or modified, adapted, changed or enhanced, or
converted to another programming language, or used to create updated, related
or derivative works, without the prior written consent of Wheelock. No part of
the Audible Strobe products shall be decomposed, disassembled or reverse
engineered.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT’S APPLICATION, OPERATION, INSTALLATION AND TESTING IS US ED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
IMPORTANT: READ SEPARATE “GENERAL INFORMATION” SHEET FOR INFORMATION ON THE PLACEMENT, LIMITATIONS, INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING OF NOTIFICATION APPLIANCES.
Limited Warranty
Wheelock products must be used within their published specifications and must
be PROPERLY specified, applied, installed, operated, maintained and
operationally tested in accordance with these instructions at the time of
installation and at least twice a year or more often and in accordance with
local, state and federal codes, regulations and laws. Specification,
application, installation, operation, maintenance and testing must be
performed by qualified personnel for proper operation in accordance with all
of the latest National Fire Protection Association (NFPA), Underwriters’
Laboratories (UL), Underwriters’ Laboratories of Canada (ULC), National
Electrical Code (NEC), Occupational Safety and Health Administration (OSHA),
local, state, county, province, district, federal and other applicable
building and fire standards, guidelines, regulations, laws and codes
including, but not limited to, all appendices and amendments and the
requirements of the local authority having jurisdiction (AHJ). Wheelock
products when properly specified, applied, installed, operated, maintained and
operationally tested as provided above are warranted against mechanical and
electrical defects for a period of three years from date of manufacture (as
determined by date code). Correction of defects by repair or replacement shall
be at Wheelock’s sole discretion and shall constitute fulfillment of all
obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL
IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS
INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES
ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK
MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR
STATUTORY WHETHER AS TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR
ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR
THE USER’S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER’S INTENDED RESULTS.
THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER
SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK’S
CONTROL. SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE
PRODUCTS, WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL
BE UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER
STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE
WILL MEET THE USER’S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE FOR ANY
DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER
PROBLEMS IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE. THE
LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE,
WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED
THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON
EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK
IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF
THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE
WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR
CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE
PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK’S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A
PRODUCT.
Limitation of Liability
WHEELOCK’S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK’S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT APPLY TO ALL PURCHASERS.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>