SICOTEC SLC TWIN RT2 LION Uninterruptible Power Supplies (Ups) User Manual
- June 9, 2024
- SICOTEC
Table of Contents
SICOTEC SLC TWIN RT2 LION Uninterruptible Power Supplies (Ups)
INTRODUCTION
THANK YOU LETTER.
We thank you in advance for the trust placed in us in the pur-chasing of this
product. Read this instruction manual carefully in order to familiarise
yourself with its content, since the more you know and understand the device
the greater your satisfac-tion, level of safety and optimisation of its
functionalities will be.
We remain at your disposal for any additional information or queries that you
may wish to make.
Yours sincerely.
SALICRU
-
The device described here is capable of causing sig-nificant physical injury if improperly handled. For this reason, its installation, maintenance and/or repair must be carried out exclusively by our staff or qualified personnel.
-
Although no effort has been spared to ensure that the in-formation in this user manual is complete and accurate, we accept no liability for any errors or omissions that may exist.
The images included in this document are for illustrative purposes and may not exactly represent the parts of the device shown; therefore they are not contractual. However, any divergence that may arise will be remedied or solved with the correct labelling on the unit. -
Following our policy of constant evolution, we reserve the right to modify the characteristics, operations or actions described in this document without prior notice.
-
Reproduction, copying, assignment to third parties, modification or total or partial translation of this manual or document, in any form or by any means, without previous written permission by us is prohibited, with the company reserving full and exclusive property rights over it.
SAFETY INFORMATION
USING THIS MANUAL.
The documentation of any standard equipment is available to the customer on our website for download (www.salicru.com).
- For devices ‘powered by socket,’ this is the website for obtaining the user manual and ‘Safety Instructions’ EK266*08.
- For devices with ‘permanent connection’ via terminals, a CD- ROM or pen drive containing all necessary information for connection and startup, including ‘Safety Instructions’ EK266*08, may be supplied with it.
Before carrying out any action on the device relating to its installation or
startup, change of location, configuration or handling of any kind, carefully
read the safety instructions.
The purpose of the user manual is to provide information regarding safety and
explanations of the procedures for installation and operation of the
equipment. Read them carefully and follow the steps indicated in the order
established.
Compliance with the ‘Safety Instructions’ is mandatory and the user is legally
responsible for compliance and enforcement.
The device is delivered properly labelled for correct identification of each of its parts, which, together with the instructions described in this user manual, allows installation and start-up operations to be performed in a simple and organised manner without any doubts whatsoever.
Finally, once the equipment is installed and operating, it is recommended to
save the documentation downloaded from the website, CD-ROM or pen drive in a
safe and easy-to-access place, for any future queries or doubts that may
arise.
The following terms are used interchangeably in the document to refer to:
-
SLC TWIN RT2 LION, TWIN RT2, TWIN, RT2, device, unit or UPS’ – Uninterruptible power supply.
Depending on the context of the phrase, it can refer either to the actual UPS itself or to the UPS and the batteries, regardless of whether or not it is all assembled in the same metal enclosure. -
Batteries’ or ‘accumulators’ – Bank or set of elements that stores the flow of electrons by electrochemical means.
-
‘T.S.S.’ – Technical Service and Support.
-
‘Customer,’ ‘installer,’ ‘operator’ or ‘user’ – These are used interchangeably and by extension to refer to the in-staller and/or operator who will carry out the corresponding actions, and the same person may be responsible for carrying out the respective actions when acting on behalf, or in representation, of the above.
Conventions and symbols used.
Some symbols may be used and appear on the device, batteries and/or in the
context of the user manual.
For more information, see Section 1.1.1 of the ‘Safety Instructions’ document
EK266*08.
QUALITY ASSURANCE AND STANDARDS
STATEMENT BY THE MANAGEMENT.
Our goal is customer satisfaction, therefore this Management has decided to
establish a Quality and Environment Policy, through the implementation of a
Quality and Environmental Management System that will enable us to comply with
the requirements demanded in the ISO 9001 and ISO 14001 and also by our
Customers and Stakeholders.
Likewise, the management of the company is committed to the development and
improvement of the Quality and Environ-mental Management System, through:
- Communication to the entire company of the importance of satisfying both the customer’s requirements as well as legal and regulatory requirements.
- The dissemination of the Quality and Environment Policy and the setting of the Quality and Environment objectives.
- Conducting reviews by the Management.
- Providing the necessary resources.
STANDARDS.
The SLC TWIN RT2 LION is designed, manufactured and sold in accordance with Quality Management Standard EN ISO 9001. The marking indicates conformity with EC Directives through the application of the following standards:
- 2014/35/EU. – Low-voltage safety.
- 2014/30/EU. – Electromagnetic Compatibility (EMC).
- 2011/65/EU. – Restriction of the use of hazardous sub-stances in electrical and electronic equipment (RoHS).
In accordance with the specifications of the harmonized standards. Reference standards:
- EN-IEC 62040-1. Uninterruptible power supplies (UPS). Part 1-1: General and safety requirements for UPS used in user access areas.
- EN-IEC 62040-2. Uninterruptible power supplies (UPS). Part 2: EMC requirements.
The manufacturer is not liable in the event of modifica-tion or intervention on the device by the user.
WARNING:
SLC TWIN RT2 LION from 1 to 3 kVA. This is a category C2 UPS. In a residential
environment, this product may cause radio interference, in which case the user
must take additional measures.
It is not appropriate to use this device in basic life sup-port applications
(BLS), where a failure of the former can render vital equipment out of service
or signifi-cantly affect its safety or effectiveness. It is also not
recommended in medical applications, commercial transport, nuclear
installations, or other applications or loads, where a failure of the product
can lead to per-sonal or material damages.
The EC declaration of conformity of the product is avail-able to the customer
upon express request to our offices.
First and second environment.
The environment examples that follow cover most UPS instal-lations.
First environment.
Environment including residential, commercial and light in-dustry
installations, directly connected, without intermediate transformers, to a low
voltage public power grid.
Second environment.
An environment that includes all commercial, light industrial and industrial
establishments that are not directly connected to a low voltage power grid
supplying buildings used for resi-dential purposes.
ENVIRONMENT.
This product has been designed to respect the environment and has been
manufactured in accordance with the ISO 14001 standard.
Recycling of the device at the end of its useful life:
We undertake to use the services of authorised and regulatory-compliant
companies to process all of the products when they are recovered at the end of
their useful life (contact your dis-tributor).
Packaging:
For the recycling of the packaging there must be compliance with the legal
requirements in force, in accordance with the specific regulations of the
country where the device is installed.
Batteries:
Batteries pose a serious hazard to health and the environment. They must be
disposed of in accordance with the laws in force.
PRESENTATION
VIEWS.
Views of the device.
Fig. 1 and Fig. 2 show illustrations of the devices according to box format
and in relation to the model’s power rating. How-ever, because the product is
constantly evolving, discrepancies or slight contradictions may arise. If in
any doubt, the labelling on the device itself will always prevail.
The nameplate of the device shows all of the values relating to its main
properties and characteristics. Act accordingly for its installation.
Fig. 2. Rear view of the the SLC TWIN RT2 LION models.
DEFINITION OF THE PRODUCT
Nomenclature.
SLC-3000-TWIN RT2 LION WCO EE29503
OPERATING PRINCIPLE
This manual describes the installation and operation of the SLC TWIN RT2 LION
series of Uninterruptible Power Supplies (UPS). SLC TWIN RT2 LION series UPSs
ensure optimum protection of any critical load, maintaining the supply voltage
of the loads between the specified parameters without interruption during
failure, deterioration or fluctuation of mains power.
Thanks to their PWM (pulse width modulation) and double-conversion technology,
SLC TWIN RT2 LION series UPSs are compact, cool, silent and high performance.
The double converter principle eliminates all mains power dis-turbances. A
rectifier converts the AC current of the mains into DC current, thereby
maintaining optimum battery charge level and powering the inverter, which, in
turn, generates a suitable AC sine-wave voltage for continuously powering the
loads. In the event that the UPS’s input power supply fails, the Li-ion
batteries will supply clean power to the inverter.
The design and construction of the SLC TWIN RT2 LION se-ries UPS has been
carried out in accordance with international standards.
Consequently, this series has been designed to maximise the availability of
critical loads and to ensure that your business is protected against any
variations in voltage, frequency, electrical noise, cuts or dropouts that may
occur in the power supply. This is the primary goal of SLC TWIN RT2 LION
series UPSs.
This manual applies to the standardised models shown in Tab. 1.
Characteristics and main advantages of Li-ion batteries. Like lead-acid
batteries, lithium-ion (Li-ion) batteries consist of four components: anode,
cathode, electrolyte and separator.
Two compounds act as electrodes and are immersed in the electrolyte. The same
material, lithium carbonate, is used for the anode in all Li-ion batteries.
The material used for the cathode can vary. Li-ion batteries use lithium oxide
(Li2O).
Main advantages:
-
Increased energy density: The accumulator’s energy density determines the battery’s capacity. The energy density of Li-ion batteries is approximately three times higher than that of lead-acid; thus, when comparing Li-ion and lead-acid batteries of similar size, the capacity of the former would be three times higher.
-
Increased energy efficiency and higher voltage: Lithium is a highly electronegative chemical element. Its increased oxidation capacity means the voltage of Li-ion batteries is higher. While a lead-acid battery cell produces 2 V, a Li-ion cell produces in excess of 3.6 V.
Overall performance levels, meanwhile, reach 98%. -
Improved energy profile: The energy profile measures the charge status in relation to charge time and battery use. Li-ion batteries boast a superior energy profile.
Because they operate at a higher voltage, a less intense current is needed to produce the same amount of energy, meaning the battery needs less time to charge. -
Depth of discharge: While the useful life of lead-acid accumulators can be maximized if they are kept at just 20%discharge, and it is not recommended to let them discharge by more than 50%, Li-ion batteries do not suffer from this problem and can be discharged up to 100%.
-
Longer useful life: Following on from the previous point, it should be noted that the useful life of a deep-cycle lead-acid Monoblock is 600-700 charge-discharge cycles. In contrast, the useful life of a Li-ion battery is around 10 times longer, i.e. 6,000+ cycles.
-
Maintenance-free: Li-ion batteries are sealed and do not require any form of maintenance.
UPS OPERATING MODES.
-
Normal mode.
Device running supplying output voltage from the inverter. Mains power present with correct input voltage and fre-quency. -
Battery mode.
Device running with mains voltage or frequency out of range or without AC input power, either due to mains failure or absence of cable connection, supplying output voltage from the batteries. -
Bypass mode.
Device running or not, supplying output voltage directly from the AC mains.
With the inverter running, this operating mode may be due to an overload, blockage or inverter fault.
The actions for each incident will be as follows: Reduce the load connected to the output, unblock the device by reset-ting it – stop it and start it up again – and, if the blockage or fault remains, contact our T.S.S.
With the inverter shut down, the output supplies mains power directly through the static bypass of the device pro-vided that it has AC input power. -
Frequency converter (CF) mode.
Operating mode of the UPS as a frequency converter. In this mode, the static bypass is disabled by the condition of dis-parate input and output frequencies.
Even if the LCD on the backlit control panel shows mes-sages, it does not mean that the inverter is operational. It is switched on by pressing the ‘ON’ button on the control panel, see Chapter 6.
Notable features.
- True on-line with double-conversion technology and output frequency separate from the mains.
- Output power factor 0.9. Pure sine-wave waveform, suit-able for all types of load.
- Input power factor > 0.99 and high overall performance (be-tween 89% and 91%). Greater energy savings and lower user installation costs (wiring), as well as low distortion of the input current, which reduces pollution in the power supply network.
- Great adaptability to the worst conditions of the mains. Wide input voltage, frequency and waveform ranges, thus avoiding excessive dependence on limited battery power.
- Battery recharge time < 3h.
- Selectable high-efficiency mode (ECO MODE) > 95%. En-ergy savings, economically beneficial to the user.
- Possibility of starting the device without mains power supply or discharged battery. Pay attention to this last as-pect because the more the batteries are discharged, the more the backup will be reduced.
- Intelligent battery management technology is very useful for extending the life of accumulators and optimising re-charge times.
- Standard communication options via the RS-232 serial port or USB port.
- Remote emergency power off control (EPO).
- Control panel with LCD display.
- Availability of optional connectability cards to improve communication capabilities.
- The device can be configured as a tower or rack using the accessories supplied. The control panel can be rotated to adapt to either format.
Model | Type | Input/output type |
---|---|---|
SLC-1000-TWIN RT2 LION |
Standard
|
Single-phase / Single-phase
SLC-1500-TWIN RT2 LION
SLC-2000-TWIN RT2 LION
SLC-3000-TWIN RT2 LION
Tab. 1. Standardised models.
OPTIONAL EXTRAS.
Depending on the configuration chosen, the device can include any of the following options:
Isolation transformer.
The isolation transformer provides galvanic isolation in order to completely
isolate the output from the input and/or change neutral point treatment.
The placement of an electrostatic screen between the primary and secondary
windings of the transformer provides a high level of electrical noise
attenuation.
The isolation transformer can be physically placed at the input or output of
the UPS depending on the technical conditions of the whole system (device
supply voltage and/or load voltage, characteristics or their type, etc.).
It will always be supplied as a peripheral component external to the device
itself in a separate enclosure.
Exterior manual maintenance bypass.
The purpose of this option is to electrically isolate the device from the
mains and the critical loads without cutting the power to the latter. In this
way, maintenance or repair operations on the device can be carried out without
interruptions to the power supply of the protected system, while preventing
unnecessary hazards for technical personnel.
Communication card.
The UPS features a slot at the rear for inserting one of the fol-lowing
communication cards.
Integration into computer networks using an SNMP adapter.
Large computer systems based on LANs and WANs that integrate servers in
different operating systems must provide the system manager with ease of
control and administration. This facility is obtained through an SNMP adapter,
which is universally sup-ported by the main software and hardware
manufacturers.
Connection of the UPS to the SNMP is internal while that of the SNMP to the
computer network is made through an RJ-45 10 base connector.
RS-485 modbus.
Large computer systems based on LANs and WANs often re-quire that
communication with any element that is integrated into the computer network be
made through a standard indus-trial protocol.
One of the most used standard industrial protocols on the market is the MODBUS
protocol.
Relay interface.
The UPS has, as an option, a relay interface card that provides digital
signals in the form of potential-free contacts, with a maximum applicable
voltage and current of 240 V AC or 30 V DC and 1 A.
This communication port enables dialogue between the device and other machines
or devices through the relays supplied in the terminal block arranged on the
same card, with a single common terminal for all of them.
From the factory, all contacts are normally open and can be changed one by
one, as indicated in the information supplied with the optional extra.
The most common use of these types of ports is to provide the necessary
information to the file-closing software.
For more information, contact our T.S.S. or our nearest dis-tributor.
Extendable guide kits for mounting in a rack cabinet.
An extendable and unique guide kit is available for all device models, valid
for any kind of rack-type cabinet.
These guides enable any TWIN RT2 LION unit to be installed like a rack in its
respective cabinet.
INSTALLATION
Read and respect the Safety Information, described in Chapter 2 of this
document. Failure to obey some of the instructions described in this manual
can result in a serious or very serious accident to persons in direct contact
or in the vi-cinity, as well as failures in the device and/or loads connected
to it.
In addition to the device’s own user manual, a number of other documents are
supplied along with the Quick Start guide. Con-sult them and strictly follow
the indicated procedure.
RECEPTION OF THE DEVICE.
Pay attention to section 1.2.1. of the safety instructions -EK266*08- in all
matters relating to the handling, movement and siting of the unit.
Use the most suitable means to move the UPS while it is packed, with a pallet
jack or forklift.
Any handling of the device must be carried out in accordance with the weights
shown in the technical specifications ac-cording to the model, indicated in
Chapter 9. Annexes.
Reception, unpacking and contents.
-
Reception. Check that:
-
The data on the label affixed to the packaging corre-sponds to that specified on the order. Once the UPS is unpacked, check the previous data with those of the device nameplate.
If there are discrepancies, report the issue as soon as possible, citing the device’s manufacturing number and delivery note references. -
It has not suffered any mishaps during transportation (packaging in perfect condition).
If this is not the case, contact your distributor.
-
-
Unpacking.
- To check the contents, it will be necessary to remove the packaging. Complete the unpacking according to the procedure of section 5.1.3.
-
Contents.
- 1 UPS.
- Quick guide on paper.
- Information for warranty registration.
- 1 USB cable.
- 3 cables with IEC connectors for loads.
- 1 cable for the device’s AC power supply.
- 2 metal pieces for use as handles and screws for in-stalling the unit in a rack cabinet.
- 4 plastic pieces for use as a base and screws to facilitate the arrangement of the UPS as a tower (vertical position).
Once the reception is completed, it is advisable to re-pack the UPS until it
is put into service in order to protect it against me-chanical shock, dust,
dirt, etc. The device’s packaging consists of a cardboard box, expanded
polystyrene corners and polyethylene cover and strapping, all of which can be
recycled. When the packaging requires dis-posal, it must be carried out in
accordance with current laws.
We recommend keeping the packaging for at least 1 year.
Storage.
The device should be stored in a dry, ventilated location protected from rain,
dust, water splashes and chemical agents. It is advisable to keep each device
and battery unit in its original packaging, as it has been specifically
designed to ensure max-imum protection during transportation and storage.
For devices that contain Li-ion batteries, the charging frequency and charge
duration indicated in the table below (which are based on the device’s storage
temperature) must be observed, otherwise the warranty may be invalidated.
Storage temperature| Charging frequency| Charge
duration
---|---|---
35ºC ~ 45ºC| Every month| 1 h @ 5ºC ~ 35ºC
25ºC ~ 35ºC| Every 1-3 months| 1 h @ 5ºC ~ 25ºC
-10ºC ~ 25ºC| Every 3-12 months| 1 h @ 5ºC ~ 25ºC
Tab. 2. Frequency and duration of Li-ion battery charging based on storage
temperature.
Then shut down the device, disconnect it and store the UPS and batteries in
their original packaging, noting the new date for recharging the batteries on
a document as a record or even on the packaging itself.
Do not store the devices where the ambient temperature ex-ceeds 50°C or drops
below -15°C, as this may cause degradation of the electrical characteristics
of the batteries.
Unpacking.
The packaging of the device consists of a cardboard box, ex-panded polystyrene
(EPS) or polyethylene foam (EPE) corners, polyethylene cover and strapping,
all of which are recyclable materials; consequently, if it requires disposal,
it must be carried out in accordance with current laws. We recommend keeping
the packaging in case it needs to be used in the future.
Proceed as follows:
- Cut the straps around the cardboard box.
- Remove the accessories (cables, brackets, etc.)
- Remove the device from the packaging, using another person to help or suitable mechanical means where necessary, depending on the weight of the model.
- Remove the protective corners from the device and the plastic bag.
- Do not leave the plastic bag within the reach of children to avoid danger of suffocation.
- Inspect the device before proceeding and, in the event of finding damage, contact the supplier or, failing that, our firm.
Transport to the site.
It is recommended to transport the UPS by means of a pallet jack or the most
appropriate method considering the distance between the two points.
If the distance is considerable, it is recommended to transport the device in
its packaging to the installation site and then un-pack it.
Siting, immobilising and considerations.
All TWIN RT2 LION UPSs are designed to be mounted as a tower model (i.e.
placed vertically) or rack model (i.e. placed horizontally) for installation
in 19” cabinets.
Follow the instructions indicated in the sections relating to ei-ther of the
two possibilities, according to the particular configu-ration of your device.
Fig. 3 to Fig. 5 provide illustrations of the device’s design.
These illustrations provide help and guidance on the steps to follow, but the
instructions are not intended to refer to a single model, although, in
practice, the actions to be carried out are always the same for all of them.
For all instructions regarding connections, refer to section 5.2.
Rotation of the control panel with LCD.
To facilitate the reading of messages on the display when the device is
installed vertically, it is possible to rotate the control panel clockwise by
90º (see Fig. 3).
Likewise, reverse the rotation of the control panel if a device arranged as a
tower needs to be installed as a rack.
In this case, the rotation of the control panel will be anti-clock-wise.
Proceed as follows:
- Insert fingertips into the recesses of the plastic trim around the display and pull outwards.
- Rotate the control panel with LCD 90º to the right with re-spect to its initial position and insert it back into the front.
Vertical tower-type mounting.
- Rotate the control panel according to section 5.1.5.1.
- Take the 4 plastic pieces supplied with the equipment, two by two, fit them together and secure them with the sup-plied screws to obtain two pedestals or bases.
- Place the UPS upright between the two bases at a distance of 70 mm from each end (see Fig. 4).
Mounting as a rack in a 19” cabinet.
To mount a device in a 19” rack cabinet, proceed as follows (see Fig. 5):
- Using the supplied screws, fix the two adapter angles for use as handles on each side of the UPS, respecting your hand.
- To install the device in a rack cabinet, it is necessary to have internal lateral guides for use as supports. Alterna-tively, and upon request, we can supply universal slides for use as guides, for installation by the user.
- Mount the guides at the required height, ensuring correct tightening of the fixing screws and appropriate fitting in the machining, according to each case.
- Place the device onto the guides and insert it all the way to the back.
- Depending on the device model and weight, and/or whether it is installed in the upper or lower part of the cabinet, it is recommended that two people carry out the installation operations.
- Fix the UPS to the cabinet frame using the screws supplied with the handles.
Preliminary considerations before connection.
Thermal control of these devices is carried out with the pas-sage of forced
air from the front to the rear.
The front surface and about 15 cm on the rear side should be left free of
obstructions to facilitate the free circulation of air for ventilation.
Follow and observe the instructions provided in this section.
Protection or external manual bypass board:
- The system will have at least one short-circuit protection on the UPS’s power supply line.
- It is advisable to have an external manual bypass board fitted with input, output and manual bypass protections.
Upon request, we can supply an external manual bypass board.
You can also choose to manufacture one, taking into account the version and
configuration of the available device or system and the attached documentation
regarding ‘Recommended in-stallation’.
Only rated currents are printed on the nameplate of the device as indicated by
the EN-IEC 62040-1 safety standard. For the cal-culation of the input current,
the power factor and the device’s own performance have been considered.
Overload conditions are considered a non-permanent and ex-ceptional working
mode, and will not be taken into account in the application of the
protections. Do not connect appliances or devices which may overload the UPS
to the terminals and/or outlets, such as motors.
If peripheral input or output elements, such as transformers or
autotransformers, are added to the UPS, the currents indi-cated on the
nameplates of these elements must be taken into consideration when determining
appropriate cross sections, in compliance with local and/or national low
voltage electrotech-nical regulations.
When a galvanic isolation transformer is added to a UPS as standard, as an
optional extra or independently, either on the input line, at the output or
both, it must be fitted with protec-tion against indirect contact
(differential circuit breaker) at the output of each transformer, since, due
to its own insulation properties, it will prevent the tripping of the
protections placed on the primary of the isolation transformer in case of
electric shock on the secondary (output of the isolation transformer).
We remind you that all the isolation transformers installed or factory
supplied, have the output neutral earthed through a jumper between the neutral
terminal and earth. If the iso-lated output neutral is required, this jumper
must be removed, taking the precautions indicated in the respective local
and/or national low voltage regulations.
This device is suitable for installation in networks with TT, TN-S, TN-C or IT power distribution systems, taking into account at the time of installation the particularities of the system used and the national electrical regulations of the destination country. The SLC TWIN RT2 LION features terminals for the installation of an external emergency power off button (EPO) or, failing that, a single device must be installed to cut the power supply to the loads in any operating mode.
Preliminary considerations before connection, regarding the batteries and
their protections.
The batteries for the SLC TWIN RT2 LION models are in the same box as the
devices.
VERY IMPORTANT: For safety reasons, the batteries are disconnected. Before installing the UPS, follow the steps below to reconnect them:
The batteries are always protected by internal fuses that are not accessible to the user.
If the mains power of the device or parallel system is cut for longer than a simple intervention and it is expected that it will be out of service for a prolonged period time, the system must be shut down completely.
Connection elements.
All of the device’s electrical connections are made from the back of each
unit:
- Input and output connection.
- Input by means of a cable with plug, connectable to the UPS through an IEC connector.
- Outputs through IEC connectors.
- Communication connectors available:
- DB9 for RS-232.
- USB to operate the UPS as a PC peripheral.
- For connection to external EPO button.
- Slot for the integration of one of the optional electronic communication units. Remove the fixing screws and plastic cover to enable it to be inserted.
CONNECTIONS
Connection of the input.
- Take the power cable with plug and IEC connector on the end and insert the latter into the input connector of the UPS.
- Plug the power cable into an earthed AC power socket.
Connection to the IEC output connectors.
The SLC TWIN RT2 LION models have a different number of female IEC output
connectors, depending on the power of the model:
- models up to 2 kVA: Two groups of four IEC 10A connectors identified as ‘OUTPUT’ and ‘OUTPUT PROGRAMMABLE (P1)’, which can be configured via the control panel and/or ViewPower.
- 3 kVA models: same connectors as models up to 2 kVA and an additional 16A IEC connector.
Do not connect loads that in their entirety exceed the specifications of the
device, as this would cause incon-venient cuts in the power supply of the
loads connected to the output.
If, in addition to the more sensitive ‘critical loads,’ it is neces-sary to
connect high-consumption inductive loads, such as for laser printers or CRT
monitors, the starting up of these periph-erals will need to be taken into
account to prevent the device from crashing.
We do not recommend connecting loads of this type due to the amount of power
they absorb from the UPS.
Connecting the loads.
Connect the loads to the 10 A IEC connectors. It is important to consider the
two groups of IEC connectors available, those for ‘critical loads’ and those
for ‘non-critical loads’.
By definition, ‘critical loads’ are considered to be those that can cause
economic damage if they stop functioning or function incorrectly.
The IEC connectors indicated in Fig. 2 as ‘non-critical loads’ can be
programmed as such through the control panel. In this case, the backup of the
batteries for the loads connected to the IEC connectors indicated in Fig. 2 as
‘critical loads’ will be reserved. Take into account that they are set by
default as ‘critical loads’.
The 3 kVA models also have a 16A IEC connector that enables the connection of
a load of the total power of the device.
Terminals for EPO (emergency power off).
The UPSs have two terminals for the installation of an external emergency
power off (EPO) output button.
The device is dispatched from the factory with its EPO circuit set to closed
(NC) by default. In other words, the UPS will cut the output power supply,
emergency power off, when the cir-cuit is opened:
- Either by removing the female connector from the socket where it is inserted. This connector has a cable connected as a jumper that closes the circuit (see Fig. 6- A),
- or by pressing the button external to the device belonging to the user installed between the terminals of the connector (see Fig. 6- B). The connection on the button must be in the normally closed contact (NC), so it will open the circuit when activated.
The reverse functionality can be selected via the communica-tions software and
control panel (settings menu 15).
Except for specific cases, we advise against this type of con-nection in view
of the purpose of the EPO button, since it will not act upon an emergency
request if either of the two cables that run from the button to the UPS is
accidentally cut.
By contrast, this anomaly would immediately be detected in a closed EPO
circuit, with the inconvenience of an unexpected cut in the powering of the
loads, but a guarantee of effective emergency functionality.
To recover the normal operating state of the UPS, it is necessary to insert
the connector with the jumper in its receptacle or deactivate the EPO button.
The device will be operational.
Fig. 6. Connector for external EPO.
Communication port.
The COM communications line is a very low voltage safety circuit. To preserve
the quality, it must be in-stalled separately from other lines carrying
dangerous voltages (power distribution line).
The RS-232 and USB interfaces are useful for the monitoring software and
updating the firmware.
It is not possible to use both the RS-232 and USB ports at the same time.
In connector DB9, the signals of the RS-232 are supplied.
The RS-232 port consists of the transmission of serial data in such a way that
a large amount of information can be sent through a communication cable with
only 3 wires.
The USB port is compatible with the USB 1.1 protocol for communication
software.Smart slot for the
integration of an electronic communication unit.
Optional electronic communication units include:
- Relay interface to terminals, not programmable.
- SNMP adapter.
- RS-485 modbus adapter.
The corresponding documentation is supplied with each option. Read it before
starting installation.
Installation.
- Remove the protective cover from the device’s slot.
- Take the corresponding electronic unit and insert it into the reserved slot. Make sure that it is properly connected, for which it is necessary to overcome the resistance caused in the connector located in the slot.
- Make the necessary connections in the terminal block or connectors available according to each case.
- Fit the new protective cover supplied with the relay inter-face card and secure it with the screws from the old cover.
- For more information, contact our T.S.S. or our nearest dis-tributor.
Protection against voltage spikes for the modem / ADSL / fax, etc., line. .
The COM communications line is a very low voltage safety circuit. To preserve
the quality, it must be in-stalled separately from other lines carrying
dangerous voltages (power distribution line).
- Connect the main line for the modem / ADSL / fax, etc., to the RJ45 connector of the device, identified as ‘Input.’
- Connect the modem / ADSL / fax, etc., to the RJ45 connector of the device, identified as ‘Output.’
Download of free ViewPower software.
ViewPower is a UPS monitoring software which provides a user-friendly
interface for monitoring and control. It features an auto shutdown function
for systems consisting of several PCs in case of power failure. The software
enables users to monitor and control any UPS in the same LAN through an RS-232
or USB communications port, regardless of how far away they are from each
other.
Installation procedure:
- Go to the web page: http://support.salicru.com
- Select the required operating system and follow the instructions described on the web page to download the software.
Considerations before startup with connected loads.
We recommend charging Li-ion batteries for at least five hours before using
the UPS for the first time.
For this, it will be necessary to supply voltage to the device. The battery
charger will work automatically.
Although the device can operate correctly without charging the batteries for
the specified 5 hours, the risk of a prolonged power cut during the first
hours of operation and the UPS’s available backup time should be assessed.
Do not start up the device and loads completely until indicated in Chapter 6.
When it is done, however, it should be carried out gradually to avoid possible
difficulties, if not at the first startup.
If, in addition to the more sensitive loads, it is necessary to connect high-
consumption inductive loads, such as for laser printers or CRT monitors, the
starting up of these peripherals will need to be taken into account to prevent
the device from crashing.
For this type of load considered NON-PRIORITY, a group of programmable
terminals is available depending on the model. De-pending on the programming
of these, the power supply may or may not be affected in the event of mains
failure.
OPERATION
START-UP.
Checks before start-up.
- Make sure that all of the connections have been made cor-rectly, following the instructions on the labelling of the de-vice and in Chapter 5.
- Check to make sure the UPS switch is in the ‘Off’ position.
- Make sure that all loads are ‘Off’.
Shut down the connected loads before starting the UPS and start the loads, one by one, only when the UPS is running. Before shutting down the UPS, check that all of the loads are ‘Off’.
- It is very important to proceed in the established order.
- For views of the UPS, see Fig. 1 and Fig. 2.
UPS STARTUP AND SHUTDOWN.
UPS startup with mains voltage.
- Check that the power connection is correct.
- Supply voltage to the device (set the input protection of the distribution board or manual bypass to ‘On’). If the board has an output switch, set it to ‘On’).
The IEC output connectors will have voltage through the device’s internal
static bypass block.
The fan or fans, depending on the model, will start to func-tion.
Then the main start screen will be displayed after a test of the device.
- Press the “ON” button for more than 2 seconds, the audible alarm will sound for 1 second and the UPS will start up.
- The UPS is set to ‘Normal mode’ after a few seconds. If the mains voltage is incorrect, the UPS will switch to ‘Battery mode’, without interrupting the power supply at the output terminals.
- Start the load or loads, making sure that the rated power of the device is not exceeded.
UPS startup without mains voltage.
-
If it has a distribution board, set the input and output pro-tections to ‘On’.
-
Press the “ON” button for more than 2 seconds, the audible alarm will sound for 1 second and the UPS will start up. The fan or fans, depending on the model, will start to func-tion.
Then the main start screen will be displayed after a test of the device. -
The UPS is set to ‘Battery mode’ after a few seconds. Depending on the level of charge of the batteries, the re-sidual backup available may be very limited. Consider the risk involved in operating without mains and discharged batteries.
If the mains voltage returns, the UPS will transfer to ‘Normal mode’ without interrupting the power supply at the output terminals. -
Start the load or loads, making sure that the rated power of the device is not exceeded.
UPS shutdown with mains voltage.
-
Shut down the load or loads.
-
Press the “OFF” button for more than 2 seconds to shut down the inverter. The audible alarm will sound for 1 second. The device will be set to ‘Bypass mode’.
The output terminals will have voltage through the device’s internal static bypass block. -
To cut the UPS’s output voltage:
-
Remove the input plug from the power socket,
-
or simply turn the input and output protectors on the UPS’s distribution board to the ‘Off’ position (this ap-plies to any model).
A few seconds later, the LCD screen turns off and the entire device will be out of service.
UPS shutdown without mains voltage.
-
Shut down the load or loads.
-
Press the ‘OFF’ button for more than 2 seconds to shut down the inverter. The audible alarm will sound for 1 second. The device will leave the output terminals without voltage.
A few seconds later, the LCD screen turns off and the entire device will be out of service. -
To leave the assembly completely isolated, set the input and output switches of the board to ‘Off’.
CONTROL PANEL WITH LCD
GENERAL INFORMATION FOR THE SERIES.
Information represented by the display.
Input information
Common abbreviations shown on the display.
Code | On display | Meaning |
---|---|---|
ENA | E A | Enabled. |
DIS | d1S | Disabled. |
ON | ON | Start-up. |
OFF | OFF | Shutdown. |
EPO | EP | Emergency power off. |
ESC | ESC | Escape. |
AO | AO | EPO normally open. |
AC | AC | EPO normally closed. |
EAT | EAt | Estimated backup time. |
RAT | tAt | Current time in backup mode. |
Ok | OK | Ok. |
SD | Sd | Shutdown. |
BL | bL | Battery low. |
OL | OL | Overload. |
OI | OI | Input overcurrent |
NC | NC | Battery not connected |
OC | OC | Battery overcharge |
SF | SF | Connection error. Rotate the connection of the input, phase and |
neutral cables.
TP| TP| Overtemperature.
CH| CH| Charger
BF| bF| Battery failure, low voltage.
BV| bV| Bypass voltage out of range.
FU| FU| Bypass frequency out of range.
BR| bR| Replace batteries.
EE| EE| Internal EEPROM error.
CONTROL PANEL
Composition of the control panel with LCD display.
- The control panel consists of:
- Three buttons with the functions described in Tab. 6.
- An LCD with backlighting.
Button | Description |
---|
__
__
__ ON/MUTE
|
-
Starting up the UPS.
Press the button for at least 2 seconds. -
Muting the alarm.
Press the button for at least 3 seconds to mute or unmute the audible alarm. -
Button to navigate upwards.
When this button is pressed in UPS settings mode, it will move upwards through the menu structure in relation to the point where it is located, accessing the previous variable with each press. -
Activating the battery test.
Press this button for 3 seconds while in normal or frequency converter (CF) mode. At the end of the test, it returns to the respective mode.
SELECT __|
- LCD readings and measurements.
Press this key to view readings for: input voltage, input frequency, input current, battery voltage, battery current, battery capacity, ambient temperature, output voltage, output frequency, output current and % of output load.
- Settings or configuration mode.
With the UPS’s inverter stopped (Bypass mode), press this key for at least 3 seconds to access this mode.
- Button to navigate downwards.
When this button is pressed in UPS settings mode, it will move downwards through the menu structure in relation to the point where it is located, accessing the following variable with each press.
OFF/ENTER
__
|
-
UPS shutdown.
Press this button for at least 2 seconds. The UPS will transfer to Standby or Bypass mode, depending on whether bypass is enabled or disabled. -
Confirmation of selection.
Press this button to confirm selection in the device’s settings mode.
__
ON/MUTE
+ SELECT
__
|
-
Transfer to Bypass mode
Pressing both keys for 3 seconds will transfer the UPS to Bypass mode, provided the input voltage is within the acceptable margins. To return to Inverter mode from this forced Bypass mode, press both keys again. -
Exiting Settings mode
From the Settings menu, press both keys in order to exit Settings mode and return to the main screen.
Tab. 6. Functionality of the control panel buttons.
Audible alarms.
Description
|
Alarm modulation or tone
| Possibility of muting
---|---|---
Bypass mode| Beep every 10 seconds.| ****
Yes
---|---|---
Battery mode| Beep every 5 seconds.
Fault| Continuous.| No
Overload| Beep every second.| Yes
---|---|---
End of backup| Beep every 1 seconds.| No
All| Continuous.| No
---|---|---
Tab. 7. Audible alarms.
Fig. 11. Arrangement of the parameters on the LCD.
-
Parameter 1:
Code of the settings menu. For more information consult Tab. 8. -
Parameters 2 and 3 are the configuration or value options for each settings menu.
Select with buttons ‘ ’ or ‘ ’ to modify the menus or parameters.
All of the parameter settings are saved when the UPS is completely shut down and provided that it
Settings.
Tab. 8 shows a summary of the adjustable codes for parameter 1, while Fig. 12
shows the structure of the menu tree with the oper-ating mode for the
settings.
Code
|
Description
---|---
01| Output voltage setting.
02| Activation/deactivation of frequency converter mode.
03| Output frequency setting.
04| Enable/disable ECO mode.
06| Enable/disable bypass (UPS ‘Off’).
09| Enable/disable programmable outputs.
10| Backup limitation configuration for programmable outputs.
11| Backup limitation configuration.
15| EPO logical configuration.
17| Viewable backup time configuration.
Tab. 8. Parameter 1 codes list.
- The values indicated with(*) are factory default settings.
- The settings can only be made in ‘byPA’ or ‘STby’ mode.
- To carry out any modification of the configuration, follow the indicated sequence with the inverter necessarily Off.
- To exit the main menu from any position, press buttons together.
SLC TWIN RT2 LION UNINTERRUPTIBLE POWER SUPPLIES (UPS)
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>