PURO LIGHTING Helo F1 Air Handling Units With UV Disinfection User Manual
- June 9, 2024
- PURO LIGHTING
Table of Contents
Helo F1 Air Handling Units With UV Disinfection
User Manual
Helo F1 Air Handling Units With UV Disinfection
UV DISINFECTION FROM ABOVE
The Helo F1 disinfects your space, delivering disinfection from above. The
unit can be ordered for installation in a drop-in grid ceiling, recessed in a
hard lid ceiling, surface or wall mounted, or used as a portable, table top
unit. It emits broad spectrum UV light to eliminate up to 99.9% of the
bacteria, viruses, and fungi in a space1 . In rooms that have been cleaned of
mold, the unit will help control return growth if used routinely2 .
The unit can be ordered for scheduled commissioning or integration into the
facility Building Automation System (BAS). Scheduled commissioning is
completed by a PURO Lighting representative. Units integrated into BACnet are
programmed through the BAS dashboard.
- Independently validated to kill up to 99.9% of E. coli, MRSA, Salmonella enterica, Norovirus, human coronavirus 229E, C. diff and C. auris
- Research Journal of Microbiology, 2 (1), 42-49, 2007; Mycological Research, Vol. 92, Issue 3, 1989
POWERED BY VIOLET DEFENSE® TECHNOLOGY
Broad Spectrum UV-C, UV-B and UV-A light to kill bacteria and viruses1
Ceiling or wall mounted installation to disinfect a whole room without
relocation.
Programmed manually or integrated into building automation systems through
BACnet.
Single UV Light Engine with pulsed Xenon lamp for up to a 10′ x 10′ ft
coverage area.
PRODUCT SPECIFICATIONS
UV ILLUMINATION
Light Source | Proprietary Pulsed Xenon Lamp |
---|---|
Pulse Interval | 1 UV Flash every 6 seconds |
Wavelengths | UV-C (200-280nm) |
UV-B (280-320nm) | UV-B (280-320nm) |
UV-A (320-400nm) | UV-A (320-400nm) |
Range | Up to 10′ x 10′ typical (100 sq feet) |
UV Bulb Rated Life | >2 Million UV Flashes |
Optics | Dual patented UV Light Engine with transmissive UV lens and pulsed |
Xenon UV lamp
Beam Angle| 170º
ELECTRICAL SYSTEM
Input Voltage | 110V AC |
---|---|
Max Current | 3.5 Amps |
Average Power | 60W during operation |
Power Connection | 3-prong grounded plug (-P) or 3-wire metal flexible conduit |
(-FC)
PHYSICAL
Weight | F1: 2.6 lbs, H1-DA-12: 2.1 lbs, H1–GA-24: 4 lbs |
---|---|
Housing/Finish | Brushed Aluminum |
ENVIRONMENT
Ambient Operating Temperature | 41ºF to 104ºF |
---|---|
Ambient Operating Humidity | <80%RH non-condensing |
CERTIFICATIONS
Safety| TUV Certified, tested to UL 61010-1:2012; CAN/CSA C22.2 NO.
61010-1:2012
---|---
FCC| Compliant with Part 15 Class A
RoHS| Compliant
WARRANTY
Warranty……………… 1 year
DIMENSIONS
Helo F1 (no flange)
Dimensions: 8.60″ x 5.60″ x 2.90″ Installation: wall mount, surface mount
or portable/table top use
H1-DA-12 (12″x12″ flange accessory)
Dimensions: 12″ x 12″ x 0.6″
Installation: recessed in hard lid ceiling
H1-GA-24 (24″x24″ flange
accessory)
Dimensions: 23.80″ x 23.80″ x 1.00″
Installation: drop-in grid ceiling
FOR MORE INFORMATION VISIT PUROLIGHTING.COM
CONTROL OPTIONS
Controlled though BACnet The unit can be switched on/off through the
facility BACnet. Programming is done through the Building Automation Software
system dashboard.
Manually Controlled The unit can be manually switched on/off for a single
default or commissioned cycle through a switched or a remote-controlled
outlet. Commissioning is done at the device using an Ethernet port and a
simple setup wizard.
Safety and Occupancy Sensors The redundant safety systems ensure the unit
will not activate while the room is occupied and will immediately suspend
operations if motion is detected in a previously unoccupied room. If
interrupted, the unit will resume its programmed cleaning cycle once motion is
no longer detected.
OPERATIONAL MODES
The unit can be ordered to operate in either a BACnet integrated mode,
scheduled mode, or single cycle mode. The modes are configured at the factory
and cannot be changed on the device.
BACnet Integration Mode Disinfection-on-Demand operation is programmed through
the Building Automation Software (BAS) with the Helo F1 through BACnet.
The cycle time, cycle repeat, cycle schedule and motion sensor settings and
unit on/off and initial activation are controlled through the system
dashboard.
Devices ordered with the BACnet Integration Mode must be initially activated
through the BAS software to operate.
NOTE: By default, this mode will have safety features DEACTIVATED.
Scheduled Mode The Helo F1 units are manually commissioned by a PURO Lighting
representative.
Commissioning for Disinfection-on-Demand includes cycle time, cycle repeat and
cycle schedule settings.
Single Cycle Mode The Helo F1units will run either a 10, 15, 20, 25 or 30
minute cycle once it is plugged in.
The unit will not run another cycle until the power has been disconnected and
reconnected.
Refer to the Commissioning Form on page 5 for more information on operational
modes.
INSTALLATION
Wiring
H-F1-6-P unit ships with a 6 foot cord terminated with a grounded 110V plug.
-
110V Outlet The unit can be plugged into a non-GFI outlet. If an outlet is not accessible near the fixture location, you may require a sufficiently rated, grounded extension cord or have a licensed electrician to install an outlet.
-
Switched 110V Outlet The non-GFI 110V outlet may be a switched outlet for convenience, especially in scheduled commissioned and controlled units. If a switch is not available, you may require a licensed electrician to install the switch.
-
Wi-Fi Smart Outlet The unit may also be plugged into a Wi-Fi or Bluetooth controlled smart outlet, eliminating the need to install a switch and using instead a smartphone based application to turn the unit on/off through the smart outlet.
H-F1-6-FC unit ships with a 6 foot metal flexible conduit to install per NEC and local codes.
Mounting
Drop-in Ceilings The Helo F1 with its 24″x24″ flange kit accessory is
simply dropped into a 24″x24″ or 24″x48″ drop-in ceiling.
Recessed Hard Lid Ceilings The Helo F1 has an integrated 12″x12″ flange
kit accessory enabling it to be recessed in a hard lid ceiling.
Wall Mount, Surface Mount or Portable/Table Top Use The Helo F1 has
attach points for a 100mmx100mm VESA mount for wall or surface mounting. The
unit can also be used as a portable or table top unit.
CERTIFICATIONS
This device is tested and certified by TUV to UL specifications.
Tested to be compliant with FCC Part 15 Class A.
Internal components of this device are UL Listed, UL Recognized or CE listed.
Independent lab testing has been conducted by accredited facilities, including
Microchem Laboratory, an ISO 17025 accredited facility.
NOTES
- Disinfection is a function of device run time and the distance to the UV light source.
- Operating Life is dependent on frequency and duration of disinfection cycles.
Cycle | Standard | Deep | Terminal |
---|---|---|---|
Time | 30 min/day | 1 hr/day | 2 hr/day |
Approx. Bulb Life | 18.3 years | 9.1 years | 4.6 years |
CAUTION
CAUTION — IF THE FIXTURE EXHIBITS UNDESIRABLE OPERATION (BUZZING, FLICKERING,
ETC. OR IF THE UNIT’S LED STATUS INDICATOR IS FLASHING RED), IMMEDIATELY TURN
OFF POWER AND CONTACT MANUFACTURER.
INDOOR USE ONLY.
HOW TO ORDER
Please specify components below using the letter code in bold to select the
desired options.
Family| Model| Cord Length| Cord Termination|
Controls| Wattage
---|---|---|---|---|---
H = Helo| F1 = Fixture unit with
Single UV Light Engine| 6 = 6 feet| P = Three-prong grounded plug
FC = Flex conduit| COM = Commissioned| 110 = 110V AC
Example order: H-F1-6-P-COM-110
Accessories
H1-DA-12 = Accesory for Single UV Light Engine in hard lid ceilings:
12″x12″ flange kit
H1-GA-24 = Accessory for Single UV Light Engine in drop-in celings:
24″x24″ flange kit
M-WMB-6524 = Tilt Wall Mount Bracket, Max Weight 30 lbs, VESA Patterns up
to 100×100
M-WMB-3613 = Fixed Wall Mount Bracket, Max Weight 66 lbs, VESA Patterns
up to 100×100
Commissioning Form
Name…………………….
SO Number……………….
Please choose one from the three commissioning options below.
1. Single Cycle Mode Unit will
run either a 10, 15, 20, 25 or 30 min cycle once it is powered on. The unit
will not run another cycle until the power has been disconnected and
reconnected.
2. Daily Scheduled Mode
How many cycles per day? (Indicate with a number 1-8)
Duration for each cycle? (Choose one)
Please note time of day you would like the schedule to take place. Helo
fixture should only be scheduled during times when the space will be
unoccupied.
Notes………………………………
Units can be scheduled to run up to eight separate cycles per day.
If scheduling more than once daily please designate in notes
3. Air Handling Unit Mode
Standard (15-minute run every 3 hours)
High Intensity (30-minute run every 3 hours)
For every 30 minutes of unit operation the fixture will automatically shut
down for 15 minutes to ensure proper cooling and will continue after 15
minutes.
What time zone will the unit(s) be operated in?
Eastern
Central
Mountain
Pacific
Alaska
Hawaii
Full Name……………………………
Date………………………………………
© Copyright 2020 PURO. All Rights Reserved. PURO, the PURO logo, Helo and
Sentry are trademarks of PURO.
All other trademarks are the property of their respective owners.
Specifications are subject to change without notice. This document is for
informational purposes only.