Master ZULA H HZ61100 Manual
- June 8, 2024
- MASTER
Table of Contents
- Master
- ZULA H
- SKU: HZ61100
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Parameter no. 1In-wall Switch Type for Load ( ) to control
- Parameter 11: Parameter no. 11 – Turn Load( ) Off Automatically with
- Parameter 12: Parameter no. 12 – Turn Load( ) On Automatically with Timer
- Parameter 21: Parameter no. 21 – Enable/Disable the Double click function
- Parameter 30: Parameter no. 30 – Restore on/off status for load after
- Parameter 40: Parameter no. 40Watt Power Consumption Reporting Threshold
- Parameter 42: Parameter no. 42Watt Power Consumption Reporting Time
- Parameter 5: Parameter no. 5Working mode
- Parameter 60: Parameter no. 60Minimum dimming value
- Parameter 61: Parameter no. 61Maximum dimming value
- Parameter 65: Parameter no. 65Dimming time when key pressed (soft on/off)
- Parameter 66: Parameter no. 66Dimming time when key holdwag
- Parameter 67: Parameter no. 67Ignore start level
- Parameter 68: Parameter no. 68Dimming duration for associations
- Parameter 70: Parameter no. 70 – Overload safety switch
- Parameter 71: Parameter no. 71Calibration trigger
- Parameter 72: Parameter no. 72Calibration status (read only)
- Parameter 73: Parameter no. 73Alarm/Notification events
- Parameter 74: Parameter no. 74Alarm/Notification time interval (dependant
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Master
ZULA H
SKU: HZ61100
Quickstart
This is a
secure
Light Dimmer
for
.
To run this device please connect it to your mains power supply.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
Zula is a MOSFET-switching light device that supports the control of low- voltage halogen lamps with electronic transformers, dimmable compact fluorescent lights, and dimmable LED bulbs. It measures power consumption of the connected device. It supports momentary switches (by default) and toggle switches. It can work with or without the neutral line. Master Zula allows the easiest and quickest installation in all types of flush mounting boxes. Master Zula also acts as a Z-Waverepeater to improve the range and stability of the Z-Wavenetwork.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 1| (Lifeline group) Supports the following command classes:Device Reset
Locally: triggered upon requestMeter Report: triggered according to
Configuration parameters 40 and 42Notification Report: triggered on
overload/over temperatureSwitch Multilevel Report: triggered upon request or
according to Configuration parameters 11 and 12 (note that this command class
is active only in dimmer mode)Switch Binary Report: triggered upon request or
according to Configuration parameters 11 and 12 (note that this command class
is active only in switch mode)
---|---|---
2| 16| Supports the following command classes:Basic set: triggered at change
of input and reflecting its state
3| 16| Supports the following command classes:Start/Stop Level Change:
triggered upon holding and releasing the switch connected to terminal I
4| 16| Supports the following command classes:Switch Multilevel Set: triggered
at change of output and reflecting its state
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Parameter no. 1In-wall Switch Type for Load ( ) to control
terminal I
With this parameter, you can select between momentary and on/off toggle
switch types.Values (size is 1-byte dec):default value 00 – momentary switch1
– on/off toggle switch
Size: 1 Byte, Default Value: 0
SettingDescription
0 | momentary switch |
---|---|
1 | on/off toggle switch |
Parameter 11: Parameter no. 11 – Turn Load( ) Off Automatically with
Timer
If Load ( ) is ON, you can schedule it to turn OFF automatically after a
period of time defined in this parameter. The timer is reset to zero each time
the device receives an ON or OFF command, either remotely (from the gateway
(hub) or associated device) or locally from the switch.Values (size is 2-byte
dec):default value 00 – Auto OFF Disabled 1 – 32536 = 1 – 32536 seconds – Auto
OFF timer enabled for a given amount of seconds
Size: 2 Byte, Default Value: 0
SettingDescription
0 | Auto OFF Disabled |
---|---|
1 – 32536 | 1 – 32536 seconds – Auto OFF timer enabled for a given amount of |
seconds
Parameter 12: Parameter no. 12 – Turn Load( ) On Automatically with Timer
If Load ( ) is OFF, you can schedule it to turn ON automatically after a
period defined in this parameter. The timer is reset to zero each time the
device receives an OFF or ON command, either remotely (from the gateway (hub)
or associated device) or locally from the switch.Values (size is 2-byte
dec):default value 00 – Auto ON Disabled 1 – 32536 = 1 – 32536 seconds – Auto
ON timer enabled for a given amount of seconds
Size: 2 Byte, Default Value: 0
SettingDescription
0 | Auto ON Disabled |
---|---|
1 – 32536 | 1 – 32536 seconds – Auto ON timer enabled for a given amount of |
seconds
Parameter 21: Parameter no. 21 – Enable/Disable the Double click function
If the Double click function is enabled, a fast double click on the
momentary switch sets the dimming level to the maximum dimming value. Values
(size is 1-byte dec):default value 0 0 – double click disabled 1 – double
click enabled
Size: 1 Byte, Default Value: 0
SettingDescription
0 | double click disabled |
---|---|
1 | double click enabled |
Parameter 30: Parameter no. 30 – Restore on/off status for load after
power failure
This parameter determines if on/off status is saved and restored for the
load after power failure.Values (size is 1-byte dec):default value 00 – Device
saves last on/off status and restores it after a power failure.1 – Device does
not save on/off status and does not restore it after a power failure, it
remains off.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Device saves last on/off status and restores it after a power failure. |
---|---|
1 | Device does not save on/off status and does not restore it after a power |
failure, it remains off.
Parameter 40: Parameter no. 40Watt Power Consumption Reporting Threshold
for Load
Choose by how much the power consumption needs to increase or decrease to be
reported. Values correspond to percentages so if 10 is set (by default), the
device will report any power consumption changes of 10 % or more compared to
the last reading. Values (size is 1-byte dec):default value 100 – Power
consumption reporting disabled 1 – 100 = 1 % – 100 % Power consumption
reporting enabled. New value is reported only when Wattage in real time
changes by more than the percentage value set in this parameter compared to
the previous Wattage reading, starting at 1 % (the lowest value possible).
NOTE: The power consumption needs to increase or decrease by at least 2 Watts
to be reported, regardless of percentage set in this parameter.
Size: 1 Byte, Default Value: 10
SettingDescription
0 | Power consumption reporting disabled |
---|---|
1 – 100 | = 1 % – 100 % Power consumption reporting enabled. New value is |
reported only when Wattage in real time changes by more than the percentage value set in this parameter compared to the previous Wattage reading, starting at 1 % (the lowest value possible).
Parameter 42: Parameter no. 42Watt Power Consumption Reporting Time
Threshold for Load
Set value refers to the time interval with which power consumption in Watts
is reported (0 – 32767 seconds). If 300 is entered, energy consumption reports
will be sent to the gateway (hub) every 300 seconds (5 minutes) if there was a
change compared from the last report.Values (size is 2-byte dec): default
value 0 0 – Power consumption reporting on time interval disabled 30 – 32767=
30 – 32767seconds. Power consumption reporting enabled. Report is sent
according to time interval (value) set here. NOTE: Values from 1 to 29 are
ignored by device due to standard recommendation.NOTE: The report will be send
only if there was a change compared to the last report.
Size: 2 Byte, Default Value: 0
SettingDescription
0 | Power consumption reporting on time interval disabled |
---|---|
30 – 32767 | 30 – 32767seconds. Power consumption reporting enabled. Report is |
sent according to time interval (value) set here
Parameter 5: Parameter no. 5Working mode
With this parameter, you can change the device presentation on the user
interface.Values (size is 1-byte dec):default value 00 – Dimmer mode1 – Switch
modeNOTE: After parameter change, first exclude the device (without setting
parameters to default value) then wait at least 30 seconds before re-
inclusion.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | Dimmer mode |
---|---|
1 | Switch mode |
Parameter 60: Parameter no. 60Minimum dimming value
The value set in this parameter determines the minimum dimming value (the
lowest value which can be set on the device, when, for example, dimming lights
with wall switch or slider in the GUI (Gateway – hub)).Values (size is 1-byte
dec):default value 15 = 15 % (minimum dimming value)0 – 98 = 1 % – 98 %, step
is 1 %. Minimum dimming value is set by entering a value. NOTE: The minimum
level may not be higher than the maximum level!
Size: 1 Byte, Default Value: 15
SettingDescription
0 – 98| 1 % – 98 %, step is 1 %. Minimum dimming value is set by entering a
value.
---|---
Parameter 61: Parameter no. 61Maximum dimming value
The value set in this parameter determines the maximum dimming value (the
highest value which can be set on the device, when, for example, dimming
lights with wall switch or slider in the GUI (Gateway – hub)).Values (size is
1-byte dec):default value 99 = 99 % (Maximum dimming value)1 – 99 = 2 % – 99
%, step is 1 %. Maximum dimming value is set by entering a value. NOTE: The
maximum level may not be lower than the minimum level!
Size: 1 Byte, Default Value: 99
SettingDescription
1 – 99| 2 % – 99 %, step is 1 %. Maximum dimming value is set by entering a
value
---|---
Parameter 65: Parameter no. 65Dimming time when key pressed (soft on/off)
Choose the time during which the device will move between the min. and max.
dimming values by a short press of the momentary switch connected to terminal
I. Values (size is 1-byte dec):default value 1 = 1 s1 – 127 = 1 seconds- 127
seconds, step is 1 second
Size: 1 Byte, Default Value: 1
SettingDescription
1 – 127 | 1 seconds- 127 seconds, step is 1 second |
---|
Parameter 66: Parameter no. 66Dimming time when key holdwag
Choose the time during which the Dimmer will move between the min. and max.
dimming values during a continuous press of the momentary switch connected to
terminal I, by an associated device or through the UI controls (BasicSet,
SwitchMultilevelSet). Values (size is 2-byte dec):default value 3 = 3 seconds
1-127 = 1 second127 seconds128253 = 1 minute126 minutes
Size: 2 Byte, Default Value: 3
SettingDescription
1 – 127 | 1 second127 seconds |
---|---|
128 – 253 | 1 minute126 minutes |
Parameter 67: Parameter no. 67Ignore start level
Choose whether the device should use (or disregard) the start dimming level
value. If the device is configured to use the start level, it should start the
dimming process from the currently set dimming level. This parameter is used
with association group 3.Values (size is 1-byte dec): default value 0 0use the
start level value1 – ignore the start level value NOTE: Parameter is valid
only in Dimmer mode. In Switch mode the parameter has no effect.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | use the start level value |
---|---|
1 | ignore the start level value |
Parameter 68: Parameter no. 68Dimming duration for associations
Choose the time during which the device will transition from the current
value to the new target value. This parameter applies to the association group
3.Values (size is 1-byte dec):default value 0 (dimming duration according to
parameter 66) 1 – 127 (from 1 to 127 seconds) NOTE: Parameter is valid only in
Dimmer mode. In Switch mode the parameter has no effect.
Size: 1 Byte, Default Value: 0
SettingDescription
1 – 127 | (from 1 to 127 seconds) |
---|
Parameter 70: Parameter no. 70 – Overload safety switch
_The function allows for turning off the controlled device in case of
exceeding the defined power for more than 5 s. Controlled device can be turned
back on by terminal I or sending a control frame. Values (size is 2-byte
dec):default value 2001200 = 1 W200 W0 = function not active NOTE: This
functionality is not an overload safety protection, please check the technical
specifications chapter for more details.In case of overload the following
message will be send towards the controller:COMMAND_CLASS_NOTIFICATIONV5The
Alarm V1 type field set to 0x00Notification Type 0x08 and 0x08 (Overload
detected)
Size: 2 Byte, Default Value: 200
SettingDescription
0 | function not active |
---|---|
1 – 200 | 1 W200 W |
Parameter 71: Parameter no. 71Calibration trigger
Choose when will be the calibration procedure triggered. Values (size is
1-byte dec):default value 0 – calibration done after power cycle if module is
excluded1calibration done after power cycle regardless of inclusion
status2force calibration. Calibration will start immediatelyNOTE: For
additional information check ZULA CALIBRATION under chapter 2.
Size: 1 Byte, Default Value: 0
SettingDescription
1 | calibration done after power cycle regardless of inclusion status |
---|---|
2 | force calibration. Calibration will start immediately |
Parameter 72: Parameter no. 72Calibration status (read only)
Whit this parameter you can check the calibration status. Values (size is
1-byte dec):default value 2calibration failed1calibration was
successful2calibration failed
Size: 1 Byte, Default Value: 2
SettingDescription
1 | calibration was successful |
---|---|
2 | calibration failed |
Parameter 73: Parameter no. 73Alarm/Notification events
This parameter defines the module behaviour in case it receives any
Alarm/Notification events.Values (size is 1-byte dec):default value 0function
not active1turn ON2turn OFF3start blinking (output turns 1 s ON, and 1 s OFF)
NOTE: When value 3 is selected the default time interval of the blinking is 10
minutes. It can be stopped with a button press or sending a control frame. To
adjust the time interval please refer to parameter 74Alarm/Notification time
interval.
Size: 1 Byte, Default Value: 0
SettingDescription
1 | turn ON |
---|---|
2 | turn OFF |
3 | start blinking (output turns 1 s ON, and 1 s OFF) |
Parameter 74: Parameter no. 74Alarm/Notification time interval (dependant
on parameter 73)
This parameter defines the time interval of the blinking state, once the
module receives an alarm/notification event. Minimum step increase is 1
minute.Values (size is 1-byte dec):default value 10 = 10 minutes1125 = 1 -125
minutes NOTE: This parameter does not have any effect if parameter 73 is not
set to value 3.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 125 | 1 -125 minutes |
---|
Technical Data
Hardware Platform | ZM5101 |
---|---|
Device Type | Light Dimmer Switch |
Network Operation | Always On Slave |
Firmware Version | HW: 2 FW: 20.00:20.00 |
Z-Wave Version | 6.71.03 |
Certification ID | ZC10-21127066 |
Z-Wave Product Id | 0x0440.0x0004.0x0081 |
Switch Type | Decorator Paddle Push |
Color | Antique Brass |
Communications Protocol | Manufacturer Proprietary Protocol |
Electric Load Type | |
Neutral Wire Required | ok |
Outdoor Use | ok |
Security V2 | S2_UNAUTHENTICATED ,S2_AUTHENTICATED |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Supported Command Classes
- Association Grp Info V2
- Association V2
- Basic
- Configuration
- Device Reset Locally
- Manufacturer Specific V2
- Meter V4
- Notification V5
- Powerlevel
- Security
- Security 2
- Supervision
- Switch Multilevel V3
- Transport Service V2
- Version V2
- Zwaveplus Info V2
Controlled Command Classes
- Basic
- Switch Multilevel V3
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>