Simon S100 Master Roller Dimmer iO 10002021-13X Manual

June 8, 2024
Simon

Simon

S100 Master Roller Dimmer iO

SKU: 10002021-13X

Quickstart

This is a ****

Wall Controller
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
When the pushbutton is released after a press of (2sec<T<10sec) the device will send a NIF to include from Z-Wave network or perform an association with other Z-Wave device.Central LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.This process does not perform a default reset of configurations.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Master Dimmer iO is ready to operate with Z-Wave controllers and configured to be managed by Simon100 iO APP using the HUB plug iO for getting a better user experience. allowing the control of other Z-Wave devices via Basic Set/Get commands.Available colors Black and White.visit http://www.simon.es/simon100/ to learn more about Simon 100 iO.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

When the pushbutton is released after a press of (30sec<T) the device will perform a factory default values operation, excluding it from network and reset the configuration parameters.Main LED will perform 1 Blink with 5 sec.Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

When the pushbutton is released after a press of (2sec<T<10sec) the device will send a NIF to include from Z-Wave network or perform an association with other Z-Wave device.Central LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.This process does not perform a default reset of configurations.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.

Exclusion

When the pushbutton is released after a press of (2sec<T<10sec) the device will send a NIF to exclude from Z-Wave network or perform an association with other Z-Wave device.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.This process does not perform a default reset of configurations.Main LED will Blink with 0,3 sec period to inform that NIF can be send after release of pushbutton.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 3 Z-Wave Plus Lifeline
2 20 ctrl. This group is used to add the devices to be controlled by Master

Roller blind. Device sends Basic Sets and Gets, and Manufacturer specific Gets, Configuration Gets and Sets when manual association is being performed over Simon devices.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Association LED

Activates the Central LED. Configuration Used by Masters iO in order to identify the devices associated to their Group2 during manual association process.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Turns Central LED OFF
1 – 255 Turns Central LED ON

Parameter 12: Behavior of LED in Repose

Sets the Central LED to 20% in order to find the device at night.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Central LED OFF
1 – 255 Central LED ON at 20percent

Parameter 13: Lock Input

Locks the local control of associated devices and controller. This configuration does not modifies the control via Z-Wave, where if a Set is received it will retransmitted to all group 2 associated nodes
Size: 1 Byte, Default Value: 0

SettingDescription

0 Local control is available
1 – 255 Local control is locked

Parameter 15: Reset Default

Write only parameter used to restore configurations or perform a completely restore default.
Size: 2 Byte, Default Value: 0

SettingDescription

17170 Configuration values are restored
39015 Factory reset

Parameter 18: Lock Manual Association

Enables or disables the manual association process.
Size: 1 Byte, Default Value: 0

SettingDescription

0| Hold press of 10sec to 30sec starts manual association of devices to group 2
---|---
1 – 255| Hold press of 10sec to 30sec sends a Node Info

Parameter 19: Press Action

Defines the function performed by the device when keypad is pressed
Size: 1 Byte, Default Value: 5

SettingDescription

0| Short press switches between the last power on and off (depending on the status of the associated control) by sending a Basic Set to 0x00 or 0xFF to the associated nodes.
---|---
1| Short press activates those associated by sending Basic Set to 0xFF
2| Short press deactivates those associated by sending Basic Set to 0x00
4| Short Press always turn on the associated nodes by sending a Basic Set to 0xFF. Press from 2sec to 10sec always turns off the associated nodes by sending a Basic Set to 0x00
5| When Short press Master inverts the load state via Basic Set, When the slider is enabled and load is ON, Multilevel Sets are sent to modify the dimming value.

Parameter 20: Identify

Write only value that performs a fast blink on Central LED during 5 seconds in order to identify the device when it is installed in a multiple frame
Size: 1 Byte, Default Value: 0

SettingDescription

1 – 255 Central LED performs a fast blink

Parameter 21: Device State

Configuration used to know the device state and last active dimming value in case of act retransmitting values different from 0 or 0xFF. This value is represented in Hexadecimal. Byte 0 informs about Load State (0 load is OFF and 1 load is ON) Byte 1 informs about Last active load value (0-0x63 or 0xFF)
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 99 Load is OFF or sunblind is stopped with diming value or position x
256 – 355 Load is ON or sunblind is going DOWN with diming value or position

x

Parameter 27: Lock Hold Press

Locks the major part of Hold press effects in order to avoid undesired Z-Wave changes, associations or restores Default. 0xFF Hold Press from 2sec to 10 sec does not performs a Node info. Hold Press of 10 to 30 does not performs a manual association process. Hold press of 30sec restores configuration except Lock Hold Press, and sends a Node info in order to add or remove from Z-Wave Network
Size: 1 Byte, Default Value: 0

SettingDescription

0 Hold press is available
1 – 255 Hold Press is Locked

Parameter 28: Consult on Touch

This configuration has only effects when there is only 1 associated node in group 2. Is used to set if Master has to be always informed about the controlled device state or it is consulted when user touches the keypad.
Size: 1 Byte, Default Value: 255

SettingDescription

0 Device must receive reports about controlled device state
1 – 255 Device consults the device state once keypad detects touch

Parameter 29: Send Central Scene

Disables the sending of Central Scene Notifications to avoid perform 2 actions at same time (Central Scene action and Group 2 action).
Size: 1 Byte, Default Value: 255

SettingDescription

0 Device does not sends Central Scene Notifications
1 – 255 Device sends Central Scene Notifications is no devices are added to

group 2

Technical Data

Hardware Platform ZM5202
Device Type Wall Controller
Network Operation Always On Slave
Firmware Version HW: 1 FW: 4.24:79.50
Z-Wave Version 6.51.07
Certification ID ZC10-18026013
Z-Wave Product Id 0x0267.0x0008.0x0000
Neutral Wire Required ok
Firmware Updatable Updatable by Professional/Technician
Z-Wave Scene Type Central Scene
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info V3
  • Association V2
  • Basic
  • Central Scene V3
  • Configuration V2
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Powerlevel
  • Switch Multilevel V3
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Association V2
  • Basic
  • Configuration V2
  • Manufacturer Specific V2
  • Switch Multilevel V3

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals