Bard QCRV-F Commercial Room Ventilator with Spring Return and Exhaust User Manual
- June 8, 2024
- Bard
Table of Contents
Bard QCRV-F Commercial Room Ventilator with Spring Return and Exhaust User Manual
QCRV-F Features
- Exhaust air damper – built in with positive closed position. Provides exhaust air capability to prevent pressurization of tight buildings.
- Actuator motor – 24 volt, power open, spring return with built-in torque limiting switch.
Electrical shock hazard.
Disconnect remote electrical power supply or supplies before servicing.
Failure to do so could result in electric shock or death.
Exposed moving parts.
Disconnect all electrical power before servicing.
Failure to do so can result in severe injury or amputation.
Sharp metallic edges.
Take care and wear appropriate protective devices to avoid accidental contact
with sharp edges.
Failure to do so can result in personal injury
Q-TEC Commercial Room Ventilator Model Nomenclature
Description
Commercial room ventilator QCRV-F is designed to be used with specific Bard models as designated on the front page of this manual.
The QCRV-F ventilator is an electromechanical vent system designed to provide fresh air to meet indoor air quality standards.
Commercial room ventilator QCRV-F is an internally mounted damper with exhaust designed to provide up to 50% fresh air. The damper blade is powered by a 24 VAC motor with spring return on power loss. The damper is powered open anytime A is energized. Blade stop screws are located under the fresh air blade and will provide 10 different airflow settings.
When installed in the models listed on the front page, the QCRV-F provides built-in exhaust provisions. When the damper blade opens to bring fresh air in, the damper also opens an exhaust relief. The exhaust air will flow into the condenser section of the unit. The condenser fan will help draw exhaust air out when it is operating with compressor in cooling or heat pump mode.
Application
The amount of outside fresh air brought into the structure is dependent on the supply and return duct static pressure present in the duct system. Refer to Graphs 1-5 on pages 9-11 for ventilation air that will be supplied at different blade settings and duct static pressures. For duct-free applications with return air filter grilles and supply grilles, use 0.00 supply air static pressure.
FIGURE 1
Programmable Thermostat Connections for QCRV-F with Heat Pumps
FIGURE 2
Non-Programmable Thermostat Connections for QCRV-F with Heat Pumps
FIGURE 3
Programmable Thermostat Connections for QCRV-F with Air Conditioners
FIGURE 4
Non-Programmable Thermostat Connections for QCRV-F with Air Conditioners
Blade Adjustment for Desired Ventilation Air
The amount of ventilation air supplied by the commercial room ventilator is dependant on four factors.
- Return air duct static pressure drop.
- Supply air duct static pressure drop.
- Indoor blower motor speed.
- Damper blade open position setting.
Refer to the appropriate graph on the following pages to determine the blade setting needed for required airflow. Adjust blade stop screws accordingly (see Figure 5).
NOTE : Blade setting shipped from factory in #3 position.
This will provide 100-150 CFM fresh air.
Balanced ClimateTM Mode
Balanced Climate mode can be used for duct free and ducted applications below 0.2″ W.C. ESP total static.
If Balanced Climate mode is enabled, blade stop screw positions will need to
be adjusted to allow approximately 28% more outdoor air to maintain
minimum ventilation requirements.
FIGURE 5
Blade Adjustment for Desired Ventilation Air
GRAPH 1
Q24H4 CRV Ventilation Delivery
GRAPH 2
Q30H4 CRV Ventilation Delivery
GRAPH 3
Q36A4 and Q36H4 CRV Ventilation Delivery
GRAPH 4
Q42A4 and Q43H4 CRV Ventilation Delivery
GRAPH 5
Q48A4 and Q48H4 CRV Ventilation Delivery
FIGURE 6
Call for Ventilation With or Without Compressor Operation
FIGURE 7
Call for Compressor or Fan Only with Ventilation Off
FIGURE 8
Wiring Diagram
Manual 2100-741B
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>